Upper Attachments: B3199R - Ceiling Flange B3199RCT - Ceiling Flange Dura-Copper Coated
Upper Attachments: B3199R - Ceiling Flange B3199RCT - Ceiling Flange Dura-Copper Coated
B3199RCT B3199R
Attachments
Order By: Part number, rod size and finish
Upper
US Patent #5,702,077
Part No. Pipe Size A B C Hole Dia. D Thread Size Design Load Approx. Wt./100
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) E Lbs. (kN) Lbs. (kg)
78-3/8 1/2" - 2” (15 - 60) 3" (76.2) 21/8" (54.0) 11/8" (28.6) 5/16" (7.9) 3/8"-16 150 (0.67) 15 (6.8)
-- Consult Factory For Data
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Pipe Hangers & Supports 216 Eaton
Upper Attachments
B3060L - Light Duty Angle Clip
Size Range: 3/8"-16 rod
Material: Steel (Stainless steel available) 7 Ga.
9/32" Dia (4.5)
Function: Designed for attaching 3/8”-16 hanger rod to the (7.1)
2 Holes 13/16" (20.6)
side of beams or walls.
7/16" Dia
Approvals: Conforms to Federal Specification WW-H-171E &
(11.1)
A-A-1192A, Type 35 and Manufacturers Standardization Society 2 Holes
17/8"
ANSI/MSS SP-69 & SP-58, Type 34. (47.6)
Finish: Plain or Electro-Galvanized 1/2"
(12.7)
Order By: number and finish. 15/16"
(33.3) 11/4"
Design Load: 300 Lbs. (1.33kN) (31.7)
Design Load: 500 Lbs. (2.22 kN) when installed in either direction.
C A
Weight: Approx. Wt./100 - 49 Lbs. (22.2 kg)
Rod Size A B C Hole 1 Hole 2 Hole 3 Max. Rec. Load Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3070-3/8x1/2 3/8"-16 x 1/2"-13 2" (50.8) 13/16" (20.6) 2" (50.8) 9/16" (14.3) 7/16" (11.1) 5/16" (7.9) 700 (3.11) 35 (15.9)
B3070-1/2x1/2 1/2"-13 x 1/2"-13 2" (50.8) 3/4" (19.0) 2" (50.8) 9/16" (14.3) 9/16" (14.3) 5/16" (7.9) 700 (3.11) 34 (15.4)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Eaton 217 B-Line series Pipe Hangers & Supports
Upper Attachments
B3060 - Side Beam Angle Clip
T
Size Range: 3/8"-16 and 7/8"-9 rod
Material: Steel (Stainless steel available) B
A
Function: Designed for attaching a hanger rod to the side of beams or walls. Hole Size
D
Approvals: Conforms to Federal Specification WW-H-171E & A-A-1192A,
Type 35 and Manufacturers Standardization Society ANSI/MSS SP-69 &
SP-58, Type 34.
C D
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials. B
Order By: Part number and finish.
B3060-3/8 7/16" (11.1) 23/16" (55.6) 2" (50.8) 11/4" (31.7) 1/4" (6.3) 305 (1.35) 53 (24.0)
B3060-1/2 9/16" (14.3) 23/16" (55.6) 2" (50.8) 11/4" (31.7) 1/4" (6.3) 565 (2.51) 51 (23.1)
B3060-5/8 11/16" (17.5) 23/16" (55.6) 2" (50.8) 11/4" (31.7) 1/4" (6.3) 909 (4.02) 48 (21.8)
B3060-3/4 13/16" (20.6) 3" (76.2) 3" (76.2) 13/4" (44.4) 3/8" (9.5) 1355 (6.03) 169 (74.8)
B3060-7/8 15/16" (23.8) 4" (101.6) 4" (101.6) 21/2" (63.5) 3/8" (9.5) 1870 (8.32) 312 (141.5)
TOLCO™ Fig. 51NFPA - Side Beam Bracket for NFPA Rod & Fastener Sizing
Hole 1
Size Range: 3/8"-16 thru 1/2"-13 rod, 1/2" (15mm) thru 8" pipe (200mm) B
Material: Steel
Hole 2
Function: Recommended for attaching hanger rod to side of beams or walls.
Designed to accommodate current rod schedule and fastener requirements per A
National Fire Protection Association (NFPA) Pamphlet 13.
B
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL), and Factory Mutual Engineering approved.
Attachments
Finish: Plain. Contact customer service for alternative finishes
Upper
and materials. A C
Order By: Part number, rod size and finish
51NFPA-3/8x3/8 1/2" - 2” (15 - 60) 3/8"-16 2" (50.8) 3/4" (19.0) 2" (50.8) 7/16" (11.1) 7/16" (11.1)
51NFPA-3/8x1/2 21/2" - 4” (65 - 100) 3/8"-16 2" (50.8) 3/4" (19.0) 2" (50.8) 9/16" (14.3) 7/16" (11.1)
51NFPA-1/2x1/2 5" - 6” (125 - 150) 1/2"-13 21/2" (63.5) 3/4" (19.0) 21/2" (63.5) 9/16" (14.3) 9/16" (14.3)
51NFPA-1/2x5/8 8” (200) 1/2"-13 21/2" (63.5) 3/4" (19.0) 21/2" (63.5) 11/16" (17.5) 9/16" (14.3)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Pipe Hangers & Supports 218 Eaton
Upper Attachments
TOLCO™ Fig. 50 - Side Beam Bracket for NFPA Rod & Fastener Sizing H
B
Size Range: 3/8"-16 thru 7/8"-9 rod
H
Material: Steel
Function: Recommended for attaching hanger rod to side of beams A
or walls. B
Approvals: Factory Mutual Engineering approved (FM).
Finish: Plain. Contact customer service for alternative finishes
and materials.
Order By: Part number, rod size and finish A C
Part No. Rod A B C Hole Size H Max. Rec. Load Approx. Wt./100
Size in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
50-3/8 3/8"-16 2" (50.8) 3/4" (19.0) 2" (50.8) 7/16" (11.1) 700 (3.22) 35 (15.9)
50-1/2 1/2"-13 2" (50.8) 3/4" (19.0) 2" (50.8) 9/16" (14.3) 700 (3.22) 35 (15.9)
50-5/8 5/8"-11 2" (50.8) 3/4" (19.0) 2" (50.8) 11/16" (17.5) 700 (3.22) 32 (14.5)
50-3/4 3/4"-10 21/2" (63.5) 3/4" (19.0) 21/2" (63.5) 13/16" (20.6) 1250 (5.56) 110 (49.9)
50-7/8 7/8"-9 21/2" (63.5) 3/4" (19.0) 21/2" (63.5) 15/16" (23.8) 1250 (5.56) 100 (45.3)
B3061-1 1 3" (76.2) 2" (50.8) 7/16" (11.1) 180 (0.80) 46 (20.8)
Upper
B3061-2 2 4" (101.6) 3" (76.1) 7/16" (11.1) 180 (0.80) 65 (29.5)
B3061-3 3 3" (76.2) 2" (50.8) 9/16" (14.3) 390 (1.73) 85 (38.5)
B3061-4 4 4" (101.6) 3" (76.1) 9/16" (14.3) 390 (1.73) 115 (52.1)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Eaton 219 B-Line series Pipe Hangers & Supports
Upper Attachments
TOLCO™ Fig. 58 - Threaded Side Beam Bracket
Size Range: 3/8"-16 rod, pipe sizes 1/2" (15mm) thru 4" (100mm) B
Material: Pre-Galvanized Steel
Function: Practical and economical bracket used to support piping from wood, concrete
or steel beams.
A
Features: Unique design allows rod to be easily threaded into bracket. Offset design
permits unlimited rod adjustment. Center mounting hole will accept 3/8" and 1/2" fastener
bolts. Per NFPA 13: 1/2" (15mm) thru 2" (50mm) pipe requires 3/8" fastener, 21/2" (65mm) thru
4" (100mm) pipe requires 1/2" fastener.*
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL), and
Factory Mutual Engineering approved thru 4" (100mm) pipe.
C
Finish: Pre-Galvanized
Order By: Part number and finish
2 - 1/4" x 2" Lag Bolts
*Note: Additionally UL has listed the Fig. 58 with fasteners (No Pre-Drilling
as shown in table below. Up to 4" (100mm) pipe
Per NFPA
1 - 3/8" or 1/2" Lag Bolts
Up to 4" (100mm) pipe
2 - #16 x 2"
Drive Screws
1/2" (15mm) - 4" (100mm) pipe
Attachments
Up to 4" (100mm) pipe
Upper
UL Listed Fastener Table
Pipe Size Qty Fastener Type Material Bolt & Hex Nut
Up to 4" (100mm) pipe
2" 2 #16 x 2" Drive screws Wood
2" 1 3/8" Lag bolt Wood
21/2" - 4" 1 1/2" Lag bolt Wood
31/2" 2 1/4" x 11/2" Lag bolts Wood
4" 2 1/4" x 2" Lag bolts ** Wood
4" 2 #14 x 1" or 1/4" x 1" Tek type screws Metal (15 gauge)
4" 2 #14 x 1" or 1/4" x 1" Tek type screws Metal (16 gauge)
** No pre-drilling
Part No. Pipe Size Rod A B C Max. Rec. Load Approx. Wt./100
in. (mm) Size in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
58 1/2" - 4” (15 - 100) 3/8"-16 23/4" (69.8) 11/2" (38.1) 11/8" (28.6) 300*** (1.33) 14 (6.3)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Pipe Hangers & Supports 220 Eaton
Upper Attachments
TOLCO™ Fig. 75 - Swivel Attachment
Size Range: — 3/8"-16 Rod Attachment
Material: Steel
Function: Three recommended applications for this product:
• May be used as a Branch Line Restraint for structural attachment to
anchor bolt, beam clamp, etc.
• May be used as an upper attachment with short hanger rod to omit
seismic bracing.
• May be used in a pitched or sloped roof application, to meet
requirements of NFPA 13 (2010) 9.1.2.6.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL) to support up to 4" (100mm) pipe.
Finish: Electro-Galvanized
Weight: Approx. Wt./100 - 13.3 Lbs. (6.0kg)
Order By: Part number
Patent: #7,887,248
Fig. 78 All
Steel Ceiling
Fig. 75 Swivel
Plate
Attachment
Fig. 200
“Trimline” All Threaded Rod
Adjustable
Band Hanger
of
Ro
ched
Pit Fig. 65 Reversible
Beam Clamp
Fig. 75 Swivel
Attachment Fig. 75 Swivel
W-Beam
All Threaded Rod Attachment
All Threaded Rod
B3100
Clevis Hanger
May be used as a upper attachment May be used with a pitched roof appli-
with short hanger rod to omit seismic cation, to meet requirements of NFPA 13
bracing (2010) Sec. 9.1.2.5.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Eaton 221 B-Line series Pipe Hangers & Supports
Upper Attachments
B3058 - Side Beam Connector
Size Range: 3/8"-16 & 1/2"13 rods
For #12 Flat Head
Material: Malleable Iron Machine Screws or
Wood Screws
Function: Designed for attaching hanger rod to the side of B
beams or walls.
Tapped Hole
Approvals: Conforms to Federal Specification WW-H-171E
& A-A-1192A, Type 35 and Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 34. A
(Rod Size) C
Finish: Plain or Electro-Galvanized Hanger Rod
Not Included
Order By: Part number and finish.
Attachments
Finish: Plain or Electro-Galvanized E
Upper
Order By: Part number and finish.
Part No. B C D E F T
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3062-3/8 7/16" (11.1) 7/8" (22.2) 13/8" (34.9) 5/8" (15.9) 17/16" (36.5) 1/4" (6.3)
B3062-1/2 9/16" (14.3) 13/16" (30.2) 113/16" (46.0) 3/4" (19.0) 17/8" (47.6) 11/32" (8.7)
B3062-5/8 3/4" (19.0) 17/16" (36.5) 23/16" (55.6) 7/8" (22.2) 21/4" (54.0) 7/16" (11.1)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Pipe Hangers & Supports 222 Eaton