York Usa Pac 15 - 20 TR
York Usa Pac 15 - 20 TR
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Component Location
(ZJ shown)
                                                                                                         HIGH
                                                                                                      EFFICIENCY   COPPER TUBE/ALUMINUM FIN
                                              20 GAUGE
                                                                                                     COMPRESSORS      CONDENSER COILS
                                          ALUMINIZED STEEL          ELECTRIC HEATER LOCATION
                                      TUBULAR HEAT EXCHANGERS   (OPTIONAL ELECTRIC/ELECTRIC UNITS)
                   LONG LASTING
                POWDER PAINT FINISH
                                                                                                                                                        ELECTRICAL
                                                                                                                                                       DISCONNECT
                                                                                                                                                         MOUNTING
                                                                                                                                                         LOCATION
                                                                                                                                                       (Field installed)
                                                                                                                                                      KNOCKOUT FOR
                                                                                                                                                      SIDE CONTROL
                                                                                                                                                      WIRING ENTRY
                                                                                                                                                         KNOCKOUT
                                                                                                                                                          FOR SIDE
2" DISPOSABLE
                                                                                                                                                       POWER WIRING
    FILTERS
                                                                                                                                                        ENTRY SIDE
                                                                                                                                GAS/ELECTRIC
                                                                   BELT-DRIVE
                          1" NPTI                                BLOWER MOTOR                                                    UNIT SHOWN
                     CONDENSATE DRAIN
                                            FULL PERIMETER
                                         14 GAUGE BASE RAILS
                                          WITH LIFTING HOLES
Nomenclature
                                                                                                                                       Additional Options
                            Electric Heat Options
                                                                                                     Standard Cabinet                             Hinged Filter Door & Tool Free Access Cabinet
                 E18 = 18 KW
                 E36 = 36 KW                                                    AA = None                                                      BA = Hinged Filter Door & Tool Free Access Panels
                 E54 = 54 KW                                                    AB = Phase Monitor                                             BB = Phase Monitor, Hinged Filter Door & Tool Free
                 E72 = 72 KW                                                    AC = Coil Guard                                                     Access Panels
                                                                                AD = Dirty Filter Switch                                       BC = Coil Guard, Hinged Filter Door & Tool Free
                                                                                AE = Phase Monitor & Coil Guard                                     Access Panels
                                   Airflow                                      AF = Phase Monitor & Dirty Filter Switch                       BD = Dirty Filter Switch, Hinged Filter Door &
                                                                                AG = Coil Guard & Dirty Filter Switch                               Tool Free Access Panels
          A = Hi Static                                                         AH = Phase Monitor, Coil Guard & Dirty Filter Switch           BE = Phase Monitor & Coil Guard, Hinged Filter
          B = Hi Static/Economizer                                              RC = Coil Guard & American Flag                                     Door & Tool Free Access Panels
          C = Hi Static/Economizer/Power Exhaust                                TA = Technicoat Condenser Coil                                 BF = Phase Monitor & Dirty Filter Switch, Hinged
              (Downflow Only)                                                   TJ = Technicoat Evaporator Coil                                     Filter Door & Tool Free Access Panels
          D = Hi Static/Motorized Damper                                        TS = Technicoat Evaporator & Condenser Coils                   BG = Coil Guard & Dirty Filter Switch, Hinged Filter
          E = Hi Static/Motorized Damper/Barometric Relief                                                                                          Door & Tool Free Access Panels
          J = Hi Static/Economizer/Barometric Relief                                                                                           BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
                                                                                                                                                    Hinged Filter Door & Tool Free Access Panels
                                                             Voltage
                                                                                ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
                                                                                     located in digits 15-18.
                                                      7 = 380/415-3-50
Installation Options
                                                                         A = No Options Installed
                                                                         B = Option 1
                                                                         E = Option 3
                                                                         F = Option 4
                                                                         G = Options 1 & 3
                                                                         H = Options 1 & 4
                                                                         L = Options 1,3 & 4
                                                                         R = Options 3 & 4
Options
                                                                         1 = Disconnect
                                                                         3 = Smoke Detector S.A.
                                                                         4 = Smoke Detector R.A.
Features and Benefits                                                     over the opening in the return air panel. With horizontal
                                                                          ductwork, it should be mounted on the return air duct.
Standard Features                                                       • System Protection - Suction line freezestats are supplied
                                                                          on all units to protect against loss of charge and coil frosting
   • High Efficiency - High efficiency units reach as high as
                                                                          when the economizer operates at low outdoor air
     10.9 EER. Gas/electric units have electronic spark ignition
                                                                          temperatures while the compressors are running. Every unit
     and power vented combustion with steady state efficiencies
                                                                          has solid-core liquid line filter-driers and high and low-
     of 80%.
                                                                          pressure switches. Internal compressor protection is
   • Balanced Heating -                                                   standard on all compressors. Phase Monitors are optional
     • Gas Heat - All gas heat units are built with two heating           on all units. This accessory monitors the incoming power to
        sections for two equal stages of capacity control. Each           the unit and protects the unit from phase loss and reversed
        section includes a durable heat exchanger with                    phase rotation.
        aluminized steel or optional stainless steel tubes, a           • Advanced Controls - Simplicity™ ZF control boards
        redundant gas valve, spark ignition, power venting, an            have standardized a number of features previously
        ignition module for 100% shut-off and all of the safety           available only as options or by utilizing additional controls.
        controls required to meet the latest ANSI standards.
                                                                          • Low Ambient - An integrated low-ambient control
        The gas supply piping can be routed into the heating                allows all units to operate in the cooling mode down to
        compartment through a hole in the base pan of the unit              0F outdoor ambient without additional assistance.
        or through a knockout in the piping panel on the front of           Optionally, the control board can be programmed to
        the unit.                                                           lockout the compressors when the outdoor air
     • Electric Heat - All electric heat models (factory installed          temperature is low or when free cooling is available.
        only) are wired for a single power source and include a
        bank of nickel chromium elements mounted at the
        discharge of the supply air blower to provide a high velocity
        and uniform distribution of air across the heating elements.
        Every element is fully protected against excessive current       The Simplicity® control board used in this product
        and temperature by fuses and two thermal limit switches.         will effectively operate the cooling system down to
        The power supply wiring can be routed into the control           25°F when this product is applied in a comfort
        box through a threaded pipe connection in the base pan           cooling application for people. An economizer is
        of the unit or through a knockout in the wiring panel on         typically included in this type of application. When
        the front of the unit.                                           applying this product for process cooling applications
   • BAS Controls - York’s Sunline™ series units offer factory           (computer rooms, switchgear, etc.), please
     mounted BAS controls such as Simplicity ® Intelli-Comfort           reference applications bulletin AE-011-07 or call the
     II ™, Novar, Honeywell, Johnson, York Commercial                    applications department for Unitary Products @ 1-
     Comfort System (YCCS) and CPC.                                      877-UPG-SERV for guidance.
   • Convertible Airflow Design - All models (including those
                                                                         • Anti-Short Cycle Protection - To aid compressor life,
     with an economizer) are suitable for either bottom or
                                                                           an anti-short cycle delay is incorporated into the
     horizontal duct connections. Models with factory
                                                                           standard controls. Compressor reliability is further
     installed power exhaust are suitable for bottom duct
                                                                           ensured by programmable minimum run times. For
     connections only. For bottom duct, you remove the sheet
                                                                           testing, the anti-short cycle delay can be temporarily
     metal panels from the supply and return air openings
                                                                           overridden with the push of a button.
     through the base of the unit. For horizontal duct, you
     replace the supply and return air panels on the rear of the         • Lead-Lag - An integrated Lead-Lag option allows equal
     unit with a side duct flange accessory.                               run time hours on all compressors, thereby extending
                                                                           the life of all compressors. This option is selectable on
   • Factory Mounted Outdoor Air Dampers - All models are
                                                                           the unit control board.
     available with these "factory mounted" outdoor air damper
     options:                                                            • Fan Delays - Fan on and fan off delays are fully
     • Single enthalpy economizer with or without power                    programmable. Furthermore, the heating and cooling
        exhaust                                                            fan delay times are independent of one another. All units
                                                                           are programmed with default values based upon their
     • BAS-ready economizer with or without power exhaust
                                                                           configuration of cooling and heat.
     • Motorized outdoor air damper
                                                                         • Safety Monitoring - The control board monitors the
     • Barometric Relief Damper                                            high and low-pressure switches, the freezestats, the gas
     A fixed outdoor air intake assembly will be shipped in the            valve, if applicable, and the temperature limit switch on
     return air compartment of all units ordered without an                gas and electric heat units. The unit control board will
     economizer or motorized outdoor air damper option. The                alarm on ignition failures, compressor lockouts and
     assembly includes a rain hood with a damper that can be set           repeated limit switch trips.
     for 10, 15 or 25% outdoor air. With bottom duct connections,        • Nuisance Trip Protection and Strikes - To prevent
     the fixed outdoor air intake assembly should be mounted               nuisance trouble calls, the control board uses a “three
          times, you’re out” philosophy. The high and low-               controller. BAS-ready actuators have an adjustable
          pressure switches and the freezestats must trip three          auxiliary end-switch for optional power exhaust control.
          times within two hours before the unit control board will      For units with optional VAV or Simplicity® Intelli-Comfort
          lock out the associated compressor.                            II™ control, a factory-installed, dry bulb sensor
        • On Board Diagnostics - Each alarm will energize a              determines if outdoor air temperature is low enough to
          trouble light on the thermostat, if so equipped, and flash     provide free-cooling operation. (Field-installed humidity
          an alarm code on the control board LED. Each high and          sensors for either outdoor air or outdoor & return air
          low-pressure switch alarm as well as each freezestat           streams are available for single enthalpy and differential
          alarm has its own flash code. The control board saves          enthalpy configurations, respectively).
          the five most recent alarms in memory, and these alarms
                                                                         The rain hood is painted to match the basic unit and must
          can be reviewed at any time. Alarms and programmed
                                                                         be field-assembled before installing.
          values are retained through the loss of power.
                                                                        • Power Exhaust - Our economizer options are available
    •   Reliable - From the beginning - All units undergo
                                                                          with power exhaust. Whenever the outdoor air intake
        computer automated testing before they leave the factory.
                                                                          dampers are opened for free cooling, the exhaust fan will
        Units are tested for refrigerant charge and pressure, unit
                                                                          be energized to prevent the conditioned space from being
        amperage, and 100% functionality. For the long term - All
                                                                          over-pressurized during economizer operation.
        units are painted with a long lasting, powder paint that
        stands up over the life of the unit. The paint used has           The exhaust fan, motor and controls are installed and
        been proven by a 1000 hour salt spray test.                       wired at the factory. The rain hood must be assembled
                                                                          and installed in the field.
    •   Full Perimeter Base Rails - The permanently attached
        base rails provide a solid foundation for the entire unit and     The power exhaust option can only be used on bottom
        protect the unit during shipment. The rails offer rigging         duct configurations.
        holes so that an overhead crane can be used to place the        • Motorized Outdoor Air Intake Damper - Includes a
        units on a roof.                                                  slide-in / plug-in damper assembly with a 2- position,
    •   Easy Installation - Gas and electric utility knockouts are        spring return motor actuator which opens to a pre-set
        supplied in the unit underside as well as the side of the         position whenever the supply air blower is operating and
        unit. Utility connections can be made quickly and with a          will drive fully closed when the blower unit shuts down.
        minimum amount of field labor. All units are shipped with         The rain hood is painted to match the basic unit and must
        2" throw-away filters installed.                                  be field assembled before installing.
    •   Wide Range of Indoor Airflows - All supply air blowers          • Barometric Relief Damper - This damper option can be
        are equipped with a belt drive that can be adjusted to            used to relieve internal building air pressure on units with
        meet the exact requirements of the job.                           an economizer without power exhaust. This accessory
    •   Warranty - All models include a 1-year limited warranty           includes a rain hood, a bird screen and a fully assembled
        on the complete unit. Compressors and electric heater             damper. With bottom duct connections, the damper
        elements each carry a 5-year warranty. Aluminized steel           should be mounted over the opening in the return air
        and stainless steel tubular heat exchangers carry a 10-           panel. With horizontal ductwork, the accessory should be
        year warranty.                                                    mounted on the return air duct.
                                                                        • Technicoat Condenser Coils - The condenser coils are
Factory Installed Options                                                 coated with a phenolic coating for protection against
YORK® offers several equipment options factory installed, for             corrosion due to harsh environments.
the ZF Series.                                                          • Technicoat Evaporator Coil - The evaporator coils are
    • Single Input Electronic Enthalpy Economizers -                      coated with a phenolic coating for protection against
      Includes a slide-in / plug-in damper assembly with fully            corrosion due to harsh environments.
      modulating spring-return motor actuator capable of                • Electric Heaters - wired for single point power supply.
      introducing up to 100% outdoor air with nominal 1%                  These nickel chromium heater elements are provided with
      leakage type dampers.                                               limit and automatic reset capability to prevent operation at
      The enthalpy system contains one sensor that monitors               excessive temperatures.
      the outdoor air and determines when the air is cool               • Filter Options - Standard units are shipped with 2" throw-
      enough and dry enough to provide free cooling.                      away filters installed. 2" pleated and 4" pleated filters are
      The rainhood is painted to match the basic unit and must            offered as a factory installed option.
      be field-assembled before installing.                             • Disconnect Switch - For gas heat units and cooling units
    • BAS-Ready Economizer - Includes a slide-in / plug-in                with electric heat, a HACR breaker sized to the unit is
      damper assembly with fully modulating spring-return                 provided. For cooling only units, a switch sized to the
      motor actuator with zero to 95-degree rotation capable of           largest electric heat available for the particular unit is
      introducing up to 100% outdoor air with nominal 1%                  provided. Factory installed option only.
      leakage type dampers.                                             • York Commercial Comfort System (YCCS) - Provides
      Actuator requires 2-10 VDC input from an external source,           rooftop system integration for YCCS single zone, change-
      such as a field-installed or factory-installed BAS                  over bypass and VAV systems.
   • Smoke Detectors - (supply air & return air) The smoke                Simplicity™ Intelli-Comfort II™ with Simplicity™LINC
     detectors stop operation of the unit by interrupting power           Control - The York® Simplicity™ Intelli-Comfort II™ with
     to the control board if smoke is detected within the air             Simplicity™LINC control is factory installed. It includes all
     compartment.                                                         the features of the Intelli-Comfort II™ control with an
                                                                          additional control to translate communications from
                                                                          MODBUS to the BACnet MSTP protocol.
                                                                          Novar® BAS Control - The Novar® building automation
                                                                          system controller is factory installed. Incudes supply air
   Factory installed smoke detectors in the return air, may
                                                                          sensor, return air sensor, dirty filter indicator switch, and
   be subjected to freezing temperatures during “off” times
                                                                          air proving switch.
   due to out side air infiltration. these smoke detectors have
   an operational limit of 32°F to 131°F. smoke detectors                 Johnson Controls BAS Control - The Johnson Control
   installed in areas that could be out side those limitations            YK-UNT-1126 building automation system controller is
   will have to be moved to prevent having false alarms.                  factory installed. Includes supply air sensor, return air
                                                                          sensor, dirty filter indicator switch, and air proving switch.
   • Coil Guard - Customers can purchase a coil guard kit to              CPC BAS Control - The Computer Process Controls
     protect the condenser coil from damage. This is not a hail           Model 810-3060 ARTC Advanced Rooftop building
     guard kit.                                                           automation system controller is factory installed. Includes
   • Stainless Steel Heat Exchanger - For applications in                 supply air sensor, return air sensor, dirty filter indicator
     corrosive environments, this option provides a full                  switch and air proving switch.
     stainless steel heat exchanger assembly.                             Honeywell BAS Control - The Honeywell W7750C
   • Stainless Steel Drain Pan - An optional rustproof                    building automation system controller is factory installed.
     stainless steel drain pan is available to provide years of           Includes air supply sensor, return air sensor, dirty filter
     trouble-free operation in corrosive environments.                    indicator switch, and air proving switch.
   • Phase Monitors - Designed to prevent unit damage. The
     phase monitor will shut the unit down in an out-of phase
                                                                     Field Installed Accessories
     condition.                                                      YORK® offers several equipment accessories for field
   • Dirty Filter Switch - This kit includes a differential          installation, for the ZF Series.
     pressure switch that energizes the fault light on the unit         • Single Input Electronic Enthalpy Economizers -
     thermostat, indicating that there is an abnormally high              Includes a slide-in / plug-in damper assembly with fully
     pressure drop across the filters. Factory installed option or        modulating spring-return motor actuator capable of
     field installed accessory.                                           introducing up to 100% outdoor air with nominal 1%
   • Hinged Filter Door/"Tool Free" Blower And Access                     leakage type dampers.
     Panels (Not Hinged) - This option allows for easy access             The enthalpy system contains one sensor that monitors
     and maintenance.                                                     the outdoor air and determines when the air is cool
NOTE: Knobs are shipped separately within the unit to prevent             enough and dry enough to provide free cooling.
      shipping damage. These must be field installed for tool             The rain hood is painted to match the basic unit and must
      free operation.                                                     be field-assembled before installing.
   • Hinged/"Tool Free" Blower, Blower Motor, Filter And                • Motorized Outdoor Air Intake Damper - Includes a
     Electric Access Panels - This option allows for complete             slide-in / plug-in damper assembly with a 2-position,
     hinged and tool free access to the unit’s blower, blower             spring return motor actuator which opens to some pre-set
     motor, filters and electrical panel sections.                        position whenever the supply air blower is operating and
                                                                          will drive fully closed when the blower unit shuts down.
Control Options                                                           The rain hood is painted to match the basic unit and must
                                                                          be field assembled before installing.
   • BAS - Building Automation System Controls
     (available on two-system cooling product only).                    • Roof Curbs - Fourteen-inch high roof curbs provide a
                                                                          water-tight seal between the unit and the finished roof.
     Simplicity™ Intelli-Comfort II™ Control - The York®
                                                                          These full perimeter curbs meet the requirements of the
     Simplicity™ INTELLI-CO2 sensor to perform Differential
                                                                          National Roofing Contractors Association (NRCA) and are
     Demand Ventilation. It uses a Patented Comfort
                                                                          shipped knocked-down for field assembly.
     Ventilation algorithm to provide comfortable ventilation air
     temperature. The patented economizer-loading algorithm               They're designed to fit inside the base rails of the unit and
     will protect the equipment when harsh operating                      include both a wood nailing strip and duct hanger supports.
     conditions exist. It uses the INTELLI-Start™ algorithm to          • High Altitude Natural Gas - Burner orifices and pilot
     maximize energy savings by recovering the building from              orifices are provided for proper furnace operation at
     the Unoccupied Setpoints to the Occupied Setpoints just              altitudes up to 6,000 feet.
     in time for the Occupied Time Period to begin. The                 • Propane - Burner orifices, pilot orifices and gas valve parts
     Simplicity™ Intelli-Comfort II™ balances space                       are provided to convert a natural gas furnace to propane.
     temperature, ventilation air temperature, CO2 and                  • High Altitude Propane - Burner orifices and pilot orifices
     humidity for ultimate comfort.                                       are provided for proper furnace operation at altitudes up
        to 6,000 feet. This accessory supplements the basic                Compressors and electric heater elements carry an additional
        propane conversion kit.                                            4-year warranty. Aluminized steel tubular heat exchangers
    •   Side Duct Flanges - One-inch flanges replace the supply            carry an additional 9-year warranty.
        and return air panels on the rear of the unit to accommodate
        horizontal duct connections. These flanges can also be used        Description
        individually for bottom supply / horizontal return or horizontal
                                                                           ZF units shall be factory-assembled, single packaged, ZF***N
        supply/bottom return. They cannot be used on units with
                                                                           Electric Cooling/Gas Heat, ZF***C/E Electric Cooling/Optional
        power exhaust.
                                                                           Electric Heat, designed for outdoor mounted installation.
    •   Barometric Relief Damper - This damper accessory can
        be used to relieve internal building air pressure on units         They shall have built-in field convertible duct connections for
        with an economizer without power exhaust. This                     down discharge supply/return or horizontal discharge supply/
        accessory includes a rain hood, a bird screen and a fully          return, and be available with factory installed options or field
        assembled damper. With bottom duct connections, the                installed accessories. The units shall be factory wired, piped,
        damper should be mounted over the opening in the return            charged with R-410A refrigerant and factory tested prior to
        air panel. With horizontal ductwork, the accessory should          shipment. All unit wiring shall be both numbered and color
        be mounted on the return air duct.                                 coded. All units shall be manufactured in a facility certified to
    •   Enthalpy Accessory Control Kit - This kit contains the             ISO 9001 standards and the cooling performance shall be rated
        required components to convert a single enthalpy                   in accordance with DOE and AHRI test procedures. Units shall
        economizer to dual enthalpy.                                       be classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No.
    •   Burglar Bars - Mount in the supply and return openings             236-M90 conditions.
        to prevent entry into the duct work.
                                                                           Unit Cabinet
    •   Flue Exhaust Extension Kit - In locations with wind or
        weather conditions which may interfere with proper                 Unit cabinet shall be constructed of galvanized steel, with
        exhausting of furnace combustion products, this kit can be         exterior surfaces coated with a non-chalking, powdered paint
        installed to prevent the flue exhaust from entering nearby         finish, certified at 1000 hours salt spray test per ASTM-B117
        fresh air intakes.                                                 standards. Indoor blower section shall be insulated with a
    •   Wood Skid - Allows unit to be handled with 90" forks.              minimum 1/2" thick insulation, coated on the airside. Aluminum
    •   CO2 Sensor - Senses CO2 levels and automatically                   foil faced insulation shall be used in the furnace compartment
        overrides the economizer when levels rise above the                and be fastened with rigid fasteners to prevent insulation from
        present limits.                                                    entering the air stream. Cabinet panels shall be easily
    •   Coil Guard - Customers can purchase a coil guard kit to            removable for servicing and maintenance. Full perimeter base
        protect the condenser coil from damage. This is not a hail         rails shall be provided to assure reliable transit of equipment,
        guard kit.                                                         overhead rigging and proper sealing on roof curb applications.
    •   Phase Monitors - Designed to prevent unit damage. The              Disposable 2" filters shall be furnished and be accessible
        phase monitor will shut the unit down in an out-of phase           through a removable access door, sealed airtight. Units filter
        condition.                                                         track shall be designed to accommodate either 2" or 4" filters.
                                                                           Fan performance measuring ports shall be provided on the
                                                                           outside of the cabinet to allow accurate air measurements of
Guide Specifications                                                       evaporator fan performance without removing panels or
                                                                           creating air by-pass of the coils. Condensate pan shall be
General
                                                                           internally sloped and conform to ASHRAE 62-89 self-draining
Units shall be manufactured by Johnson Controls Unitary                    standards. Condensate connection shall be a minimum of 1"
Products in an ISO 9001 certified facility.                                I.D. female and be a ridged mount connection. Unit shall
                                                                           incorporate a fixed outdoor air damper with an outdoor air
ZF models have 2 condenser fan motors and compressors. All                 intake opening covered with a bird screen and a rain hood
compressors include crankcase heat and internal discharge                  painted to match the exterior of the unit.
temperature protection. Every refrigerant circuit includes an
expansion valve, a liquid line filter-drier, a discharge line high         Indoor (Evaporator) Fan Assembly
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch. The unit control circuit includes          Fan shall be a belt drive assembly and include an adjustable-
75 VA and 150 VA transformers, a 24-volt circuit breaker and a             pitch motor pulley. Job site selected (B.H.P.) brake horsepower
relay board with two compressor lockout circuits, a terminal               shall not exceed the motors nameplate horsepower rating, plus
strip for thermostat wiring, plus an additional set of pin                 the service factor. Units shall be designed not to operate above
connectors to simplify the interface of additional field controls.         service factor. Fan wheel shall be double-inlet type with
All units have long lasting powder paint cabinets with 1000 hour           forward-curved blades, dynamically balanced to operate
salt spray test approval under ASTM-B117 procedures. All                   smoothly throughout the entire range of operation. Airflow
models include a 1-year limited warranty on the complete unit.             design shall be constant air volume.
Outdoor (Condenser) Fan Assembly                                           d. Unit shall incorporate "AUTO RESET" compressor over
                                                                              temperature, over current protection.
The outdoor fans shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to                  e. Unit shall operate with conventional thermostat designs
corrosion resistant steel spider brackets and shall be                        and have a low voltage terminal strip for easy hook-up.
dynamically balanced for smooth operation. The 2 outdoor fan               f. Unit control board shall have on-board diagnostics and
motors shall be totally enclosed with permanently lubricated                  fault code display.
bearings, internally protected against overload conditions and
staged independently.                                                      g. Standard controls shall include anti-short cycle and low
                                                                              voltage protection, and permit cooling operation down to
Refrigerant Components                                                        25°F.
                                                                           h. Control board shall monitor each refrigerant safety switch
Compressors:
                                                                              independently.
    a. Shall be Scroll compressors internally protected with
       internal discharge temperature protection over                      i. Control board shall retain last 5 fault codes in non volatile
       temperature protection.                                                memory, which will not be lost in the event of a power
                                                                              loss.
    b. Shall have internal spring isolation and sound muffling to
       minimize vibration and noise, and be externally isolated        Gas Heating Section (ZF***N Models)
       on a dedicated, independent mounting.
                                                                       Shall be designed with induced draft combustion with post purge
Coils:                                                                 logic and energy saving direct spark ignition, redundant main gas
    a. Evaporator and condenser coils shall have aluminum              valve. Ventor wheel shall be constructed of stainless steel for
       plate fins mechanically bonded to seamless internally           corrosion resistance. The heat exchanger shall be of the tubular
       enhanced copper tubes with all joints brazed. Special           type, constructed of T1-40 aluminized steel for corrosion
       Phenolic coating shall be available as a factory option.        resistance and allowing minimum mixed air entering temperature
    b. Evaporator and Condenser coils shall be of the direct           of 25 °F. Burners shall be of the in-shot type, constructed of
       expansion, draw-thru, design.                                   aluminum coated steel and contain air mixture adjustments. All
                                                                       gas piping shall enter the unit cabinet at a single location through
Refrigerant Circuit and Refrigerant Safety Components shall            either the side or curb, without any field modifications. An
include:                                                               integrated control board shall provide timed control of evaporator
    a. Balance-port thermostatic expansion             valve    with   fan functioning and burner ignition. Heating section shall be
       independent circuit feed system.                                provided with the following minimum protection:
    b. Filter drier/strainer to eliminate any moisture or foreign          a. Primary and auxiliary high-temperature limit switches.
       matter.                                                             b. Induced draft motor speed sensor.
    c. Accessible service gage connections on both suction                 c. Flame roll out switch (automatic reset).
       and discharge lines to charge, evacuate, and measure
       refrigerant pressure during any necessary servicing or              d. Flame proving controls. Unit shall have two independent
       troubleshooting, without losing charge.                                stages of capacity.
    d. The refrigeration system shall provide at least 10° F of        Electric Heating (ZF***C/E Models)
       sub-cooling at design conditions.
                                                                       Nickel chromium electric heating elements shall be provided as
    e. All models shall have two independent circuits.                 required by the application with 1 or 2 stage control, as
Unit Controls                                                          required, from 18 KW to 72 KW nominal capacities. The heating
                                                                       section shall have a primary limit control(s) and automatic reset
    a. Unit shall be complete with self-contained low-voltage          to prevent the heating element system from operating at an
       control circuit protected by a resettable circuit breaker on    excessive temperature. Units with Electric Heating shall be
       the 24-volt transformer side.                                   wired for a single point power supply with branch circuit fusing
                                                                       (where required).
    b. Unit shall incorporate a lockout circuit which provides
       reset capability at the space thermostat or base unit,          Unit Operating Characteristics
       should any of the following standard safety devices trip
       and shut off compressor.                                        Unit shall be capable of starting and running at 125° F outdoor
    c. Loss-of-charge/Low-pressure switch.                             temperature, exceeding maximum load criteria of AHRI
                                                                       Standard 340/360. The compressor, with standard controls,
         1. High-pressure switch.                                      shall be capable of operation down to 25° F outdoor
         2. Freeze-protection thermostat, evaporator coil. If any of   temperature. Unit shall be provided with fan time delay to
            the above safety devices trip, a LED (light-emitting       prevent cold air delivery before heat exchanger warms up (Gas
            diode) indicator shall flash a diagnostic code that        heat only).
            indicates which safety switch has tripped.
     • Motorized Outdoor Air Dampers - Outdoor and return                • Dirty Filter Switch
       air dampers that are interlocked and positioned by a 2-           • Phase Monitor
       position, spring-return damper actuator. The maximum              • Coil Guard
       leakage rate for the outdoor air intake dampers shall not
                                                                         • Bas Controls - Simplicity ® Intelli-Comfort II ™, CPC,
       exceed 2% when dampers are fully closed and operating
                                                                           JOHNSON, HONEYWELL, NOVAR, YORK
       against a pressure differential of 0.5 IWG. A unit-mounted
                                                                           COMMERCIAL COMFORT SYSTEM (YCCS)
       potentiometer shall be provided to adjust the outdoor and
       return air damper assembly to take in the design CFM of           • BAS Ready Economizer (2-10 V.D.C. Actuator Without a
       outdoor air to meet the ventilation requirements of the             Controller)
       conditioned space during normal operation. Whenever the           • Hinged Filter Door Access And Tool Free Access
       indoor fan motor is energized, the dampers open up to               Panels
       one of two pre-selected positions - regardless of the             • Hinged Tool Free Blower, Blower Motor, Filter And
       outdoor air enthalpy. Dampers return to the fully closed            Electrical Access Panels
       position when the indoor fan motor is de-energized.
                                                                         • 2" Pleated Filters, MERV 7
       Dampers shall fully close on power loss.
                                                                         • 4" Pleated Filters, MERV 13
Other Pre-engineered Accessories Available                               • Disconnect Switch
     • Roof Curb - 14" high, full perimeter curb with wood nailer        • Supply Air Smoke Detector
       (shipped knocked-down).
                                                                         • Return Air Smoke Detector
Physical Data
Capacity Performance
ZF180-240 Cooling Capacities
     1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
     2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
     3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
        WC.
     1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
     2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
     3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
        WC.
     1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
     2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
     3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
        WC.
     1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
     2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
     3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
        WC.
Airflow Performance
ZF180-240 Side Duct Application
  1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
  2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
     1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
     2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
  1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
  2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
     1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
     2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
     3. kW = BHP x 0.838.
RPM Selection
   Size                                    Motor    Blower    6 Turns           5 Turns    4 Turns    3 Turns     2 Turns      1 Turn    Fully
           Model        HP     Max BHP
  (Tons)                                  Sheave    Sheave     Open              Open       Open       Open        Open        Open     Closed
    180
             ZF        4.0       4.72     1VP62      BK75       925               967        1009       1051         1093      1135      N/A
   (15)
    240
             ZF         6.3      7.13     1VP75     BK100       895               926        956         987         1018      1049      N/A
   (20)
* Maximum blower speed is 1400 RPM for ZF180 and 1200 RPM for ZF240
Drive Selection
1.     6800 CFM
2.     2.0 iwg
3.     Using the supply air blower performance table below, the following data point was located: 1020 RPM & 5.92 BHP.
4.     Using the RPM selection table below, Size X and Model Y is found.
5.     5.92 BHP exceeds the maximum continuous BHP rating of the 5.0 HP motor. The 7.5 HP motor is required.
6.     1020 RPM is within the range of the 7.5 HP drives.
7.     Using the 7.5 HP motor and drive, 3.5 turns open will achieve 1020 RPM.
1.100
1.050
                                     1.000
                                                                                                                               Sea Level
                                     0.950
                 Correction Factor
                                                                                                                               1000 ft
                                     0.900                                                                                     2000 ft
                                                                                                                               3000 ft
                                     0.850
                                                                                                                               4000 ft
                                     0.800                                                                                     5000 ft
                                                                                                                               6000 ft
                                     0.750                                                                                     7000 ft
                                                                                                                               8000 ft
                                     0.700
                                                                                                                               9000 ft
                                                                                                                               10000 ft
                                     0.650
                                     0.600
                                               40           50           60             70          80           90           100
                                                                          Air Temperature (ºF)
1.100
1.050
                                     1.000
                                                                                                                              Sea Level
                                     0.950
                 Correction Factor
                                                                                                                              305 Meter
                                     0.900                                                                                    610 Meter
                                                                                                                              914 Meter
                                     0.850
                                                                                                                              1219 Meter
                                     0.800                                                                                    1524 Meter
                                                                                                                              1829 Meter
                                     0.750                                                                                    2134 Meter
                                                                                                                              2430 Meter
                                     0.700
                                                                                                                              2743 Meter
                                                                                                                              3048 Meter
                                     0.650
                                     0.600
                                                   4.4   10           15.5      21        26.6                 32            38
                                                                         Air Temperature (ºC)
Sound Performance
ZF Indoor Sound Power Levels
                                                                                                     Sound Power, dB (10-12) Watts
    Size                          ESP           Blower                             1
                     CFM                                           Sound Rating                            Octave Band Centerline Frequency (Hz)
   (Tons)                        (IWG)
                                           RPM          BHP           dB (A)             63          125       250     500           1000     2000         4000    8000
   180 (15)          6000         1.0      1,080        4.6             91               88          90        90       87            85       81           81      76
   240 (20)          8000         1.0      1,020        6.6             86               85          85        83       82            82       78           75      70
  1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
     provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way
     of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
     in any other form than sound power level ratings.
Electrical Data
ZF180 - 240
ZF180-240 - High Static Drive
                                                          OD Fan   Supply
                              Compressors
                                                          Motors   Blower           Electric Heat Option                     Max Fuse2/
  Size                          (each)
                                                          (each)   Motor                                             MCA1     Breaker3
            Volt
 (Tons)                                                                                                             (Amps)      Size
                     RLA          LRA         MCC
                                                           FLA      FLA     Model      kW     Stages       Amps               (Amps)
                   C1   C2      C1   C2     C1   C2
                                                                            None       --        --         --        49         60
                                                                            E18       11.3       1         17.1       49         60
          380-3-50 18.6   14.5 100.0 90.5   26.0   20.3    2.1      6.3     E36       22.6       2         34.3       51         60
                                                                            E54       33.8       2         51.4       73         80
  180                                                                       E72       45.1       2         68.6       90        100
  (15)                                                                      None       --        --         --        49         60
                                                                            E18       13.5       1         18.7       49         60
          415-3-50 18.6   14.5 111.0 101.0 26.0    20.3    2.1      6.7     E36       26.9       2         37.4       56         60
                                                                            E54       40.0       2         56.2       79         80
                                                                            E72       53.8       2         74.9       84         90
                                                                            None       --        --         --        60         70
                                                                            E18       11.3       1         17.1       60         70
          380-3-50 20.7   20.0 110.0 110.0 29.0    28.0    2.1      8.2     E36       22.6       2         34.3       60         70
                                                                            E54       33.8       2         51.4       75         80
  240                                                                       E72       45.1       2         68.6       96        100
  (20)                                                                      None       --        --         --        60         70
                                                                            E18       13.5       1         18.7       60         70
          415-3-50 20.7   20.0 118.0 118.0 29.0    28.0    2.1      9.1     E36       26.9       2         37.4       60         70
                                                                            E54       40.0       2         56.2       82         80
                                                                            E72       53.8       2         74.9       87         90
                        THERMOSTAT                                                         CONTROL
                         TERMINALS                                                         TERMINAL
                                                                                            BLOCK
W1 W1
                                 W2
                                        1                                                     W2
                                                                                              Y1
                                 Y1
                                                                                              G
                                        2
                                 Y2                                                           OCC
                                                                                               P
                                 G
                                                                                              P1
                                  R
                                                                                              Y2             Smoke
                                                                                                             Detector
                                  C                                                            X
                                                                                               R
                             4                                                                        R    Jumper
                                                                                                                    3
                                 RC
                                                                                              SD
                                                                                                      SD
                                        5
                                                                                               C
                                 OCC                                                                  SD                24 VAC
                                        6                                                                               Class 2
                                  X                                                                   C
                         TERMINALS ON
                           A LIMITED
                          NUMBER OF
                         THERMOSTATS
                                                                                     Y
                                                                 X
                                                                                          FRONT
                                                          LEFT
                                            B                                                                                         C
                                                                                                                            B
                                                                     C                                                                                         D
        A                                                                                 A                                                          E
                                                 FRONT                                                                                                       )
                                                                                                                                                          80
                                                                                                                                    FRONT             ) (1 40)
                                                                                                                                                    4” 2
                                                                                                                                                4 (6 9”) (
                                                                                                                                              2     6
                                D                                                                                     F                     16 58 (
                                                                                                                                             1 7
ZF180-240 Unit Weights Imperial
   Size                    Weight (lbs.)   Center of Gravity 4 Point Load Location (lbs.)                                 6 Point Load Location (lbs.)
                Model
  (Tons)                Shipping Operating   X         Y       A       B     C       D                           A         B       C      D        E                F
 180 (15)        ZF       1929      1924    66.5      45.7    448     507   514    454                          293       317     345    350      322              297
 240 (20)        ZF       2579      2574     70        44     599     632   690    653                          395       410     426    464      447              431
ZF180-240 Unit Accessory Weights Imperial                                          ZF180-240 Unit Accessory Weights Metric
                                                    Weight (lbs.)                                                                              Weight (kg.)
               Unit Accessory                                                                      Unit Accessory
                                                Shipping         Operating                                                                  Shipping      Operating
                 Economizer                        165               160                                Economizer                            74.8             72.6
               Power Exhaust                       90                85                            Power Exhaust                              40.8             40.8
                Electric Heat1                     40                40                               Electric Heat1                          18.1             18.1
                            2
                 Gas Heat                          240               240                                Gas Heat2                            108.9             108.9
              Motorized Damper                     150               150                          Motorized Damper                            68                68
              Barometric Damper                    50                45                           Barometric Damper                           22.7             22.7
     Econ./Motorized Damper Rain Hood              60                55              Econ./Motorized Damper Rain Hood                         27.2             27.2
      Econ./Power Exhaust Rain Hood                95                90                   Econ./Power Exhaust Rain Hood                       43.1             43.1
                 Wood Skid                         220               220                                Wood Skid                             99.8             99.8
                  Roof Curb                        190               185                                Roof Curb                             86.2             86.2
     1. Weight given is for the maximum heater size available                        1. Weight given is for the maximum heater size available
        (54KW).                                                                         (54KW).
     2. Weight given is for the maximum number of tube heat                          2. Weight given is for the maximum number of tube heat
        exchangers available (8 tube).                                                  exchangers available (8 tube).
Unit Dimensions
RETURN AIR
SUPPLY AIR
                                                                              OUTDOOR AIR
                                                                              (Discharge)
                                                                              OUTDOOR AIR
                                                                              (Economizer)
RETURN AIR
SUPPLY AIR
                                                                               OUTDOOR AIR
                                                                               (Discharge)
                                                                               OUTDOOR AIR
                                                                               (Economizer)
                                                                                                                                                         EVAPORATOR
                                                                                                                                                         SECTION
                                                                                                                                                                 DOT PLUG
                                                              1026                                                                                               (For pressure
                                                            (40-3/8")                                                                                            drop reading)
                                                                                                                                                                 FILTER
                                                                                                                                                                 ACCESS
                                                                                    SUPPLY
                                                                                    AIR
                                                                                                  RETURN
                                                                                                  AIR
                                                         COMPRESSOR
                                                                                                                     OUTDOOR
                                                         ACCESS
                                                                                                                     AIR
                                                                                                                                                       1029
                                                          SUPPLY AIR
                                                                                                                                                     (40-1/2")
                                                          ACCESS                 474
                                                                               (18-5/8")
                                                                                                                                                         1" NPT FEMALE
                        Dimensions listed are for side                                  130                                                              COND. DRAIN
                                                                    RETURN AIR        (5-1/8")                                                           CONNECTION
                        duct flange openings; see                   ACCESS
                                                                                                   705
                                                                                                 (27-3/4")
                                                                                                                                           OUTDOOR AIR
                        Field Accessories for Side                                                           ZF180 727 (28-5/8”)           COMPARTMENT
                        Duct Flange Kit.                                   REAR                              ZF240 1006 (39-5/8")          ACCESS
VIEW
NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts.
                                                        ECONOMIZER
                                                        MOTORIZED
           SUPPLY AIR     POWER EXHAUST                 DAMPER
           COMPARTMENT    RAIN HOOD                     RAIN HOOD
                          (on Return Air Compartment)   (on Outdoor Air Compartment)        ECONOMIZER / MOTORIZED DAMPER
                                                                                            AND POWER EXHAUST RAIN HOODS
                                                                                                                   FIXED
                                                                                                                   OUTDOOR AIR
                                                                                                                   INTAKE HOOD
                                                                                                                   (located on
                                                                                                                   Return Air
                                                                                  930                              Compartment)
                                                                                (36-5/8”)
                                                                                                                                              25 (1“) CONDENSATE
                                                                                                       410                                    DRAIN
                                                                                                     (16-1/8”)                                (Must be trapped)
127 (5”)
                                                                                                716                                   2337
                                                                                             (28-3/16”)                               (92”)
                                                                        DETAIL “Y”
                                                                  UNIT WITH RAIN HOODS
Unit Clearances And Rainhood Dimensions (15 & 20 Ton)