Curva de Daño de Equipos

This document shows the protection settings and curves for the relays protecting a substation transformer and motor. It displays the settings for the overcurrent protection relays on the primary and secondary sides of the transformer, including pickup values, time dials, and time delays. It also lists the settings for the motor protection relay, including its pickup value, time dial, and time delay. Graphs show the tripping curves for each relay on the log-log scale.

Uploaded by

diego
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views1 page

Curva de Daño de Equipos

This document shows the protection settings and curves for the relays protecting a substation transformer and motor. It displays the settings for the overcurrent protection relays on the primary and secondary sides of the transformer, including pickup values, time dials, and time delays. It also lists the settings for the motor protection relay, including its pickup value, time dial, and time delay. Graphs show the tripping curves for each relay on the log-log scale.

Uploaded by

diego
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 100 Barra 8 (Nom. kV=4,16, Plot Ref.

kV=4,16)
,5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 T4 500
FLA
300 300

100 Relay_Sec_trafo_4 - P 100

OC1
50 Siemens 50
Mtr2-100% Mtr2-Cold 7SJ61
30 CT Ratio 800:5 30
Mtr2-Hot IEC - Long Inverse
Pickup = 5,2 (0,5 - 10 Sec - 5A)
Time Dial = 0,19
10 3x = 11,4 s, 5x = 5,7 s, 8x = 3,26 s 10
Inst = 16,6 (0,5 - 175 Sec - 5A)
Time Delay = 0,2 s
5 Relay_Motor_2 - P 5
Seconds

Seconds
OC1 Relay_Prim_trafo_4 - P
3 Siemens
OC1 3
7SJ61 Siemens
CT Ratio 300:5 7SJ61
IEC - Long Inverse CT Ratio 300:5
1 Pickup = 5,1 (0,5 - 20 Sec - 5A) IEC - Long Inverse 1
Time Dial = 0,65 Pickup = 4,35 (0,5 - 10 Sec - 5A)
3x = 39 s, 5x = 19,5 s, 8x = 11,1 s Time Dial = 0,21
,5
Inst = 38 (0,5 - 175 Sec - 5A) T4 3x = 12,6 s, 5x = 6,3 s, 8x = 3,6 s ,5

Time Delay = 0,05 s Inst = 15,2 (0,5 - 175 Sec - 5A)


,3 Time Delay = 0,25 s ,3
Relay_Prim_trafo_4
CB3
±

I>

T4
5 MVA
,1 ,1
±

I>
T4
CB2 Relay_Sec_trafo_4 Inrush
,05 ,05
Barra 8
CB1 Relay_Motor_2
,03 ,03
±

I>

Mtr2
1500 kW
,01 ,01
,5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 Barra 8 (Nom. kV=4,16, Plot Ref. kV=4,16) ETAP Star 12.6.0H

Star32

Project: Date: 26-04-2020


Location: SN:
Contract: Rev: Base
Engineer: Fault: Phase
Filename: C:\ETAP 1260\TALLERPRACTICO1\TALLERPRACTICO1.OTI