CRD1-0200-PFV

HCFC, R-22, 60 Hz, 1 -Phase, 208/230 V


Air Conditioning
Production Status: This model is obsolete and is no longer in production for both OEM and service replacement.
Please contact Customer Service about possible replacement models.

Performance Mechanical
Evaporator Temp. (°F) 45 45 Displacment(in^3/Rev): 2.51
Condensing Temp. (°F) 130 100 Displacment(ft^3/hr): 304.60
Return Gas Temp. (°F) 65 65 Overall Length (in): 9.44
Liquid Temp. (°F) 115 85 Overall Width (in): 9.00
Capacity (Btu/hr) 24100 30700 Overall Height (in): 13.81
Power (W): 2440 1940 Mounting Length (in): 7.50
Current (Amps): 10.80 8.60 Mounting Width (in): 7.50
EER (Btu/Wh): 9.90 15.80 Mounting Height (in): 14.19 *
Mass Flow (lbs/hr): 353 395 Suction Size (in),Type: 5/8 Stub
Sound Data @ Discharge Size (in),Type: 3/8 Stub
Sound Power (dBA): 73 Avg 78 Max Initial Oil Charge (oz): 55
Vibration mils(peak-peak): 1.7 Avg 2.7 Max Oil Recharge (oz): 51
Record Date: 2004-08-19 Net Weight (lbs): 63.0
Internal Free Volume (in^3): 355.0
Electrical Horse Power:
*Overall compressor height on Copeland Brand Product's specified
LRA-High*(Amp): 59.0 mounting grommets.
LRA Low* (Amp):
LRA-Half Winding (Amp):
MCC (Amps): 18.8
Capacitors
Max Operating Current(Amp):
RLA, MCC/1.4;use for contactor selection (Amp): 13.4

RLA, MCC/1.56;use for breaker & wire size selection (Amp): 12.1
RPM: 3500
UL File No:
UL File Date: 1984-12-28
*Low and High refer to the low and high nominal voltage ranges for
which the motor is approved.

Alternate Applications
Refrigerant Voltage Phase Freq (Hz) Application
R-22 HCFC 200/230 1 50 High Temp

R-22 HCFC 200/230 1 50 Air Conditioning

R-22 HCFC 208/230 1 60 High Temp

Public Public Page 1 Of 1