SPEC AC90 CU
AC90
No. 14 to 2 AWG, Copper Conductors, 600V / -40ºC MIN, 90ºC MAX, XLPE (type RW90)
1
2
3
4
5
CONSTRUCTION:
Solid copper circuit conductors, (No. 8 AWG and larger are stranded) with low temperature XLPE insulation (RW90),
copper bonding conductor, twisted assembly wrapped with a paper binder and covered with aluminum interlocking
armour. Rated 600 volts.
1. Copper Conductor
2. XLPE Insulation
3. Bare Copper Bonding Conductor
4. Oil Impregnated Kraft Paper Binder
5. Aluminum Interlock Armour
CONDUCTOR COLOURS:
• For 2 conductor constructions: black and white circuit conductors plus a bare copper bonding conductor.
• For 3 conductor constructions: black, red and white circuit conductors plus a bare copper bonding conductor.
• For 4 conductor constructions: black, red, blue and white circuit conductors plus a bare copper bonding conductor.
APPLICATIONS AND FEATURES:
Southwire’s AC90 is designed for exposed and concealed wiring such as ventilated cable trays and other dry locations,
where the maximum conductor temperature will not exceed 90°C. Meets CSA cold bend and impact tests at -40ºC.
SPECIFICATIONS:
Southwire’s AC90 cables meet or exceed the following requirements:
• CSA Spec. C22.2, No. 51 - Armoured Cables
• CSA File Listing: LL90458
• CSA -40°C Cold Temperature Rating
Southwire Canada Company | 5705 Cancross Court Suite 100 | Mississauga, ON L5R 3E9 | www.southwire.ca
Copyright © 2018 Southwire Company, LLC. All Rights Reserved.
AC90CU_326 (18-03) Rev 6.00
SPEC AC90 CU
SPECIFICATIONS
Conductor Bare Approximate Approximate Net Allowable Amps 30°C
Bonding Diameter Cable Weight Ambient in Conduit **
Size Insulation Thickness Conductor
(AWG # of Size
or kcmil) Conductors inches mm (AWG)* inches mm lb/1000ft kg/km 60°C 75°C 90°C
14 2 0.030 0.76 14 0.452 11.48 90 134 15* 20* 25*
12 2 0.030 0.76 14 0.486 12.34 111 165 20* 25* 30*
10 2 0.030 0.76 12 0.528 13.41 148 220 30* 35* 40*
14 3 0.030 0.76 14 0.475 12.07 109 162 15* 20* 25*
12 3 0.030 0.76 14 0.508 12.90 137 204 20* 25* 30*
10 3 0.030 0.76 12 0.554 14.07 188 280 30* 35* 40*
14 4 0.030 0.76 14 0.530 13.46 130 193 15* 20* 25*
12 4 0.030 0.76 14 0.544 13.82 165 246 20* 25* 30*
10 4 0.030 0.76 12 0.620 15.75 244 363 30* 35* 40*
3 3 0.045 1.143 6 1.038 26.36 805 1198 85 100 115
† Allowable ampacities are for general use as specified by the 2018 Canadian Electrical Code, Table 2
* See the 2018 Canadian Electrical Code Rule 14.104(2) for details.
Southwire Canada Company | 5705 Cancross Court Suite 100 | Mississauga, ON L5R 3E9 | www.southwire.ca
Copyright © 2018 Southwire Company, LLC. All Rights Reserved.
AC90CU_326 (18-03) Rev 6.00