SHAKING TABLE TEST OF A REDUCED-SCALE STRUCTURE WITH COPPER-
BASED SMA ENERGY DISSIPATION DEVICES
Article
CITATIONS READS
5 208
5 authors, including:
Rubén Boroschek María Ofelia Moroni
University of Chile University of Chile
110 PUBLICATIONS 860 CITATIONS 44 PUBLICATIONS 483 CITATIONS
SEE PROFILE SEE PROFILE
Mauricio Sarrazin
University of Chile
44 PUBLICATIONS 364 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
ASSESSMENT OF GROUND MOTION AND CORRELATION WITH DAMAGE IN BUILDINGS, 2010 CHILE EARTHQUAKE View project
B Isolation View project
All content following this page was uploaded by Mauricio Sarrazin on 05 January 2015.
The user has requested enhancement of the downloaded file.
Proceedings of the 8th U.S. National Conference on Earthquake Engineering
April 18-22, 2006, San Francisco, California, USA
Paper No. 1003
SHAKING TABLE TEST OF A REDUCED-SCALE STRUCTURE WITH COPPER-
BASED SMA ENERGY DISSIPATION DEVICES
M. Cerda1, R. Boroschek2, G. Farías1, O. Moroni3 and M. Sarrazin4
ABSTRACT
A series of pullback and shaking table tests were performed for evaluating the
seismic performance of (1) a scale model of a three-story steel rigid frame
structure and (2) the same model equipped with shape memory alloy (SMA)
dampers. The dampers consisted of wires made of a copper, aluminum and
beryllium alloy, located as bracings at each level. The Sylmar, Kobe, Taft, El
Centro and Llolleo scaled earthquake records, as well as white noise motion were
used as input for the shaking table tests. Acceleration at different levels,
deformation and force at the dampers were registered. The inclusion of Cu-Al-Be
dampers increased the damping ratio from 0.59% in the bare structure to 5.95%
in the braced one. At the same time the structure stiffness increased making the
first natural frequency to change from 2.5 Hz to 3.7 Hz. The net effect of these
two factors was a reduction of peak acceleration and peak displacements to near
60% of the bare case.
Introduction
The Shape Memory Alloys (SMA) are metallic alloys that can undertake large strains,
and recover their initial configuration after unloading (named superelastic effect) or by heating
(named shape memory effect), without permanent deformation. Energy is dissipated during the
loading-unloading process, fact that makes them suitable for its use as seismic dissipation
devices.
Although Nitinol, a binary alloy of nickel and titanium, have received most of the
commercial attention, especially because of biomedical applications, copper-based alloys may
be more attractive for seismic applications because they are less expensive and easier to
1
Graduate Research Assistant, Dept. of Civil Engineering, University of Chile
2
Assistant Professor, Dept. of Civil Engineering, University of Chile
3
Associate Professor, Dept. of Civil Engineering, University of Chile
4
Professor, Dept. of Civil Engineering, University of Chile
machine. In fact, due to the hardness of Nitinol, machining large bars is difficult and special
tools are required.
Thorough reviews concerning potential uses of Ni-Ti in earthquake engineering can be
found in DesRoches and Smith (2004a) and Wilson and Wesolowsky (2005). Both include state
of the art information about modeling, design and testing of devices as well as theoretical and
laboratory studies on their use in buildings and bridges. Janke et al., (2005) discuss Ni-Ti and
Fe-Mn-Si SMA potential applications on civil engineering. With respect to copper-based SMA
alloys most of the literature covers aspects of material sciences, material models and mechanical
behaviour of tertiary alloys such as Cu-Zn-Al, Cu-Al-Ni and Cu-Al-Be. Studies on mechanical
properties and energy dissipation capacity of copper-based alloys can be found in Witting and
Cozzarelli (1992) and Gillet et al. (1994). More recently, Casciati and Faravelli (2004) and Torra
et al. (2005) studied Cu-Al-Be alloy towards its exploitation in passive control devices.
Cyclic behaviour depends on the type of alloy, the thermo-mechanical processing which
influences the grain size; the temperature at which the material is used in relation to the phase
transformation temperatures, dimension of the test sample, loading history and loading rate. For
instance, DesRoches et al. (2004b) found that Ni-Ti wires show higher strength and damping
compared with bars and that increased loading rates lead to decreases in equivalent damping.
In this study, a series of experiments were conducted on a scale model of a three-storey
moment resistant steel frame building. Damping devices based on austenite Cu-Al-Be wires
were installed in the longitudinal direction as braces. Pull-back and shaking table tests were
performed on the bare frame structure and on the braced one. The main objective was the
evaluation of the effectiveness of Cu-Al-Be dampers during severe seismic loads.
Characteristics of SMA Braces
Cu-Al-Be shape memory alloy wires (φ = 0.5 mm) were selected as energy dissipation
devices. Material was produced by Trefimetaux, France. Previously, in order to characterize
their actual behavior, sinusoidal displacements were applied to pre-tensioned austenite wire
samples that were submitted to different thermal treatment and, therefore, had different grain
sizes. Wires were heated at 717ºC during different periods of time, followed by water quenching
and aging process at 88ºC for 20 h and at 96ºC for 4 h. For comparison, an untreated wire was
also tested.
Tests were performed at 1 Hz with displacement amplitude of 3.2 mm on wire samples
that were 130 mm long. Strains were measured with a 2.5 cm length extensometer. Table 1
shows some results from the tests as secant stiffness, energy loss per cycle ED, internal friction,
and maximum strain attained. The secant stiffness is the difference between the maximum and
minimum load divided by the difference between the maximum and minimum deformation. The
energy loss is the area enclosed by the hysteresis loop. The internal friction is expressed as
ED
ξ= (1)
2π * A
where A is the area under the loading branch of the curve. Heating softens the wires and the
energy loss increases. Clearly, the untreated material is much more rigid than the treated one,
and in the latter case, less cycles were needed to stabilize the stress-strain loops. Based on these
results the wires installed in the structure were heated at 717ºC for 225 sec, followed by water
quenching and aging as explained earlier.
Table 1. Characteristics of Cu-Al-Be wires
Time of heating Secant Energy loss Internal Maximum
at 717ºC (sec) stiffness ED friction strain
(kN/m) (N mm) (%) (%)
0 35.42 29.9 2.1 3.82
90 24.88 38.7 5.2 6.08
135 25.36 37.1 4.9 6.50
180 27.95 36.9 5.3 8.36
225 21.48 41.0 4.5 8.40
Model Description
Dimensions of the model are 120 cm high, 70 cm long and 42 cm wide; the steel
columns (3 x 0.4 cm) are bolted to the beams which are welded to the floor slab. The model was
intended to work in the longitudinal direction, so four steel wires (φ =0.5 mm) were installed at
each story in the transverse direction to avoid torsion. Each floor weights 180 N which gives a
total weight of 540 N, [Cerda, 2005].
Four SMA dampers were installed at each level. Each brace consists of a steel channel
shape 15 x 15 x 1.5 mm, 45 cm long, and a Cu-Al-Be wire (φ = 0.5 mm) that is 40 cm long. The
steel angle has at one extreme a longitudinal 3/8’’ bolt (φ = 9.19 mm) that serves to tension the
damper by means of a nut. The wire is fixed to the steel angle and to the floor slab through a
transverse 1/16’’ bolt (φ = 1.53 mm).
Instrumentation and Experimental Results
Twelve accelerometers that measure longitudinal and transverse accelerations were
installed in the bare structure. Additionally, in the damped structure, eight load-cells and eight
potentiometers were installed to measure forces and axial deformations in each damper located
at the first and second floor. Figure 1 shows the model, the damper tension mechanism and
instrumentation details.
Three pull-back tests were first performed to the bare structure to obtain the modal
parameters in the longitudinal direction. Shaking table tests were then performed using 5
minutes of white noise motion and amplitude-scaled records from Sylmar 1994 (0.36g peak
acceleration), Kobe 1995 (0.23g peak acceleration), Taft 1952 (0.36g peak acceleration), El
Centro 1940 (0.21g peak acceleration) and Llolleo 1985 (0.24g peak acceleration) earthquakes.
The test series ended with three pull back tests followed by 25 minutes of low amplitude white
noise motion. The long duration white noise motion was intended for fatigue evaluation. A
similar sequence was used for the damped model. All tests were performed at room temperature
(≈ 20ºC).
The shake table is a MOOG system, Model 6DOF2000E, with a load capacity of 10 kN
and approximately 25 cm of displacement capacity in three directions. Longitudinal as well as
simultaneous longitudinal and vertical components were applied.
damper tension mechanism
model and dampers load cell and potenciometer
Figure 1. Steel frame scaled model and instrumentation
The CuAlBe wires were pre-stressed with a tensile force of 30 N. This was performed at
the beginning of the tests; stressing first the wires on the east side and then those on the west
side. This sequence produced non uniform pre-strain, being them some what larger at the west
side. For each test the initial and final tensions were registered and some relaxation was noticed,
but due to the test procedures no action could be taken to restore the original 30 N.
Table 2 shows the frequencies and equivalent damping ratios obtained for the bare model
from the pull-back tests performed before and after shaking table tests. Analyses to obtain
natural frequencies and damping ratios were conducted using the Ibrahim Time Domain Method
[Ibrahim and Mikulcik, 1977]. Differences in frequencies are very small for both set of test.
Damping, although rather low, shows a larger percentage variation in the first and second mode
that may be related to relaxation of some of the connections.
Table 3 shows the first fundamental frequency and equivalent damping ratio for the
damped structure obtained from the pull-back tests, prior and post shaking table tests. In this
case there is a range of frequencies indicating non-linear behavior of the wires. The logarithm
decrement method was used to determine an average damping.
Table 2. Frequencies and damping ratio in bare model (pull-back tests)
Mode Prior to shake table test Post shake table test
Frequency Damping Frequency Damping
[Hz] [%] [Hz] [%]
First 2.49 0.59 2.50 0.40
Second 7.25 0.35 7.20 0.54
Third 10.95 0.44 10.90 0.45
Table 3. First mode frequency and damping ratio in braced model
Prior to shake table test Post shake table test
Frequency Damping Frequency Damping
[Hz] [%] [Hz] [%]
3.35-3.71 5.63 3.45-3.73 4.44
Experimental data from shaking table tests shows the effectiveness of the SMA dampers
in vibration reduction. Figure 2 compares peak accelerations and peak relative displacements in
each floor for the bare and braced structure for all applied records. Calculation of the relative
displacements included (1) filtering the absolute acceleration records at each floor to eliminate
noise, (2) obtaining relative acceleration at each floor by subtracting the shake table absolute
acceleration record, (3) integrating the relative acceleration records twice, and (4) comparing the
drifts with the horizontal components of the braces’ strains, that were measured directly with
potentiometers installed at the first and second floors. Llolleo and Kobe records caused the
largest relative displacements and accelerations. Significant reductions were apparent for all
cases. The coincidence of peak accelerations and absolute displacements at level 0 (shake table
level) for the bare and braced structures, respectively, confirms the similitude between the
motions applied to each cases.
Figure 3 shows the hysteresis cycles for all dampers located at the first and second floor
during the scaled Sylmar record. Some wires in the first floor underwent deformation amplitudes
up to 15 mm, which corresponds to approximately 3.75% strain. Stiffness of the wires at the east
side differed from those of the west side. Due to the procedure followed to pre-stress the wires, it
is believed that differences in the pre-strain from one side to the other may explain some
variation in stiffness. In fact, Dolce et al. [2000] tested Nitinol wires and bars for several
different conditions and established, among other conclusions, that the secant stiffness varies
depending on the pre-strain.
Figure 4 shows the wires maximum and minimum load and the maximum horizontal
component deformation attained at the first and second floor for different earthquake records
and the initial pull-back test. The first two bars correspond to wires located at the east side of the
structure (es and en) while the last two correspond to the wires located at the west side of the
structure (ws and wn). The largest loads and deformations were registered at the first floor for
Sylmar and Llolleo earthquakes. The 30 N initial load was insufficient to avoid complete loss of
preload at the first floor during Llolleo earthquake.
Peak Acceleration [g]- Llolleo Peak Displacements [cm] - Llolleo
0,0 1,0 2,0 3,0 4,0 5,0 6,0
0,0 0,2 0,4 0,6 0,8 1,0 1,2 1,4
3
3
2 2
Story
Story
1 1
0 0
Peak Acceleration [g] - Kobe Peak Displacements [cm] - Kobe
0,0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 0,0 1,0 2,0 3,0 4,0 5,0 6,0
3 3
2 2
Story
Story
1 1
0 0
Peak Acceleration [g] - Sylmar Peak Displacements [cm] - Sylmar
0,0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 0,0 2,0 4,0 6,0 8,0 10,0 12,0
3 3
Story
2 2
Story
1 1
0 0
Peak Acceleration [g] - Taft Peak Displacements [cm] - Taft
0,00 0,20 0,40 0,60 0,80 1,00 1,20 1,40 0,0 1,0 2,0 3,0 4,0 5,0 6,0
3 3
2 2
Story
Story
1 1
0 0
Peak Acceleration [g] - El Centro Peak Displacements [cm] - El Centro
0,0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 0,0 1,0 2,0 3,0 4,0 5,0 6,0
3 3
2 2
Story
Story
1 1
With SMA bracings
0 0 Bare frame
Figure 2. Peak acceleration and displacement comparisons.
Figure 3. Damper stress-strain relationships for Sylmar earthquake
nd nd
Maximum load - 2 story Minimim load - 2 story
70 70
60 60
50 50
es
Load [N]
Load [N]
40 40 en
30 30 ws
wn
20 20
10 10
0 0
pull-back Sylmar Kobe Taft El Centro Llolleo pull-back Sylmar Kobe Taft El Centro Llolleo
st st
Maximum load - 1 story Minimum load - 1 story
70 70
60 60
50 50
es
Load [N]
Load [N]
40 40 en
30 30 ws
20 wn
20
10 10
0 0
pull-back Sylmar Kobe Taft El Centro Llolleo pull-back Sylmar Kobe Taft El Centro Llolleo
st nd
1 story - maximum horizontal component wire deformation 2 story - maximum horizontal component wire deformation
9 9
Deformation [mm]
es
Deformation [mm]
6 6 en
ws
wn
3 3
0 0
pull-back Sylmar Kobe Taft El Centro Llolleo pull-back Sylmar Kobe Taft El Centro Llolleo
Figure 4. Wire loads and deformations at first and second story.
Figure 5 shows the wires secant stiffness as function of the pre-tensile load. Stiffness
increases for lower pre-stress loads. Differences between wires are apparent indicating some
problems with the thermal treatment applied. After the application of 25 minutes of white noise
all wires showed fatigue problems, as it could be expected, and a dramatic reduction of stiffness.
Some of them broke when tension loads were applied again.
20
18 2º es
Secant stiffness [Gpa]
16
2º en
14
2º ws
12
2º wn
10
1º es
8
1º en
6
1º ws
4
1º wn
2
0
0,00 5,00 10,00 15,00 20,00 25,00 30,00 35,00 40,00
pre tensile load [N]
Figure 5. Wires secant stiffness as function of tensile loads
Conclusions
The experimental behaviour of a scale model of a three-storied structure which includes
copper-based dissipation devices has been presented. The model corresponds to a rigid-framed
steel structure with CuAlBe dissipation devices located as bracing at each story. The weight of
the model was 540 N and the volume of the braces was 0.942 cm3. Three pull-back tests were
first performed to the bare structure to obtain the three modal shapes in the longitudinal
direction. Shaking table tests were then performed using 5 minutes white noise motion.
Afterwards scaled records from Sylmar, Kobe, Taft, El Centro and Llolleo earthquakes were
applied. Finally, the model was subjected to three pull-back tests and 25 minutes of white noise
motion. A similar sequence was applied to the damped model. All tests were performed at room
temperature. The model was instrumented with accelerometers at each story level and LVDT and
load cells at the bracing system.
Based on the test results, the following conclusions can be drawn:
(1) Inclusion of the braces produced a stiffness increase of 44, 47 and 50% in the first, second
and third mode, respectively.
(2) Equivalent damping in the structure increased from 0.59% to 5.95% in the first mode. This
damping is higher than the one obtained by Aiken et al (1993) for a similar model with Nitinol
bracings.
(3) The balance of these two factors was a reduction of the peak accelerations and drifts to near
60% compared to the one obtained without dissipation devices.
(4) During the seismic tests a deformation of up to 3.75% was obtained in the SMA wires
without rupture.
(5) The thermal treatment of the copper-based SMA material proved to be critical for obtaining
the desired superelastic properties.
(6) No appreciable difference was detected when vertical components were included.
Movements in the transverse direction were negligible.
In order to scale up these results to actual building structures more research is needed.
Large diameter bars of Cu-Al-Be alloy have shown lower damping than Cu-Al-Be wires.
Alternatively, cables form by wires could be used in real structures.
Acknowledgments
This project was sponsored by the University of Chile and Fondecyt Grant Nº1030554.
The authors are also grateful to Prof. Paul Roschke from Texas A&M University for his helpful
comments.
References
Aiken, I.D., Nims, D.K., Whittaker, A.S. and Kelly, J.M., 1993. Testing of Passive Energy Dissipation
Systems, Earthquake Spectra, 9(3), 335-370.
Casciati, F. and Faravelli, L. 2004. Experimental characterization of a Cu-based shape memory alloy
toward its exploitation in passive control devices, J. Phys. IV France, 115, 299-306.
Cerda M. 2005. Shaking table test of a scale model frame structure with SMA copper-based dampers,
Civil Engineer Thesis, University of Chile. (in Spanish)
DesRoches, R. and Smith, B. 2004a. Shape Memory Alloys in seismic resistant design and retrofit: a
critical review of their potential and limitations, Journal of Earthquake Engineering, 8(3), 415-
429.
DesRoches, R., McCormick, J., and Delemont, M. 2004b. Cyclic properties of superelastic shape memory
alloy wires and bars, J. Struct. Eng. 130, 38-46.
Dolce, M., Cardone, D. and Marnetto R. 2000. Implementation and testing of passive control devices
based on shape memory alloys. Earthquake Eng. Struct. Dyn. 29, 945-968.
Gillet, Y., Patoor, E. and Berveiller, M. 1994. Beam Theory Applied to Shape Memory Alloys, SMST-94,
Proceedings of the First International Conference on Shape Memory and Superelastic
Technologies (Asilomar, California, March 1994), edited by A. Pelton, D. Hodgson and Duerig
T., pp. 169-174.
Ibrahim, S. and Mikulcik, E. 1977. A method for the direct identification of vibration parameters from the
free response, The shock and Vibration Bulleting,47(4).
Janke, L., Czaderski, C., Motavalli, M., and Ruth, J. 2005. Applications of shape memory alloys in civil
engineering structures-overview, limits and new ideas, Materials and Structures, 38, 578-592.
Torra, V., Isalgue, A., Martorell, F., Terriault, P. and Lovey F. 2005. From experimental data to quake
th
damping by SMA: a critical experimental analysis and simulation, Proc. 9 world seminar on
seismic isolation, energy dissipation and active vibration control of structures, Kobe, Japan.
Wilson, J. and Wesolowsky, M. 2005. Shape Memory Alloys for seismic response modification: A state-
of-the-art review, Earthquake Spectra, 21(2), 569-601.
Witting, P.R. and Cozzarelli, F.A. 1992. Shape Memory Structural Dampers: Materials Properties, Design
and Seismic Testing, Technical Report MCEER 92-0013, State University of New York, Buffalo,
USA.