Electrical Plan MD Rock Concrete Mix Corporation: Motorpool Building As-Built Plan As Shown

The document provides notes and specifications for electrical work. It specifies that all electrical work must comply with Philippine electrical codes and use 230V single phase 3-wire 60Hz power. Conduits inside buildings should be PVC or rigid steel. Wiring details such as heights of outlets and minimum wire gauges are also outlined. A schedule of loads lists one circuit for lighting and convenience outlets requiring 2-3.5mm wires in 15mm conduits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
493 views1 page

Electrical Plan MD Rock Concrete Mix Corporation: Motorpool Building As-Built Plan As Shown

The document provides notes and specifications for electrical work. It specifies that all electrical work must comply with Philippine electrical codes and use 230V single phase 3-wire 60Hz power. Conduits inside buildings should be PVC or rigid steel. Wiring details such as heights of outlets and minimum wire gauges are also outlined. A schedule of loads lists one circuit for lighting and convenience outlets requiring 2-3.5mm wires in 15mm conduits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

1 2 3

GENERAL NOTES:
1. ALL ELECTRICAL WORKS SHALL BE DONE IN
ACCORDANCE WITH THE RULES AND REGULATIONS
LATEST OF THE PHILIPPINE ELECTRICAL CODE THE EXISTING
OF THE
230 VOLTS, SINGLE PHASE, 3 WIRE, 60 HERTZ, SERVICE DROP
LOCAL ORDINANCE AND WITH THE REQUIREMENTS OF THE
LOCAL ELECTRIC COMPANY.
2. POWER SUPPLY TO BE USED SHALL BE 230V, SINGLE
PHASE, 3 WIRES, 60 HERTZ ALTERNATING CURRENT.
3. CONDUIT PIPES FOR ELECTRICAL INSTALLATION INSIDE
CEILING, WOOD PARTITION UNDERGROUND OR EMBEDDED IN
20AT
A FLOOR SLAB SHALL BE PVC ELECTRICAL CONDUIT, ORANGE
COLORED OR APPROVED EQUAL TYPE FOR MAIN CONDUIT
d INSTALLATION SHALL BE IN STANDARD RIGID STEEL CONDUIT.
4. THE JOB SHALL BE EXECUTED IN THE MOST THOROUGH,
c PROMPT AND MANLIKE WORK MANNR, EMPLOYING STANDARD
Sd TOOLS, EQUIPTMENTS METHODS AND GOOD WORKING 2- 3.5 MM² THHN/
S abc PRACTICES; THE JOB SHALL BE DONE COMPLETELY IN ALL
ASPECTS AS REQUIRED IN THE PLANS AND SPECIFICATIONS 15MM Ø ELECTRICAL PIPE
AND READY FOR OPERATIONS.
B 1
5. ALL ELECTRICAL MATERIALS TO BE USED SHALL BE BRAND
NEW AND WITH THE APPROVED TYPE IN ALL LOCATIONS AND
b PURPOSES.
b
6. WIRING SERVICES SHALL BE IN THE FOLLOWING HEIGHT,
FROM CENTER OF OUTLET TO FINISH FLOOR LEVEL. KW-H
A. CONVENIENCE OUTLET 0.30 MTS.
B. WALL SWITCHES 1.40 MTS. C. METER
C PANEL BOARD
OUTLET
1.80 MTS. D. ACU
1.80 MTS.
7. THE MINIMUM SIZE OF WIRE SHALL BE 3.5 mm THW
a
COLUMBIA WIRE BRAND, THE WIRES MUST BE COLOR CODED; 2- 3.5 MM² THHN/
a LIVE IS BLACK, NEUTRAL IS WHITE, EARTH WIRE IS GREEN.
8. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE WITH 15MM Ø ELECTRICAL PIPE
THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL
ENGINEER.
D 20AT
ROOFLINE

2- 3.5 MM² THHN/


LEGENDS AND SYMBOLS: 15MM Ø ELECTRICAL PIPE
40 WATTS FLUORESCENT LAMP WITH BASE
E1 ELECTRICAL LAYOUT
SWITCH ( 1.40 meter )
1 SCALE 1:50MTS S

CONVENIENCE OUTLET (0.30 METER) SINGLE LINE DIAGRAM


PANEL BOARD

1 CIRCUIT HOMERUN

SCHEDULE OF LOADS:
CKT
CKT DESCRIPTION OF LOAD VOLTS WATTS AMPS PROTECTION WIRES AND CONDUIT
LIGHTING LOAD & 2-3.5 MM² THHN/
1 230 1300 5.65 2P, 20AT
CONVENIENCE OUTLET 15 MM Ø ELECTRICAL PIPE

OWNER PROJECT SHEET CONTENT SHEET NO.


MD ROCK APPROVED BY:

ELECTRICAL
CONCRETE MIX MOTORPOOL BUILDING AS-BUILT PLAN AS SHOWN E/1
REGISTRATION NO. DATE ISSUED:
PLAN
CORPORATION ADDRESS:
PTR: DATE ISSUED: LOCATION: