Vicinity Map: General Notes

This document provides a schedule of loads for an electrical panelboard listing 22 circuits. It details the load description, number of loads, voltage, watts, amps, circuit breaker rating, conduit, and wire size for each circuit. The largest loads are a range rated at 3500 watts and water heaters also rated at 3500 watts. Power is provided through a 175 amp, 2 pole main circuit breaker and the panelboard enclosure is NEMA 3R rated.

Uploaded by

Nefritiri Blance
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views1 page

Vicinity Map: General Notes

This document provides a schedule of loads for an electrical panelboard listing 22 circuits. It details the load description, number of loads, voltage, watts, amps, circuit breaker rating, conduit, and wire size for each circuit. The largest loads are a range rated at 3500 watts and water heaters also rated at 3500 watts. Power is provided through a 175 amp, 2 pole main circuit breaker and the panelboard enclosure is NEMA 3R rated.

Uploaded by

Nefritiri Blance
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PANELBOARD ( LP )

SCHEDULE OF LOAD
USE 2 - 125MM THHN
CKT VOLTS WATTS AMPS CB CONDUIT + 1-30mm TW(G)
1 , 230V, 60Hz.
No. LOAD DESCRIPTION NO. OF LOADS RATING POWER SERVICE ENTRANCE WIRE IN 40 MM RSC
1 LIGHTING OUTLET 19 x 100 / 9 x 50 230 2350 11.52 20AT THHN WIRE 20
2 LIGHTING OUTLET 10 x 100 / 11 x 50 230 1450 7.61 20AT THHN WIRE 20
3
4
LIGHTING OUTLET
LIGHTING OUTLET
9 x 100 / 19 x 50
8 x 100 / 19 x 50
230
230
2850
1750
9.35
8.69
20AT
20AT
THHN
THHN
WIRE
WIRE
20
20
M
5 CONVENIENCE OUTLET 11 x 180 230 1890 10.17 20AT THHN WIRE 20
6 CONVENIENCE OUTLET 7 x 180 230 1260 5.48 20AT THHN WIRE 20 175 A, 2P MCB
7 CONVENIENCE OUTLET 10 x 180 230 1800 9.39 20AT THHN WIRE 20 NEMA 3R ENCLOSURE
8 CONVENIENCE OUTLET 7 x 180 230 1260 7.03 20AT THHN WIRE 20 USE 2 - 60MM THHN
9 REFRIGERATOR 1 x 500 230 500 2.17 20AT THHN WIRE 20 + 1-30mm TW(G)
10 WASHING MACHINE 1 x 1500 230 1500 6.52 30AT THHN WIRE 20 WIRE IN 50 MM PVC
11 RANGE 1 x 3500 230 3500 15.22 30AT THHN WIRE 20 2- 14mm 1- 8.00mm
12 SPLIT TYPE A.C.U 1 x 2300 230 2300 10 30AT THHN WIRE 20 THHN WIRE IN 32mm RSC 175 AT
13 SPLIT TYPE A.C.U 1 x 2300 230 2300 10 30AT THHN WIRE 20 20A 20A
14 ACU 1 x 2300 230 2300 10 30AT THHN WIRE 20 L.O. 1 2 L.O.
230 THHN WIRE
MTS 20A 20A
15 SPLIT TYPE A.C.U 1 x 2300 2300 10 30AT 20
60AT 60AT L.O. 3 4 L.O.
16 ACU 1 x 2300 230 2300 10 30AT THHN WIRE 20 20A 20A
17 ACU 1 x 2300 230 2300 10 30AT THHN WIRE 20 C.O. 5 6 C.O.
30A 30A
18 ACU 1 x 2300 230 2300 10 20AT THHN WIRE 20 C.O. 7 8 C.O.
19 WATER HEATER 1 x 3500 230 13.04 THHN WIRE 30A 30A
3500 20AT 20
230 2- 14mm 1- 8.00mm REF 9 10 W.M.
20 WATER HEATER 1 x 3500 3500 13.04 20AT THHN WIRE 20 30A 30A
21 WATER HEATER 1 x 3500 230 3500 13.04 20AT THHN WIRE 20 THHN WIRE IN 32mm PVC RAN. 11 12 A.C.U. VICINITY MAP
30A 30A 2
22 WATER HEATER 1 x 3500 230 3500 13.04 20AT THHN WIRE 20 LPE E3 E3
A.C.U. 13 14 A.C.U. SCALE NOT TO SCALE
23 WATER HEATER 1 x 3500 230 3500 13.04 20AT THHN WIRE 20 30A 20A
24 BOOSTER PUMP 1 x 1500 230 1500 6.52 20AT THHN WIRE 20 60 AT A.C.U. 15 16 A.C.U.
THHN WIRE
20A 20A
25 LPE - 230 5520 24 60AT 32 20A 20A
TW WIRE A.C.U. 17 18 A.C.U.
20A 20A
- 230 - - 20AT - - C.O. 2 1 L.O.
26 SPARE 20A 20A W.H. 19 20 W.H.
20A 20A
60,730 258.87 THHN WIRE C.O. 4 3 L.O.
TOTAL OF LOADS 175AT TW WIRE 40 20A 20A W.H. 21 22 W.H.
20A 20A
PANELBOARD ( LPE )
ACU 6 5 REF. COMPUTATION OF ELECTRICAL DESIGN ANALYSIS
W.H. 23 24 PUMP
60A 20A
SCHEDULE OF LOAD LPE 25 26 SPARE A. TOTAL LOAD
CKT VOLTS WATTS AMPS CB CONDUIT a.) General Lighting and Receptacle load
No. LOAD DESCRIPTION NO. OF LOADS RATING GROUND (FROM LOAD SCHEDULE) = 14,610VA
1 LIGHTING OUTLET 6 x 100 230 600 2.61 20AT 20
2 LIGHTING OUTLET 5 x 100 230 500 2.17 20AT
THHN WIRE
THHN WIRE 20 APPLICATION OF DEMAND FACTOR
3 CONVENIENCE OUTLET 4 x 180 230 720 3.13 20AT
THHN WIRE
THHN WIRE 20 GROUND First 3,000 Volt-Amperes @ 100% D.F. = 3,000VA
4 CONVENIENCE OUTLET 5 x 180 230 900 3.91 20AT
THHN WIRE
THHN WIRE 20 Remainder @ 35% D.F. (11,610x35) = 4,063.5VA
5 REFRIGERATOR 1 x 500 230 500 2.17 20AT THHN WIRE
THHN WIRE
20 SUBTOTAL = 7,063.5VA
THHN WIRE
6 SPLIT TYPE A.C.U 1 x 2300 230 2300 10 20AT THHN WIRE 20
SUB-TOTAL 5520 24 60AT
THHN WIRE
32 SINGLE LINE RISER DIAGRAM b.) ACU Load @ 100% D.F.
- TW WIRE 1 7 Units 1.5HP ACU, 1 Phase @2300VA = 16,100VA
SCALE: NTS
E3 E3
c.) Water Heater Load @ 40% D.F.
5 Units of Water Heater @ 3.5kVA
(15,000x.40) = 7,000VA
GENERAL NOTES
d.) Range Load @ 100% D.F.
1. ALL PLANS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PLANS & SPECIFICATIONS. 7. ALL ELECTRICAL WORKS SHALL UNDER THE DIRECT SUPERVISION 1 Unit @ 3.5kVA (3,500VA) = 3,500VA
2. THE ELECTRICAL INSTALLATION HEREIN SHALL BE DONE IN ACCORDANCE WITH THE OF A DULY LICENSED ELECTRICAL ENGINEER.
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE 8. USE ADEQUATE GROUNDING SYSTEM AND PROVIDE IF NECESSARY ADDITIONAL GROUND e.) Other Loads
RODS TO MEET THE REQUIRED GROUND RESISTANCE.
EXISTING LOCAL ORDINANCES AND REQUIREMENTS OF THE 1-Unit Booster Pump @ 43 Hp. 220V, 1Phase (1,500VA) = 1,500VA
LOCAL POWER COMPANY. 9. ALL CONDUITS SHALL BE PROTECTED AGAINST DAMAGES BY THE ENTRANCE OF WATER 1-Unit Refrigerator Appliance Load @ 500VA = 500VA
AND FOREIGN MATERIALS DURING CONSTRUCTION AND ALL OF CONDUITS SHALL PLUGGED
3. THE JOB SHALL BE DONE IN THE MOST THOROUGH PROMPT AND WORKMANLIKE 1-Washing Machine @ 1,500VA = 1,500VA
TO ECLUDE MOISTURE AND DUST IMMEDIATELY AFTER THE CONDUITS ARE PLACED.
MANNER UTILIZING STANDARD TOOLS, EQUIPMENTS, METHODS AND GOOD ENGINEERING
PRACTICE. THE JOB SHALL BE DONE COMPLETE IN ALL ASPECTS AS REQUIRED 10. ALL CONDUIT BENDS SHALL BE OF MINIMUM BENDING RADIUS AND CONFORM IN SUBTOTAL = 30,100VA
PER PLANS, SPECIFICATIONS AND READY FOR OPERATIONS. ACCORDANCE WITH THE CODES. TOTAL NET COMPUTED LOAD = 37,163.5VA
4. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO PRESENT A GENERAL LAYOUT 11. WALL SWITCHES SHALL BE RATED 15 AMP. 300 VOLTS TUMBLER TYPE AND CONVENIENCE
AND BROAD OUTLINE DESCRIPTION OF THE PROJECT BUT NOT NECESSARILY INDICATE OUTLETS SHALL BE OF GROUNDING TYPE 3-WIRE 230 VOLTS. B. SERVICE ENTRANCE CONDUCTORS
DESCRIBE THE ACTUAL LOCATIONS, LEVELS, AND DISTANCES OF EQUIPMENT. THE TOTAL FULL LOAD CURRENT (37,163.5VA / 230V) = 161.58 Amperes
12. UTILIZE PULL BOXES BUT DIMENSIONS SHALL BE COMPUTED BASED ON THE CODE
CONTRACTOR IS HEREBY REQUIRED TO MAKE SUCH ADJUSTMENT AS LOCATIONS, LEVELS, =161.58 + 0.25(10) = 164.08 Amperes
REQUIREMENTS.
AND DISTANCES ARE GOVERNED BY ACTUAL CONDITION.
12. ALL BEDROOMS & GUEST ROOM ARE MULTI-POINT WATER HEATER.
5. ALL ELECTRICAL FIXTURES, MATERIALS, DEVICES & EQUIPMENTS USE: 2-60mm2 THNN Copper Wire 1-14mm2 TW copper wire in 40mm RSC pipe
TO BE USED SHALL BE BRAND NEW & OF THE APPROVED TYPE 14. MOUNTING HEIGHT OF DEVICES:
FOR ITS SPECIFIC PURPOSE, USE & LOCATION. a. CONVENIENCE OUTLET: 0.30 FROM FFL C. SERVICE EQUIPMENT
6. ALL CONDUIT SHALL BE CONCEALED INSIDE THE CEILING, FLOOR AND WALLS. b. LIGHT CONTROL SWITCHES: 1.40M FROM FFL Maximum Current Rating of Protective Device by using:
INVERSE TIME CIRCUIT BREAKER
161.58 + 1.50 (10) = 176.58 Amperes

USE: 175 AT / 225 AF 2-Pole 240V molded case circuit breaker (bolt-on-type)

REPUBLIC ACT NO. 9266 OWNER: PROJECT TITLE: SHEET CONTENT: FILE NAME / DATE: SHEET NO:
ARTICLE III, SECTION 20, CHAPTER 4
(SEAL, ISSUANCE, AND USE OF SEAL)
YOKOHAMA (2) 2017
DANTE G. TOLENTINO PROPOSED TWO-STOREY
ELECTRICAL ENGINEER
DRAWINGS AND SPECIFICATIONS DULY SIGNED, STAMPED OR
SEALED, AS INSTRUMENTS OF SERVICE, ARE THE INTELLECTUAL
PROPERTIES AND DOCUMENTS OF THE ARCHITECT, WHETHER RESIDENTIAL HOUSE AUGUST 2017
E3
THE OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. INTERHOUSE AS-SHOWN
IT SHALL BE UNLAWFUL FOR ANY PERSON, WITHOUT THE SOUTH CORPORATION
CONSENT OF THE ARCHITECT OR AUTHOR OF THE SAID
DOCUMENTS, TO DUPLICATE OR TO MAKE COPIES OF SAID
ADDRESS: CADD BY: CHECKED BY:
PRC No.:
PTR No.:
0002300
2800812 DATE : 1.03.17 PLACE : BATS. CITY
DOCUMENTS FOR USE IN THE REPETITION OF AND FOR OTHER
PROJECTS OR BUILDINGS, WHETHER EXECUTED PARTLY OR IN
WHOLE.
BLOCK 16, LOT 27, YOKOHAMA ST.
TALON, LAS PINAS, METRO MANILA NBM 2017 NBM 3 3