1. The document provides sample calculations for estimating the power requirements of a PLC system including a central controller and remote input/output (RIO) panels. 2. For a central controller, the power needs of individual components like the CPU, CP, and OLM are summed to calculate the total load of 57VA. 3. For a RIO panel powering IO cards, sensors, and modules, the background current draw and load of each component type is considered to calculate a total VA requirement of 388.81VA.

Uploaded by

Arunava Basak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
180 views1 page

Basak, Arunava IN CCU MT: From: Sent: To: Subject

1. The document provides sample calculations for estimating the power requirements of a PLC system including a central controller and remote input/output (RIO) panels. 2. For a central controller, the power needs of individual components like the CPU, CP, and OLM are summed to calculate the total load of 57VA. 3. For a RIO panel powering IO cards, sensors, and modules, the background current draw and load of each component type is considered to calculate a total VA requirement of 388.81VA.

Uploaded by

Arunava Basak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Basak, Arunava IN CCU MT

From: Basak, Arunava IN CCU MT


Sent: Wednesday, February 04, 2015 1:45 PM
To: Basak, Arunava IN CCU MT
Subject: FW: NMDC- SMS -UPS sizing calculation

Sample calculation for PLC – Central Controller and RIO load sizing. 
 
PLC: 
Net
Per Unit Qty
Item Load
(VA) (nos)
(VA)
PLC 1.2 GAS CLEANING & PRIM DEDUST SYSTEM
Central Controller 57 1 57

Description Qty Unit VA Requirement Total VA


CPU 417-5H 2 1.9A @ 5V for Backplane bus + 33.4 VA
150mA @24V for Each DP interface*2 =
16.7 VA
CP 443-1 2 1.4A @ 5V for backplane bus = 7 VA 14 VA
OLM 2 Power consumption 0.2A @ 24V = 4.8 9.6 VA
VA
Total 57 VA

RIO:
1 PLC 5.0 BOF PUMPHOUSE
1.2 BOF PH - E - RIO1 388.8096 1 388.8096

Building
PLC RIO Panel Total IO
No.
Cards SITOP IM DO DO Non- Counter DP Total VA
considered pair Bundle DI Relay Relay AI RTD AO FDI FDO FAI module OLM Coupler Required
PLC 5.0 BOF PH - E - RIO1 11 18 2 2 9 4 3 1 1 388.810
2X15.6 + 9X4.3104 + 4X63.84 + 3X8.544 + 1X6.624 + 1X31.2 = 388.8 VA

Max. Input Current


for backplane bus
Name of the component (Self) A @ 24V Max. Input Current (Load) A Total VA required Remarks
IM Bundle 0.65 15.6 650mA @ 24V 0.65 x 34 = 15.6 VA
=16(nos. of channel)*0.8(20% spare
channel)*7mA(consumption per channel) 90mA @ 24V for backplane bus+ 7mA @24V
DI 0.09 =0.0896A 4.3104 per channel
100mA @24V for backplane bus + 20mA
DO Non-Relay 0.1 0.256 8.544 @24V per channel
100mA @24V for backplane bus + 200mA
DO Relay 0.1 2.56 63.84 @24V per channel
20mA @24V for backplane bus + 40mA @24V
AI 0.02 0.256 6.624 per channel
240mA @24V for backplane bus + 40mA
RTD 0.24 0.256 11.904 @24V per channel
350mA @24V for backplane bus + 40mA
AO 0.35 0.256 14.544 @24V per channel
350mA @24V for backplane bus + 10mA
FDI 0.45 0.192 15.408 @24V per channel
100mA @24V for backplane bus + 150mA
FDO 0.1 1.2 31.2 @24V per channel
150mA @24V for backplane bus + 40mA
FAI 0.15 0.192 8.208 @24V per channel
150mA @24V for backplane bus + 9mA @24V
Counter module 0.15 0.0576 4.9824 per channel
DP Coupler 1 24 1A @24V
Y-Link 1 24 1A @24V
 