NEF1 - Non-Directional Earth-Fault Protection Low-Set Stage (NEF1Low) High-Set Stage (NEF1High) Instantaneous Stage (NEF1Inst)
NEF1 - Non-Directional Earth-Fault Protection Low-Set Stage (NEF1Low) High-Set Stage (NEF1High) Instantaneous Stage (NEF1Inst)
Issued: 10/1997
Version: F/03.05.2002
                                                                                 Non-Directional
                                                                          Earth-Fault Protection
                                                                       Low-Set Stage (NEF1Low)
                                                                      High-Set Stage (NEF1High)
Data subject to change without notice                            Instantaneous Stage (NEF1Inst)
                         Contents
                         1. Introduction .............................................................................................. 2
                           1.1     Features.............................................................................................. 2
                           1.2     Application........................................................................................... 2
                           1.3     Input description.................................................................................. 3
                           1.4     Output description ............................................................................... 3
                         2. Description of operation .......................................................................... 4
                           2.1     Configuration....................................................................................... 4
                           2.2     Measuring mode ................................................................................. 4
                           2.3     Operation criteria................................................................................. 4
                           2.4     Delayed reset facility and drop-off time in DT and IDMT modes.......... 5
                           2.5     IDMT type operation of NEF1Low ....................................................... 6
                                 2.5.1      Standard curve groups ............................................................... 7
                                 2.5.2      RI curve groups.......................................................................... 8
                                 2.5.3      RD curve groups ........................................................................ 8
                                 2.5.4      IEEE curve groups ..................................................................... 9
                           2.6     Setting groups ..................................................................................... 9
                           2.7     Test mode ......................................................................................... 10
                           2.8     START, TRIP and CBFP outputs ...................................................... 10
                           2.9     Resetting........................................................................................... 11
                         3. Parameters and events .......................................................................... 12
                           3.1     General ............................................................................................. 12
                           3.2     Setting values.................................................................................... 13
                                 3.2.1      Actual settings.......................................................................... 13
                                 3.2.2      Setting group 1......................................................................... 14
                                 3.2.3      Setting group 2......................................................................... 15
                                 3.2.4      Control settings ........................................................................ 16
                           3.3     Measurement values ......................................................................... 18
                                 3.3.1      Input data ................................................................................. 18
                                 3.3.2      Output data .............................................................................. 19
                                 3.3.3      Recorded data.......................................................................... 19
                                 3.3.4      Events ...................................................................................... 24
                         4. Technical data ........................................................................................ 25
 NEF1_                                                                     Substation Automation
1. Introduction
1.1 Features
1.2 Application
         The non-directional earth-fault protection function blocks are designed for non-
         directional earth-fault protection whenever the DT characteristic or, as concerns
         NEF1Low, the IDMT (Inverse Definite Minimum Time) characteristic is appropriate.
         Suppression of harmonics is possible.
2
 Substation Automation                                                                                    NEF1_
)LJXUH )XQFWLRQEORFNV\PEROVRI1()/RZ1()+LJKDQG1(),QVW
                                                                                                                   3
 NEF1_                                                                       Substation Automation
2.1 Configuration
         The measuring devices and signal types for analogue channels are selected and
         configured in a special dialogue box of the Relay Configuration Tool included in the
         CAP 505 Tool Box. Digital inputs are configured in the same programming
         environment (the number of selectable analogue inputs, digital inputs and digital
         outputs depends on the type of the hardware used).
         When the analogue channels and digital inputs have been selected and configured in
         the dialogue box, the inputs and outputs of the function block can be configured on a
         graphic worksheet of the configuration tool. The neutral current I0 can be connected to
         the Io input of the function block. Furthermore, digital inputs are connected to the
         Boolean inputs of the function block and in the same way, the outputs of the function
         block are connected to the output signals.
         The operation of the function block is based on two alternative measuring principles:
         the average value of consecutive instantaneous peak-to-peak values or the numerically
         calculated fundamental frequency component of the neutral current. The measuring
         mode is selected by means of an HMI parameter or a serial communication parameter.
         With both the measuring principles, the operation is insensitive to the DC component
         and the operation accuracy is defined in the frequency range f/fn=0.95...1.05. In peak-
         to-peak measurement, the harmonics of the neutral current are not suppressed,
         whereas in fundamental frequency measurement the harmonics suppression is at least
         -50 dB at f = n x fn, where n = 2, 3, 4, 5,...
         The function block starts if the neutral current exceeds the set start current. When the
         function block starts, the START signal is set to TRUE. Should the duration of the
         earth fault exceed the set definite operate time or, at the inverse-time operation, the
         time determined by the level of the measured current, the function block operates. The
4
 Substation Automation                                                                                    NEF1_
                         internal delay of the heavy-duty output relay is included in the total operate time.
                         When the function block operates, the TRIP signal is set to TRUE. Operation mode
                         instantaneous is selectable in the function blocks NEF1High and NEF1Inst. In
                         instantaneous mode the TRIP signal is immediately activated.
                         The DT or IDMT timer is allowed to run only if the blocking signal BS1 is inactive,
                         i.e. its value is FALSE. When the signal becomes active, i.e. its value turns to TRUE,
                         the timer will be stopped (frozen).
                         When the blocking signal BS2 is active, the TRIP signal cannot be activated. The
                         TRIP signal can be blocked by activating the signal BS2 until the function block
                         drops off.
2.4 Delayed reset facility and drop-off time in DT and IDMT modes
                         The purpose of the delayed reset function is to enable fast clearance of intermittent
                         faults, e.g. self-sealing insulation faults, and severe faults which may produce high
                         asymmetrical fault currents that partially saturate the current transformers. It is typical
                         for an intermittent fault that the fault current contains so-called drop-off periods
                         during which the fault current is below the set start current. Without the delayed reset
                         function the DT or the IDMT timer would reset once the current drops off. In the
                         same way, an apparent drop-off period of the secondary current of the saturated
                         current transformer might reset the DT or the IDMT timer. The adjustable delayed
                         reset function also enables closer co-ordination with electromechanical induction disc
                         relays.
                         When the DT timer has started, it goes on running normally even if the current drops
                         off, provided the drop-off period is shorter than the set drop-off time. In the same
                         situation, the IDMT timer is frozen. If the drop-off period is longer than the set drop-
                         off time, the DT or the IDMT timer will be reset when the drop-off time elapses. The
                         situation in the case of the DT timer is described in Figure 2.4.-1.
                         In Figures 2.4.-1 and 2.4.-2 the input signal IN of the DT timer is TRUE when the
                         current is above the set start value and FALSE when the current is below the set start
                         value.
                                                                                                                    5
 NEF1_                                                                                   Substation Automation
                1
          IN
                0
START
TRIP
                                Drop-off time
         Drop-off
         timer
                                                                         Dropoff1.fh7
                           Operate time
         Operate
         timer
         )LJXUH 7KHGURSRIISHULRGLVORQJHUWKDQWKHVHWGURSRIIWLPH
         If the drop-off period is shorter than the set drop-off time and the DT timer time has
         elapsed during the drop-off period, the function block will trip once the current
         exceeds the set value again (Figure 2.4.-2).
                    1
          IN
                    0
START
TRIP
                                   Drop-off time
         Drop-off
         timer
                                                                          Dropoff2.fh7
                                   Operate time
         Operate
         timer
)LJXUH 7KHGURSRIISHULRGLVVKRUWHUWKDQWKHVHWGURSRIIWLPH
         In the inverse-time mode, the operate time of the stage is a function of the current.
         The higher the current, the shorter the operate time is. Fourteen time/current curve
         groups are available. Four of the groups comply with the BS 142 and IEC 60255
         standards, whereas the two curve groups RI and RD (RXIDG) are special type of
         curve groups corresponding to the ABB praxis. Eight IEEE curves comply with the
         IEEE C37.112 standard. The setting "Operation mode" is used for selecting the
         desired operate time characteristic.
6
 Substation Automation                                                                                     NEF1_
                         The relationship between time and current is in accordance with the standard IEC
                         60255-4 and can be expressed as follows
                                           kxβ
                             t[s] =
                                           I α
                                      (      )   −1
                                          I>
                         where
I phase current
                             Inverse-time                        α                            β
                             characteristic
                             Normal inverse                          0.02                         0.14
                             Very inverse                            1.0                          13.5
                             Extremely inverse                       2.0                          80.0
                             Long-time inverse                       1.0                          120
                         According to the standard BS 142: 1966 the effective current range is defined as
                         2...20 times the set start current. If the time/current characteristic is normal inverse,
                                                                                                                     7
 NEF1_                                                                         Substation Automation
         very inverse or extremely inverse, the function has to start at the latest when the
         current exceeds the set start current by 1.3 times. For the long-time inverse
         characteristic, the effective current range is specified to be 2...7 times the set start
         current and the relay is to start at the latest when the current exceeds the setting value
         by 1.1 times. The function block NEF1Low will start and the IDMT integration will
         begin once the current exceeds the set start current.
         The operate time tolerances specified by the standard BS 142 : 1966 are the following
         (E denotes the accuracy in percent):
         The tolerance factors are in accordance to those defined by the standard BS 142: 1966
         for currents 2 and 5 times the setting. The NEF1Low complies with the tolerances of
         class 5 (E = 5.0%) for all inverse-time curves.
For example:
                             k
         t s =
                                      I>
                  0. 339 − 0. 236 x
                                      I
8
 Substation Automation                                                                                 NEF1_
                                                      I
                         t[s] = 5. 8 -1. 35 x ln
                                                   k x I>
                         The accuracy of the RI- and RD-type characteristics is 5%. Also with the RI- and RD-
                         type characteristics, the function block will start and the IDMT integration will begin
                         once the current exceeds the set start current.
IEEE time overcurrent curve equation according to the standard IEEE C37.112:
                                                 
                                                 
                                       $         
                          t[s] =          3
                                               + % × Q
                                   ,  − 1    
                                  ,>             
                                               
where
n adjustable IEEE time dial setting, parameters S5, S45 and S75
                          Curve                             A                B                  p
                          IEEE Extremely Inverse            6.407            0.025              2.0
                          IEEE Very Inverse                 2.855            0.0712             2.0
                          IEEE Inverse                      0.0086           0.0185             0.02
                          IEEE Short Time Inverse           0.00172          0.0037             0.02
                          IEEE Short Time Ext. Inverse      1.281            0.005              2.0
                          IEEE Long Time Ext. Inv.          64.07            0.250              2.0
                          IEEE Long Time Very Inv.          28.55            0.712              2.0
                          IEEE Long Time Inverse            0.086            0.185              0.02
                         Two different groups of setting values, group 1 and group 2, are available for the
                         function block. Switching between the two groups can be done in the following three
                         ways:
                                                                                                               9
 NEF1_                                                                             Substation Automation
         3 By means of the input signal GROUP when allowed via the parameter “Group
           selection” (i.e. when V3 = 21)).
            1)
                 Group selection (V3): 0 = Group 1; 1 = Group 2; 2 = GROUP input
         The group settings come into effect immediately after selection. The control
         parameter "Active group" indicates that the setting group is valid at a given time.
         The digital outputs of the function block can be activated with separate control
         settings for each output either locally via the HMI or externally via the serial
         communication. When an output is activated with the test parameter, an event
         indicating the test is generated.
The protection functions operate normally while the outputs are tested.
         The output signal START is always pulse-shaped. The minimum pulse width of the
         corresponding output signal is set via a separate parameter on the HMI or on serial
         communication. If the start situation is longer than the set pulse width, the START
         signal remains active until the start situation is over. The output signal TRIP may
         have a non-latching or latching feature. When the latching mode has been selected,
         the TRIP signal remains active until the output is reset even if the operation criteria
         have reset.
         The circuit-breaker failure protection function provides a delayed trip signal CBFP
         after the TRIP signal unless the fault has disappeared during the set CBFP time delay.
         The CBFP output can be used to operate a circuit breaker in front of the circuit
         breaker of the feeder. The control parameter “Trip pulse” also sets the pulse width of
         the CBFP output signal.
10
 Substation Automation                                                                                                  NEF1_
2.9 Resetting
                         The TRIP output signal and the registers can be reset either via the RESET input, or
                         over the serial bus or the local HMI.
The operation indicators, latched trip signal and recorded data can be reset as follows:
                                                                                                                             11
 NEF1_                                                                     Substation Automation
3.1 General
         • Each function block has a specific channel number for serial communication
           parameters and events. The channel for NEF1Low is 38, that for NEF1High 39 and
           that for NEF1Inst 90.
         • The data direction of the parameters defines the use of each parameter as follows:
             Data direction        Description
             R, R/M                Read only
             W                     Write only
             R/W                   Read and write
         • The different event mask parameters (see section “Control settings”) affect the
           visibility of events on the HMI or on serial communication (LON or SPA) as
           follows:
             Event mask 1 (FxxxV101/102)              SPA / HMI (LON)
             Event mask 2 (FxxxV103/104)              LON
             Event mask 3 (FxxxV105/106)              LON
             Event mask 4 (FxxxV107/108)              LON
            For example, if only the events E3, E4 and E5 are to be seen on the HMI of the
            relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
            1” parameter (FxxxV101).
            In case a function block includes more than 32 events, there are two parameters
            instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A”
            (FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events
            32...63.
12
 Substation Automation                                                                                                  NEF1_
NEF1Low
                         IEEE time dial       S5     0.5...15.0      -          0.5       R            IEEE time dial ‘n’ in IDMT
                                                                                                       mode
                            1)
                                 Operation mode      0 = Not in use; 1 = Definite time; 2 = Extremely inv.; 3 = Very inv.;
                                                     4 = Normal inv.; 5 = Long-time inv.; 6 = RI-type inv.; 7 = RD-type inv.; 8 =
                                                     IEEE Ext.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 =
                                                     IEEE S.T.E. inv; 13 = IEEE L.T.E. inv.; 14 = IEEE L.T.V. inv.; 15 = IEEE L.T.
                                                     inv.
                                                                                                                                     13
 NEF1_                                                                                      Substation Automation
NEF1Low
         Time multiplier     S44     0.05...1.00     -          0.05      R/W          Time multiplier ‘k’ in IDMT
                                                                                       mode
         IEEE time dial      S45     0.5...15.0      -          0.5       R/W          IEEE time dial ‘n’ in IDMT
                                                                                       mode
            1)
                 Operation mode      0 = Not in use; 1 = Definite time; 2 = Extremely inv.; 3 = Very inv.;
                                     4 = Normal inv.; 5 = Long time inv.; 6 = RI-type inv.; 7 = RD-type inv.; 8 =
                                     IEEE Ext.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 =
                                     IEEE S.T.E. inv; 13 = IEEE L.T.E. inv.; 14 = IEEE L.T.V. inv.; 15 = IEEE L.T.
                                     inv.
14
 Substation Automation                                                                                                  NEF1_
NEF1Low
                         Time multiplier     S74     0.05...1.00     -          0.05      R/W          Time multiplier ‘k’ in IDMT
                                                                                                       mode
                         IEEE time dial      S75     0.5...15.0      -          0.5       R/W          IEEE time dial ‘n’ in IDMT
                                                                                                       mode
                            1)
                                 Operation mode      0 = Not in use; 1 = Definite time; 2 = Extremely inv.; 3 = Very inv.;
                                                     4 = Normal inv.; 5 = Long time inv.; 6 = RI-type inv.; 7 = RD-type inv.; 8 =
                                                     IEEE Ext.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 =
                                                     IEEE S.T.E. inv; 13 = IEEE L.T.E. inv.; 14 = IEEE L.T.V. inv.; 15 = IEEE L.T.
                                                     inv.
                                                                                                                                     15
 NEF1_                                                                                        Substation Automation
NEF1Low
16
Substation Automation                                                                                                 NEF1_
                                                                                                                                  17
 NEF1_                                                                                        Substation Automation
NEF1Low
18
 Substation Automation                                                                                                   NEF1_
3.3.3.1 General
                         The information required for later fault analysis is recorded when the function block
                         starts or trips, or when the recording function is triggered via an external triggering
                         input.
                         The data of three last operations (operation 1...3) are recorded and the values of the
                         most recent operation always replace the data of the oldest operation. The registers
                         are updated in the following order: Operation 1, Operation 2, Operation 3, Operation
                         1, Operation 2,...
                         The recording function can be blocked via the BSREG input. For example, if an auto-
                         reclose sequence is initiated by the trip signal of the function block, the values most
                         reliable for later fault analysis are those recorded just before Shot 1. When the auto-
                         reclose sequence has started, no recordings are needed at the moment of tripping. The
                         output signal ACTIVE in AR5Func indicating AR in progress is connected to the
                         BSREG input to prevent useless recording.
The time stamp indicates the rising edge of the START, TRIP or TRIGG signal.
3.3.3.3 Duration
                         If the function block trips, the current values are updated at the moment of tripping
                         i.e. on the rising edge of the signal TRIP. For external triggering the current values are
                                                                                                                             19
 NEF1_                                                                          Substation Automation
           updated at the moment of triggering i.e. on the rising edge of the input signal TRIGG.
           If the function block starts but does not trip, the neutral current value captured one
           fundamental cycle (20 ms at rated frequency 50 Hz) after the beginning of the start
           situation is recorded. The value of the neutral current I0 is recorded as a multiple of
           the rated current In.
           The status data of the input signals BS1 and BS2 as well as the “Active group”
           parameter are recorded at the moment of recording. The “Active group” parameter
           indicates the setting group valid for the recorded data.
3.3.3.6 Priority
           1 Tripping
           2 Starting
           3 External triggering,
           which means that if the function block has started, it will neglect an external
           triggering request.
20
 Substation Automation                                                                                                           NEF1_
NEF1Low
                                                                                                                                            21
 NEF1_                                                                                               Substation Automation
NEF1Low
22
 Substation Automation                                                                                                     NEF1_
NEF1Low
                                                                                                                                      23
 NEF1_                                                                                 Substation Automation
3.3.4 Events
24
Substation Automation                                                                                                         NEF1_
NEF1Low:
Reset time 40...1000 ms (depends on the set minimum output pulse width)
0 No suppression
C -
NEF1High B -
C -
NEF1Inst B -
D -
25