Industrial Dehumidifier Guide
Industrial Dehumidifier Guide
This application note will highlight the primary sources of INDUSTRIAL FACILITY
moisture in industrial facilities. Different methods of solving HEATING
COIL
moisture problems are outlined along with formulas for
CONDENSATION / HUMID ENVIRONMENT
estimating the moisture content. A questionnaire is incorporated
WARM, MOIST
to obtain the minimum information required for proper sizing of OUTSIDE AIR
EXHAUST AIR
SUPPLY
dehumidification equipment.
D ry Air
Quality and productivity are an ever increasing concern for
Figure 1 - Make-up Air Method
today’s businesses. The effect moisture laden air has on these
two concerns is becoming more important as industry strives for Using compression to dry air is effective when small quantities
tighter operational tolerances. Manufacturers must insure are needed. When air is compressed, the dew point is raised,
that products maintain specific quality specifications and that is, the temperature at which water vapor will condense is
efficiency is maintained throughout the four seasons. raised. This method has high installation and operational costs
and is most common when less than 100cfm of dry air is
There are many commercial and industrial applications which
required.
require dry air. To eliminate the moisture problem at a reasonable
cost, the specifier needs to know how much moisture is present, BYPASS DAMPER
how did it get in the facility and how to select the proper dehu- CONDENSER COIL
DRY
midification system. WARM
AIR
BLOWER
COMPRESSOR
M ethods of Drying Air
RECEIVER TANK
MOIST
WARM
There are several methods of drying air. Each method has AIR
• Compression
• Refrigerated dehumidification Figure 2 - Refrigeration Dehumidifier Schematic
• Desiccant dehumidification
Refrigeration dehumidifiers reduce the moisture in the air by
The fist method uses the principle of dilution, removing a passing the air over a cold surface, removing the moisture by
portion of the moisture laden air from a space and replacing it condensation. A detailed discussion on this technique is
with drier air. The net result is a lower average moisture content. explained in Desert Aire Technical Bulletin #1. This method is
This method is relatively inexpensive to install, but relies on the effective for desired conditions down to 45 percent RH for stan-
fact that drier air is available. Since the most common source is dard applications. Specially designed systems can achieve
outside make up air, this method is difficult to apply in summer dew points as low as 35°F. This method has moderate capital
months and expensive to operate in winter due to heating costs. costs and can recover much of the latent energy thus offsetting
operating costs.
REGENERATED
AIR OUT effect on the vapor migration. Desert Aire has used some basic
models to make assumptions to estimate moisture infiltration
and permeation.
Infiltration and permeation are often considered the same thing. The rate of infiltration is a function of the magnitude of
Infiltration is the movement of water vapor through cracks, joints imbalance between the outside absolute humidity and that
and seals. Permeation is the migration of water vapor through inside the conditioned space. The greater the difference, the
materials such as brick and wood. One of the physical laws of greater the driving force to make the vapor pressures equal.
nature states that all conditions must be balanced. In the case of The migration factor compensates for this influence.
water vapor the partial pressure of the water vapor must be the
The ∆GR (grain/lb) deviation must be obtained from the
same on either side of a barrier. For this reason water vapor will
Psychrometric chart. By locating the outside and inside
migrate through brick walls to get to the less humid side. The
conditions on the chart an absolute humidity in grains/lb can
rate of migration in an unbalanced situation exceeds the rate of
be obtained. The formula uses the difference in grain/lb
air through cracks and seals and will in effect find a path to
between these two conditions. Refer to Table 2 and 3 for
attempt to balance partial pressures.
humidity values for specific locations and inside design
Moisture load in a space due to infiltration and permeation is not conditions. For other values the Psychrometric chart must
easily measured. Factors such as the actual moisture deviation, be utilized. Please refer to Desert Aire Technical Bulletin
materials of construction, vapor barrier and room size all have an Number 3 if assistance is required to read the chart.
APPLICATION NOTE 11
Industrial Dehumidifier Sizing
Another primary factor is the amount of moisture that is allowed into account since it will vary depending on the location of the
to permeate through the walls, floor and roof. The construction opening with respect to the wind source. Local weather stations
factor takes into account the effect good vapor barriers and can provide details on the normal prevailing direction and speed.
construction materials will have on the moisture migration. However, a guideline is 12 CFM of outside air per square feet of
Table 4 gives factors for common construction materials. This opening.The amount of air can be estimated by the following
factor will vary between 0.3 and 1.0. A composite wall must be formula.
modeled and a factor estimated.
AREA x OPEN x ∆GR x 12
LB/HR =
RELATIVE HUMIDITY 7000 x 13.5
40% 50% 60% 70%
Where:
55 25* 32* 40* 45
AREA = Surface area of opening ( Sq. Ft.)
60 31* 39* 46 54
65 37* 46 55 65 OPEN = Minutes area is open per hour
DRY BULB
D oor Openings CO
Stockton
Denver
72
78
Detroit
Flint
114
117
OR
Eugene
Portland
73
72 WI
Green Bay
Madison
117
115
MI
CT Hartford 111 Grand Rapids 116 Erie 114 Milwaukee 115
DC Washington Nat’l 129 Sault St. Marie 102 Philadelphia 124 WV Charleston 120
Another source of moisture is the opening of DE Wilmington 121 Duluth 98
PA
Pittsburgh 116
CANADA
Daytona Beach 137 MN Rochester 120 Scranton 114
doors and windows to the conditioned space or Fort Myers 143 St. Paul 114 RI Providence 114 AL Calgary 69
Jacksonville 134 Kansas City 126 Charleston 136 BC Vancouver 76
other openings such as conveyor passages. In Miami 137
MO
St. Louis 132
SC
Columbia 122 MN Winnipeg 97
FL
Orlando 136 Jackson 136 SD Sioux Falls 119 NB Saint John 87
these cases, the amount of moisture is directly Pensacola 143
MS
Meridian 127 Bristol 118 NF St. John’s 89
MT
proportional to the frequency of the opening, the Tallahassee
Tampa
136
136
Billings
Cape Hatteras
70
142 TN
Chattanooga
Knoxville
126
124
NS Halifax
Ottawa
100
101
In the case of, open water tanks, the evaporation rate can be CFM = Volume of outside air introduced
calculated with the following equation.
∆GR = The deviation from the outside to the
desired conditions (grains/LB)
LB/HR = 0.1 x AREA x (VPH2O - VPAIR)
60 = Conversion factor for min/hr
Area = Surface area of water (square feet). 7000 = Conversion factor for GR/LB