0% found this document useful (0 votes)
51 views1 page

120/240 VAC 75 W Transformer 639A0130H02

The document provides a setup procedure for a Quantum HD Unity liquid injection system with an EZ Cool LIOC to control compressor discharge temperature. The procedure involves logging into the Unity, enabling liquid injection and oil cooling, setting valve and temperature control setpoints, and calibrating the analog output channel to send a 4-20 mA signal.

Uploaded by

Pedro Bancayan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views1 page

120/240 VAC 75 W Transformer 639A0130H02

The document provides a setup procedure for a Quantum HD Unity liquid injection system with an EZ Cool LIOC to control compressor discharge temperature. The procedure involves logging into the Unity, enabling liquid injection and oil cooling, setting valve and temperature control setpoints, and calibrating the analog output channel to send a 4-20 mA signal.

Uploaded by

Pedro Bancayan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Setup Procedure

Quantum HD Unity Liquid Injection with Hansen motorized valve.


EZ Cool LIOC is used to control the compressor discharge temperature and subsequently the oil and oil separator temperatures.
•Log into the Quantum HD Unity as a Service User.
•Go to Menu>Package>Liquid Injection LIOC.
•Enable Liquid Injection Oil Cooling.
•Set the Valve Type setpoint to Analog Modulating.
•Set the ON & OFF Solenoid Control setpoints for your application. Default setpoints are On 122°F, Off 121°F.
•Set the EZ Cool PI Control setpoints for your application. Default setpoints are Control Setpoint 160°F, PB 25°F, IT 30 Sec,
120/240 VAC 75 W transformer High Limit 100%, Low Limit 0%, I/O Board 1, I/O Output Channel 4, Port Multiplier 1, Analog board 1, I/O Output Channel 4, Port Multiplier 1
•Adjustments may be needed to these setpoints for your application.
639A0130H02 •Calibrate the analog output channel for the 4-20 mA signal. Refer to the Quantum HD Unity Operation manual for calibration instructions.