Section 3: Safety Switches
Section 3: Safety Switches
Section 3
Safety Switches
Light Duty
Fusible 3-2
Application Data and Dimensions 3-3
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under File E2875.
• NEMA Standards Publication KS1. Enclosed Switches.
General Duty
Light Duty, p. 3-2 Fusible and Non-Fusible 3-2
Application Data and Dimensions 3-3
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under File E2875.
• NEMA Standards Publication KS1. Enclosed Switches.
Heavy Duty
Fusible 3-4
Non-Fusible 3-6
Special Application Enclosures 3-7
Motor Disconnect and Receptacle Switches 3-8
Accessories 3-11
General Duty, p. 3-2 Application Data and Dimensions 3-13
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under files E2875, E154828, E233505 and E317818.
• UL 508 Industrial Control Equipment, file E 164864.
• NEMA Standards Publication KS1 Enclosed Switches (UL98 Switches Only).
Double Throw
Fusible and Non-Fusible 3-15
SAFETY SWITCHES
Accessories 3-18
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under files E2875 (unless otherwise noted).
• NEMA Standards Publication KS1 Enclosed Switches (applies to Type DT and
DTU series F only).
Heavy Duty, p. 3-4 Application Data and Dimensions 3-19
3
• UL 98 Enclosed and Dead Front Switches
• UL Listed under file E343347
• IEC 60947 - 1 Electrical
• IEC 60947 - 3 Mechanical
• NEMA standard. Publication KS-1 Enclosed Switches
• IP 63 and NEMA 3 Enclosure
greater protection, 600g Cart. D326N 5823.00 D326NR 7877.00 DRK600 111.00 — 75 — 150
consider using a heavy 600f Class T D326NT 5598.00 D326NTR 7569.00 — — — 75 — —
duty safety switch. Refer 800f Class T T327N 9722.00 T327NR 12438.00 — — — 100 — —
to UL Listed Maximum a Bolt-on hubs—Refer to page 3-10.
Short Circuit Current
Ratings—AC only—on b When installed, this kit rejects all but Class R fuses.
page 3-6. If a UL Listed c For corner grounded delta systems only. Use switching poles for ungrounded conductors. See data bulletin 2700DB0202 for additional information.
short-circuit current rating d If corner grounded delta, use outer switching poles for ungrounded conductors.
is required, this non- e For 200% neutral, order (1) additional neutral kit SN20A and (1) neutral jumper kit SN20NI.
fusible switch must be f Class T 400–800 A general duty safety switches use 300 Vac Class T fuses and are UL Listed for use on systems with up to 100 kA available fault current.
replaced with a Square D g Order Class J fuse kit: GDJK600 for Class J fuses.
general duty fusible safety
switch equipped with the Table 3.3: Non-Fusible
appropriate class and size
fusing. Consult the wiring NEMA 1 Indoor NEMA 3R Rainproof h Horsepower Ratings (Max.)
diagram of the switch to System Amperes
verify the UL Listed short- Cat. No. $ Price Cat. No. $ Price 1Ø 3Ø
circuit current rating. 2 Wire (2 Blades)—240 Vac Maximum
b 50 kA for 60 A non-fusible
switch. 30 — — DU221RB 177.00 3 —
60 — — DU222RB 353.00 10 —
60 QO260NATSij 161.00 QO200TR ijk 161.00 10 —
100 QO2000NSij 276.00 QO2000NRBik 338.00 20 —
200 Use 3P Switch — Use 3P Switch — — —
400p Use 3P Switch — Use 3P Switch — — —
600 Use 3P Switch — Use 3P Switch — — —
3 Wire (3 Blades)—240 Vac Maximum
30 DU321 155.00 DU321RB 293.00 3 7-1/2
60 DU322 206.00 DU322RB 443.00 10 15
100 DU323l 477.00 DU323RBl 816.00 15 30
200 DU324m 884.00 DU324RBm 1461.00 15 60n
400p DU325 2198.00 — — — 125
600 DU326n 4191.00 — — — 150
h Bolt-on hubs—Refer to page 3-10.
i Enclosed molded case switch—Refer to page 1-24.
j Includes factory-installed grounding kit.
k Not service entrance rated—Refer to page 1-19 for more information.
l If a neutral assembly is required, order and field-install SN0610.
m If a neutral assembly is required, order and field install a SN20A Neutral Assembly Kit. For a 200% neutral application, order and field install (2) SN20A
Neutral Assembly Kits and (1) SN20NI Neutral Jumper Kit.
n If a neutral assembly is required, order part number D600SN. Available for field-installation.
o For single phase hp rating, use two switching poles.
p To accept J class fuses, move fuse bases to the embossed guide inside of the switch.
Table 3.4: Terminal Lug Data a Table 3.6: Field-Installed Service Grounding Kits
Wire Range Amperes Cat. No. $ Price Wire Size (AWG)
Amperes Conductors Lug Wire Range
Per Phase Wire Bending Space Per NEC Table 312.6 AWG/kcmil (2) 12 Cu or
AWG/kcmil
30 PK3GTA1 11.40 (2) 10 Al or
30 1 12–6 (Al) or 14–6 (Cu) 12–6 (Al) or 14–6 (Cu)
(1) 4 Al/Cu Max.
60 1 10–3 (Al) or 14–3 (Cu) 10–2 (Al) or 14–2 (Cu)
(2) 12 Cu or
100 1 12–1 (Al) or 14–1 (Cu) 12–1/0 (Al) or 14–1/0 (Cu)
60a PK3GTA1 11.40 (2) 10 Al or
200 1 6 –250 (Al/Cu) 6 –300 (Al/Cu)
(1) 4 Al/Cu Max.
1 1/0 –600 (Al/Cu) (1) 1/0 –750 (Al/Cu)
400 (2) 12 Cu or
or or or
NEMA 1 2 1/0 –300 (Al/Cu) (2) 1/0 –300 (Al/Cu) 60b GTK03 11.40 (2) 10 Al or
(1) 1 –600 (Al/Cu) (1) 4 Al/Cu Max.
400 2 1/0–250 (Al/Cu) or 100 GTK0610 18.90 (2) 1/0 Al/Cu Max.
NEMA 3R (2) 1/0 –250 (Al/Cu)
200 PKOGTA2 55.00 (2) 2/0 Al/Cu Max.
600 2 4 –500 (Al/Cu) 4 –600 (Al/Cu)
400 PKOGTA2 (2) 2/0 Al/Cu Max.
800 3 3/0 –500 (Al/Cu) 3/0 –500 (Al/Cu) 55.00
o o 600 (Two Required) Per Lug
a 30–100 A switches suitable for 60 C or 75 C conductors. 200–800 A switches suitable for
75oC conductors. 800 PKOGTA3 123.00 (6) 3/0 Al/Cu Max.
a Series E switch only.
b Series F switch only.
NOTE: Field-installed lug kits are located in the Supplemental
Digest page 2.2.
Field-Installed Electrical Interlock Kits
Electrical interlocks for Series F 100–200 A general duty safety switches
Field-Installed Fuse Puller Kits and Series F 60 A fusible general duty safety switches are available in
Kit consists of three fuse pullers as required for a 3P, fusible, 60 and 100 A kit form for field installation. Each kit contains instructions for proper field
mounting. A pivot arm operates from switch mechanism, breaking the
general duty switch. Kits can be installed in 60 and 100 A Series F switches. control circuit before the main switch blades break. Switches with
Table 3.5: Fuse Puller Kits electrical interlocks installed are UL Listed.
Description Cat. No. $ Price Table 3.7: Electrical Interlock Kit
Series F 60 A Fuse Puller Kit FPK03 30.00 Switch’s Electrical Interlock Kit
Series F 100 A Fuse Puller Kit FPK0610 42.60 Series $ Price
Amperes Rating Cat. No.a
EIK031 or
60 Fb 218.00
EIK032
W
EIK1 or
100–200 F 311.00
EIK2
a Electrical interlock kit catalog numbers with -1 suffix indicates one normally open and one
normally closed contact; -2 indicates two normally open and two normally closed contacts.
Kits are UL Listed.
b Fusible series.
H
W/H D
SAFETY SWITCHES
Table 3.8: Approximate Dimensions
H W W/H D Std. H W W/H D Std.
Cat. No. Series Cat. No. Series
in. mm in. mm in. mm in. mm Pack in. mm in. mm in. mm in. mm Pack
L111N E2 7.63 194 5.00 127 6.13 156 4.00 102 1 D325NTRc E1 30.63 778 21.38 543 22.25 565 10.13 257 1
L211N E2 7.63 194 5.00 127 6.13 156 4.00 102 1 D326Nc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1
L221N E2 7.63 194 5.00 127 6.13 156 4.00 102 1 D326NTc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1
D211Nc E3 9.25 235 6.75 171 7.25 184 3.63 92 5 D326NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1
D211NRBc E2 9.63 245 7.25 184 7.75 197 3.75 95 5 D326NTRc E1 49.13 1246 24.75 629 25.13 638 8.88 226 1
D221Nc E3 9.25 235 6.75 171 7.25 184 3.63 92 5 DU221RBc E2 9.63 245 7.25 184 7.75 197 3.75 95 5
D221NRBc E3 9.63 245 7.25 184 7.75 197 3.75 95 5 DU222RBc E1 9.63 245 7.25 184 7.75 197 3.75 95 5
3
D222N F1 14.63 372 6.50 165 7.45 189 4.88 124 1 DU321c E2 9.25 235 6.75 171 7.25 184 3.63 92 5
D222NRB F1 14.88 378 6.63 168 7.45 189 4.88 124 1 DU321RBc E2 9.63 245 7.25 184 7.75 197 3.75 95 5
D223N F3 17.50 445 8.50 216 10.50 267 6.50 165 1 DU322c E1 9.25 235 6.75 171 7.25 184 3.63 92 5
D223NRB F3 17.50 445 8.50 216 10.50 267 6.50 165 1 DU322RBc E1 9.63 245 7.25 184 7.75 197 3.75 95 5
D224N F1 29.00 737 17.25 438 19.00 483 8.25 210 1 DU323 F3 17.50 445 8.50 216 10.50 267 6.50 165 1
D224NRB F1 29.25 743 17.25 438 19.00 483 8.25 210 1 DU323RB F3 17.50 445 8.50 216 10.50 267 6.50 165 1
D225N E3 45.12 1146 24.00 610 24.88 632 8.88 226 1 DU324 F1 29.00 737 17.25 438 19.00 483 8.25 210 1
D225NR E1 30.63 778 21.38 543 22.25 565 10.13 257 1 DU324RB F1 29.25 743 17.25 438 19.00 483 8.25 210 1
D226Nc E3 49.13 1248 24.00 610 24.88 632 8.88 226 1 DU325c E3 45.12 1146 24.00 610 24.88 632 8.88 226 1
D226NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1 DU326c E3 49.13 1248 24.00 610 24.88 632 8.88 226 1
D321Nc E3 9.25 235 6.75 171 7.25 184 3.63 92 5 QO200TRc G3 6.50 165 4.63 118 — — 3.88 99 5
D321NRBc E3 9.63 245 7.25 184 7.75 197 3.75 95 5 QO260NATSc E2 9.25 235 4.88 124 — — 3.25 83 1
D322N F1 14.63 372 6.50 165 7.45 189 4.88 124 1 QO2000NRBc E1 14.00 356 7.75 197 — — 4.50 114 1
D322NRB F1 14.88 378 6.63 168 7.45 189 4.88 124 1 QO2000NSc E1 13.38 340 6.13 156 — — 3.50 89 1
D323N F3 17.50 445 8.50 216 10.50 267 6.50 165 1 T327Nc E1 49.13 1248 24.00 610 24.88 632 8.88 226 1
D323NRB F3 17.50 445 8.50 216 10.50 267 6.50 165 1 T327NRc E1 49.13 1248 24.75 629 25.13 638 8.88 226 1
D324N F1 29.00 737 17.25 438 19.00 483 8.25 210 1
D324NRB F1 29.25 743 17.25 438 19.00 483 8.25 210 1
D325Nc E3 45.12 1146 24.00 610 24.88 632 8.88 226 1
D325NTc E3 45.12 1146 24.00 610 24.88 632 8.88 226 1
D325NRc E1 30.63 778 21.38 543 22.25 565 10.13 257 1
c 30–100 A switches suitable for 60oC or 75oC conductors. 200–800 A switches suitable for 75oC conductors.
Visible blade heavy duty safety switches are designed for application where maximum
performance and continuity of service are required. All heavy duty safety switches
feature quick-make, quick-break operating mechanism, a dual cover interlock and a
color coded indicator handle. They are suitable for use as service equipment when
equipped with a field- or factory-installed neutral assembly or equipment grounding kit,
unless a 600Y/347 V or 480 Y/277 V, 1000 A or greater, solidly grounded WYE system
is used, per NEC 215-10. Heavy duty safety switches are UL Listed (except as noted),
File E2875 and 154828 and meet or exceed the NEMA Standard KS1. For UL Listed
short circuit current ratings, see page 3-6.
60 Use four-wire devices H322DS 2532.00 H322A 914.00 H322AWK 864.00 3 7-1/2 10 15 10
100 For three-wire applications H323DS 5346.00 H323A 1412.00 H323AWK 1331.00 7-1/2 15 15 30 20
200 H324DS 7496.00 H324A 2040.00 H324AWK 1926.00 15 25 — 60 40
400 H325 3425.00 H325R 3975.00 H325DS 14961.00 — — H325AWK 4253.00 — 50 — 125 50
600 H326 6170.00 H326R 8286.00 H326DS 21399.00 — — H326AWK 7365.00 — 75 — 200 50
800 H327 11456.00 H327Rg 14849.00 — — — — H327AWK 14528.00 50 100 50 250 50
SAFETY SWITCHES
SAFETY SWITCHES
d For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors.
e On 3P devices, use two outside poles for switching dc.
f 60 A switch with 30 A fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks.
g Suitable for NEMA 5 applications with drain screw installed.
h Not suitable for use as service equipment.
3
page 3-10.
Class J Fuse Provisions:
Provisions for installing Class J fuses are included in 30 through 400 A 600 Volt, and 100 through 400 A 240 Volt,
fusible heavy duty safety switches. Conversion to Class J fuse spacing requires relocating the load side fuse base
assembly from the standard Class H fuse location to an alternate position as marked in the enclosure. With Class J
fuses installed, the switch is UL Listed for use on systems with up to 200 kA available fault current. Switches rated
Class R Fuse
600 A, 240 or 600 Volt, require the addition of an adapter kit, H600J at $456. One kit per 3P switch.
Class L Fuse Provisions:
Fusible 800 A and 1200 A safety switches use Class L bolt-in fuses and are rated for use on systems with up to 200 kA
at 600 Vac maximum. 1200 A switches accept class L fuses from 601–1200 A, 800 A switches accept class L fuses
from 601–800 A.
UL Listed Maximum Short Circuit Current Ratings—AC only Non-Fusible Safety Switches
NOTE: Consult the wiring diagram of the switch to verify the Any brand of circuit breaker or fuse not exceeding the ampere rating of the
UL Listed short circuit current rating. switch may be used in conjunction with an non-fusible safety switch when
there is up to 10 kA short circuit current available (see table below).
Above 10 kA—When applied on systems with greater than 10 kA short
circuit current available, the UL Listed short circuit current rating for
Table 3.12: Fusible Safety Switches Square D non-fusible switches is based upon the switch being used in
For the short circuit current rating, refer to the table below.
conjunction with fuses or Square D circuit breakers or Mag-Gard motor
Heavy Duty UL Listed UL Listed Short Circuit circuit protectors.
Safety Switch Type Fuse Class Current Ratings
Fusible
H, K 10 kA Table 3.13: Non-Fusible Safety Switches
R, J, L 200 kAm
Heavy Duty Switch Rating Fuse or Circuit 3-Phase
m On 600 V, 200 A switches, 100,000 A max. on corner grounded delta when protected by
Class J or R fuses. Safety Switch Type (A) n Breaker Typeo 240 Vac 480 Vac 600 Vac
Any brand circuit
breaker Up to 10 kA
All H, K
R,T,J.L 200 kA 200 kA 200 kA
30–100 Hp 65 kA 35 kA 35 kA
Non-Fusible 30–100 FA 14 kA 14 kA 14 kA
Switches 30–100 FH 18 kA 18 kA 18 kA
200 H, J p 65 kA 35 kA 35 kA
200 KA
22 kA 22 kA 22 kA
400 LA
200 KH
25 kA 25 kA 25 kA
400 LH
n Applies to NEMA 1, 3R, 4X stainless, 12 switches.
o Ampere rating of fuse or circuit breaker not to exceed switch ampere rating.
p All H and J circuit breakers are acceptable, but will only support the noted Short Circuit
Current Ratings.
Krydon™ Enclosures—NEMA 4X
Krydon enclosures are compression molded of fiberglass reinforced polyester, specially formulated to withstand attack from
almost any corrosive atmosphere found in the toughest industrial application. Switches are furnished with hubs
(page 3-14) and equipment grounding lugs. UL Listed.
Table 3.16: 3P, 600 Vac, 600 Vdc
SAFETY SWITCHES
Electrical Interlock Kits Horsepower Ratings– 3Øa
Class R Fuse Kits
Amperes Cat. No. $ Price Field-Installed Cat. No. c 480 Vac 600 Vac 600 Vdcb
Cat. No. $ Price 1 NO/1 NC Contact 2 NO/2 NC Contacts Std. Max. Std. Max. Max.
Fusible
30 H361DX 4161.00 RFK06 25.50 9999TC10 9999TC20 5 15 7-1/2 20 15
60 H362DX 4626.00 RFK06H 25.50 9999TC10 9999TC20 15 30 15 50 30
H361DX 100 H363DX 8858.00 RFK10 47.70 9999TC10 9999TC20 25 60 30 75 50
Non-Fusible
30 HU361DX 3960.00 — — 9999TC10 9999TC20 — 20 — 30 15
60 HU362DX 4406.00 — — 9999TC10 9999TC20 — 50 — 60 30
100 HU363DX 8438.00 — — 9999TC10 9999TC20 — 75 — 100 50
NEMA 7 and 9
An enclosed automatic molded case switch for use in Divisions 1 and 2 of the following: Class I, Groups C and D; Class II,
Groups E, F and G; or Class III, Hazardous Locations as defined in NEC™ Article 500. Furnished with threaded conduit
3
openings in both top and bottom endwall (page 3-14). Suitable for use as service equipment and listed as “Raintight’’ for
outdoor applications. cULus Listed. Equipment grounding lugs supplied as standard.
Table 3.17: 3P, Non-Fusible, 600 Vac, 250 Vdc Maximum, Short Circuit Rating 10 kA AIR
Enclosed Molded Case Switchdf Solid Neutral Assembly Horsepower Ratings—3Ø
Amperes
Cat. No. $ Price Cat. No. $ Price 240 Vac 480 Vac 600 Vacb
60 H60XFA 2571.00 100SNA 143.00 15 30 50
60 H60XFA1212 2886.00 100SNA 143.00 15 30 50
100 H100XFA 3045.00 100SNA 143.00 30 60 75
100 H100XFA1212 3287.00 100SNA 143.00 30 60 75
H60XFA 225 H225XJGg 6387.00 225SNA 189.00 60 125 150
225 H225XJGAAeg 6701.00 225SNA 189.00 60 125 150
a Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
b For switching dc use two switching poles.
c Electrical interlock not available. For auxiliary switches, refer to page 7-4 for catalog number suffix and price adder (e.g. H60XFA1212).
d Includes PKDB1, breather and drain kit, required for rainproof application—NEMA 7 only.
e Includes auxiliary contacts.
f For available options, contact customer service prior to placing an order.
g Not UL listed or CSA Certified due to wire bending space.
The MD motor disconnect switch is listed UL508 Suitable For Motor Control (UL File
E164864). It is in a compact NEMA 4X enclosure suitable for use in NEMA Type 1, 3, 3R, 4,
4X and 12 applications. The MD's key benefits are an extremely small footprint, a more
economically efficient NEMA 4X solution and a handle interlock preventing cover removal
when the switch is in the ON position.
Table 3.18: MD Motor Disconnect Switch—Non Metallic NEMA 1, 3, 3R, 4, 4X and
12 Enclosureabc
Maximum Horse Power Ratings
Height Width Depth
Amperes Cat. No. Three Phase Vac $ Price (in.) (in.) (in.)
220–240 440–480 600
30 MD3304X 7.5 20 25 121.00 6.38 3.9 4.37
60 MD3604X 20 40 40 161.00 8.27 4.94 4.37
a See table 8.9 for accessories.
b Complies with OSHA lockout/tagout requirements—accepts up to three 8 mm padlocks.
c Suitable for NEMA 1, 3R, 4, 4X and 12 enclosure applications.
W
MD Motor Disconnect Switches
3
SAFETY SWITCHES
NEMA
3, 3R, 4, 4X, 5, 12 Horsepower
NEMA 1 NEMA 12, 3R Use with Plug a
304 Stainless Steel Ratings–3Øb
Amperes Enclosure
480 Vac 600 Vac 250 Vdcc
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
Std. Max. Std. Max. Std. Max.
Fusible—3P, 600 Vac, 250 Vdc
30 H361WA 2076.00 H361DSWA 4401.00 H361AWA 2289.00 ACP3034BC 1235.00 5 15 7-1/2 20 5 —
H362AWA 60 H362WA 2412.00 H362DSWA 4668.00 H362AWA 2508.00 ACP6034BC 1295.00 15 30 15 50 10 —
Interlocked Receptacle 100 H363WA 3689.00 H363DSWA 8468.00 H363AWA 3758.00 ACP1034CD 1928.00 25 60 30 75 20 —
Switch with Appleton Non-Fusible—3P, 600 Vac, 250 Vdc
Powertite Receptacle 30 HU361WA 1893.00 HU361DSWA 4001.00 HU361AWA 2076.00 ACP3034BC 1235.00 — 20 — 30 — 5
60 HU362WA 2306.00 HU362DSWA 4412.00 HU362AWA 2357.00 ACP6034BC 1295.00 — 50 — 60 — 10
100 HU363WA 3153.00 HU363DSWA 8010.00 HU363AWA 3347.00 ACP1034CD 1928.00 — 75 — 100 — 20
a Receptacle UL Listed for use with “Appleton ACP or CPH” plugs; UL Classified for use with Crouse-Hinds “APJ” Arktite plugs listed on this page.
b Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
c For switching dc, use two switching poles.
SAFETY SWITCHES
30 HU361WC 1952.00 HU361DSWC 5888.00 HU361AWC 2136.00 APJ3485 1235.00 — 20 — 30
H362AWC 60 HU362WC 2634.00 HU362DSWC 7374.00 HU362AWC 2678.00 APJ6485 1295.00 — 50 — 60
Interlocked Receptacle 100 HU363WC 5249.00 HU363DSWC 14025.00 HU363AWC 5444.00 APJ10487 1928.00 — 60 — 100
Switch with Crouse-Hinds d Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
Arktite Receptacle
Hubbellock Receptacle
• UL Listed, suitable for use as service equipment.
• Short circuit rating: 10 kA.
Note: The Hubbellock receptacle switch utilizes the Square D interlocked plug SD12781 available only from Square D.
Table 3.21:
NEMA 1 NEMA 12 Use with Plug Horsepower Ratings—3Øe
Amperes 480 Vac 600 Vac
3
Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price
Std. Max. Std. Max.
Fusible—3P, 600 Vac Maximum
60 H362WH 2351.00 H362AWH 2459.00 SD12781f 609.00 15 30 15 50
Non-Fusible—3P, 600 Vac Maximum
60 HU362WH 2237.00 HU362AWH 2310.00 SD12781f 609.00 — 50 — 60
e Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
f Hubbell plug is furnished with a Kellems grip for 1-1/2 in. to 1-21/64 in. cable diameter.
H362AWH
Interlocked Receptacle
Switch with Hubbell™
Hubbellock Receptacle
Electrical Interlock Kits Table 3.24: Class R Fuse Kits—600 V (one kit per 3P switch)
Electrical interlocks for heavy duty 30–1200 A safety switches are Series Number Class R Fuse Kit $ Price Factory-Installed
available factory-installed or in kit form for field installation. Each kit Amperes (See pages 3-13, 3-14) Cat. No. $ Price
contains instructions for proper field mounting. A pivot arm operates 30h F1, F5–F7 RFK03Hi 25.50 293.00
from switch mechanism, breaking the control circuit before the main 30 h F3 RFK06 25.50 293.00
switch blades break. Switches with electrical interlocks installed are UL 60 h F1–F7 RFK06H i 25.50 293.00
Listed. For factory-installed electrical interlocks add EI (for one contact) 100 h F2–F7 RFK10 47.70 231.00
or EI2 (for two contacts) suffix to catalog number. See Supplemental 200 F5–F6 HRK1020 47.70 231.00
Digest page 2-4 for electrical interlock contact ratings. 400–600 E2–E4 HRK4060 111.00 360.00
h See page 3-7 for Class R Fuse Kits in NEMA 4X Fiberglass Reinforced Polyester and
Table 3.22: Electrical Interlock Kit a Krydon switches.
i The following Series F5–F7 devices use RFK06: H3612, H3612A, H3612AWK, H3612RB,
Switch’s Series Number Electrical Interlock Kit $ Price Factory-Installed H461, H461DS, H461AWK, H361AWA and H361AWC.
Amperes Rating (See pages 3-13, 3-14) Cat. No.b $ Price
EIK031c d
F1, F5–F7 218.00 359.00
30
EIK032c d Internal Barrier Kits
EIK1
F3
EIK2
311.00 452.00 Internal Barrier Kits provide an additional barrier that helps prevent
F1-F3 EIK1 accidental contact with live parts. Field-installed transparent barriers do
F5–F7 (600 V) EIK2
311.00 452.00 not restrict visual inspection of the switch. Barriers provide IEC529 IP2X
60
F4 EIK031e “finger safe” protection when door of enclosed disconnect switch is
F5–F6 (240 V) EIK032e
218.00 359.00 open. Convenient door allows use of test probes without accessing
EIK1 fuses and replacement of fuses without removing barrier. Barrier can
100–200 F2–F7
EIK2
311.00 452.00 also be used with the skirt kit to enclose a panel mounted Type 9422
3
EIK40601 disconnect.
400–1200 E1–E4 533.00 674.00
EIK40602
a See page 3-7 for electrical interlocks on NEMA 4X fiberglass reinforced polyester and Safety Switch Application 9422 Type T
Krydon™. Cat. No. Description (F Series Only) Disconnect Application $ Price
b Electrical interlock kit catalog numbers with 1 suffix indicates one normally open and one
normally closed contact; 2 indicates two normally open and two normally closed contacts. Interior Barrier for 30 A 240 / 600 Vac – 30 A
SS03 NA 150.
SAFETY SWITCHES
Neutral Assemblies—Field-Installed Neutral Assemblies for Fusible and Non-Fusible 240 and 600 Volt Safety Switches
Standard
Series Number Terminal Data $ Price Optional Copper Only Terminal Data
Amperes (See Neutral Kit $ Price
pages 3-13, 3-14) AWG/kcmil Neutral Kit Cat. No. AWG/kcmil
Cat. No.
30 F1, F5–F6 SN03a (3) 2 Max. Al/Cu 83.00 SN03C a (3) 6 Max. Cu 102.00
F1–F3, (2) 1/0 Max. Al/Cu (2) 1/0 Max. Cu
SN0610 107.00 SN0610C 114.00
F5–F6 (600 V) (2) 6 Max. Al/Cu (2) 6 Max. Cu
60
F4, SN03a (3) 2 Max. Al/Cu 83.00 SN03Ca (3) 6 Max. Cu 102.00
F5–F6 (240 V)
(2) 1/0 Max. Al/Cu (2) 1/0 Max. Cu
100 F2–F6 SN0610 107.00 SN0610C 114.00
(2) 6 Max. Al/Cu (2) 6 Max. Cu
(2) 250 Max. Al/Cu (2) 250 Max. Cu
200b F5–F6 SN20A 200.00 SN20C 246.00
(1) 1/0 Max. Al/Cu (1) 1/0 Max. Cu
(2) 600 Max. Cu
400 and (4) 750 Max. Al/Cu
E1–E4 H600SN 327.00 H600SNC (2) 350 Max. Cu 452.00
600 (1) 300 Max. Al/Cu
(1) 250 Max. Cu
(6) 750 Max. Al/Cu
800 E2–E4 H800SNE4 753.00 — — —
(2) 350 Max. Al/Cu
(8) 750 Max. Al/Cu
1200 E2–E4 H1200SNE4 1034.00 — — —
(2) 350 Max. Al/Cu
Note: Neutrals cannot be installed in 4P, 6P, or 200 A NEMA 4X fiberglass reinforced polyester
safety switches.
a The following Series F5–F6 devices use SN0610(C): H-361-2, H-361-2RB, H-361-2A and
H-361-2AWK.
b For 200% neutral, order (2) neutral kits and (1) SN20NI neutral jumper kit.
(2) 350 Max. Al/Cu.
SAFETY SWITCHES
4 and 6 pole switches.
3
Z535.1 for marking physical hazards. padlock from being inadvertantly inserted
into the switch lockplate. The device is
Table 3.26: Safety Colors designed to help prevent accidental
Safety Color Suffix
misapplication of a lockout device. These
kits are marked cURus (UL Component
Black SP0
Recognized) for field or factory installation.
Red SP2
Orange SP3
Factory-
Yellow SP4 Kit Cat. Field-Installed
Amperesc Installed
No. $ Price
Green SP5 $ Price
Blue SP6
30 A
Purple SP7 LOGK1 44.30 146.00
Gray SP8 60 A 240 V
Gray ANSI 61 SP861a 60 A 600 V
White SP9 LOGK2 45.00 177.00
100 and 200 A
a Standard Square D ANSI 49 grey paint, when selecting this suffix, switches will receive
additional coat of paint. b For factory installation, add suffix “LOG” to the switch
A minimum quantity of 10 is required. Not available for NEMA Type 7/9 catalog number.
c For use with 30–200 Ampere Series F NEMA 1, 3R,
or stainless steel products. 12 and 12K switches only.
d Factory install and kits are available for NEMA 1, 3R,
12 and 12K switch enclosures only.
SAFETY SWITCHES
H266 E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU266 E4 50.25 1276 27.63 702 10.13 257 27.63 702
H266R E5 50.31 1278 27.76 705 9.53 242 27.88 708 HU266R E5 50.31 1278 27.76 705 9.53 242 27.88 708
H267 E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU267 E4 69.13 1756 36.62 930 17.75 451 36.62 930
H267R E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU267R E4 69.13 1756 36.62 930 17.75 451 36.62 930
H268 E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU268 E4 69.13 1756 36.62 930 17.75 451 36.62 930
H268R E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU268R E4 69.13 1756 36.62 930 17.75 451 36.62 930
H321N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU361 F5 14.60 371 6.50 165 4.88 124 7.55 192
H321NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU361RB F5 14.88 378 6.63 168 4.88 124 7.55 192
H322N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU361WA F6 18.19 462 9.00 229 6.81 173 10.50 267
H322NRB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU361WC F6 18.19 462 9.00 229 6.81 173 10.50 267
H323N F5 21.25 540 8.50 216 6.38 162 10.50 267 HU362 F5 17.50 445 9.00 229 6.38 162 10.50 267
H323NRB F5 21.25 540 8.50 216 6.38 162 10.50 267 HU362RB F5 17.50 445 9.00 229 6.38 162 10.50 267
H324N F5 29.00 737 17.13 435 8.25 210 18.50 470 HU362WA F6 18.19 462 9.00 229 6.81 173 10.50 267
H324NRB F5 29.25 743 17.25 438 8.50 216 18.63 473 HU362WC F6 16.75 425 9.00 229 7.00 178 10.50 267
3
H325, N E4 50.25 1276 27.88 708 10.13 257 27.88 708 HU362WH F5 18.19 462 9.00 229 6.81 173 10.50 267
H325R, NR E5 50.31 1278 27.76 705 9.53 242 27.88 708 HU363 F5 21.25 540 8.50 216 6.38 162 10.50 267
H326, N E4 50.25 1276 27.63 702 10.13 257 27.63 702 HU363RB F5 21.25 540 8.50 216 6.38 162 10.50 267
H326R, NR E5 50.31 1278 27.76 705 9.53 242 27.88 708 HU363WA F6 21.85 462 9.00 229 6.81 173 10.50 267
H327, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU363WC F6 21.85 555 9.00 229 6.81 173 10.50 267
H327R, NR E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU364 F5 29.00 737 17.13 435 8.25 210 18.50 470
H328, N E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU364RB F5 29.25 743 17.25 438 8.50 216 18.63 473
H328R, NR E4 69.13 1756 36.62 930 17.75 451 36.62 930 HU365 E4 50.25 1276 27.63 702 10.13 257 27.63 702
H361, N F5 14.60 371 6.50 165 4.88 124 7.55 192 HU365R E5 50.31 1278 27.76 705 9.53 242 27.88 708
H361-2 F5 17.50 445 9.00 229 6.38 162 10.50 267 HU366 E4 50.25 1276 27.63 702 10.13 257 27.63 702
H361NRB, RB F5 14.88 378 6.63 168 4.88 124 7.55 192 HU366R E5 50.31 1278 27.76 705 9.53 242 27.88 708
H361WA F6 18.19 462 9.00 229 6.81 173 10.50 267 HU367 E4 69.13 1756 36.62 930 17.75 451 36.62 930
H361WC F6 18.19 462 9.00 229 6.81 173 10.50 267 HU367R E4 69.13 1756 36.62 930 17.75 451 36.62 930
H362, N F5 17.50 445 9.00 229 6.38 162 10.50 267 HU368 E4 69.13 1756 36.62 930 17.75 451 36.62 930
H362NRB, RB F5 17.50 445 9.00 229 6.38 162 10.50 267 HU368R E4 69.13 1756 36.62 930 17.75 451 36.62 930
H362WA F6 18.19 462 9.00 229 6.81 173 10.50 267 HU461 F5 20.50 521 14.75 375 6.85 174 16.13 410
H362WC F6 16.75 425 9.00 229 7.00 178 10.50 267 HU462 F5 20.50 521 14.75 375 6.85 174 16.13 410
H362WH F5 18.19 462 9.00 229 6.81 173 10.50 267 HU463 F5 20.50 521 14.75 375 6.85 174 16.13 410
H363, N F5 21.25 540 8.50 216 6.38 162 10.50 267 HU464 F5 29.00 737 23.25 591 8.75 222 24.88 632
H363NRB, RB F5 21.25 540 8.50 216 6.38 162 10.50 267 HU465 E4 50.25 1276 33.88 861 10.13 257 33.88 861
H363WA F6 21.85 462 9.00 229 6.81 173 10.50 267 HU466 E4 50.25 1276 33.88 861 10.13 257 33.88 861
H363WC F6 21.85 555 9.00 229 6.81 173 10.50 267
H222DS F6 14.93 379 7.22 183 5.11 130 8.67 220 HU362AWA F7 16.50 419 9.00 229 7.00 178 10.50 267
H223AWK, A F6 20.50 521 9.00 229 7.00 178 10.50 267 HU362AWC F7 16.50 419 9.00 229 7.00 178 10.50 267
H223DS F6 20.82 529 9.36 238 6.97 177 11.25 286
H224A,AWK F6 29.00 737 17.25 438 8.75 216 18.63 473 HU362AWH F6 16.50 419 9.00 229 7.00 178 10.50 267
HU362AWK, A F6 16.50 419 9.00 229 7.00 178 10.50 267
H224DS F6 29.00 737 17.75 451 8.88 226 19.25 489 HU362DS F6 16.87 428 8.92 227 6.97 177 10.81 275
H225AWK, DS E4 46.25 1175 26.25 667 10.13 259 26.25 667 HU362DSWA F7 16.87 428 8.92 227 5.11 130 10.81 275
H225NAWK, NDS E4 46.25 1175 26.25 667 10.13 259 26.25 667 HU362DSWC F7 16.87 428 8.92 227 5.11 130 10.79 274
SAFETY SWITCHES
SAFETY SWITCHES
30–100 A DT, DTU (Series F)
NEMA 1
82,000 Line
NEMA 1
Line
Load
Line
Line
60 F DTU222 962.00 — — — — — — — — 10 — 10 f
Line 100 F DTU223 1371.00 DTU223RB 1347.00 — — — — — — 15 — 20 f
Load
30 T4 92251 g 585.00 — — — — — — — — — — —
200 E 82254 k 1815.00 DTU224NRB ghk 2177.00 — — H82254 4671.00 15 — — — —
— — — — — — — — — — 15 — — — —
400 A 82255 gk 5850.00 82255R g 8715.00 — — H82255 g 10335.00 — — — — —
3
Line
30 F DTU321 804.00 — — — — — — — 3d 5e 10 d 5f
SAFETY SWITCHES
60 F DTU322 1119.00 — — — — — — — — 10 e 15 d 10 f
Line 100 F DTU323 1764.00 DTU323RB 1953.00 — — — — — — 15 e 30 d 20 f
Load
30 T4 92351 g 687.00 — — — — — — — — — — —
200 E 82354 g 2564.00 DTU324NRB gh 3005.00 — — H82354 gi 5408.00 — 15 — — —
200 E DTU324N gh 2798.00 — — — — — — — 15 — — —
400 A 82355 g 8040.00 82355R g 13038.00 — — H82355 g 11715.00 — — — — —
600 A DTU326 12555.00 DTU326R 13890.00 — — — — — 125 — — 50
Non-Fusible—4P, 240 Vac
30 T4 92451 g 953.00 — — — — — — — — — — —
200 E 82454 k 5184.00 82454R k 7517.00 — — H82454 j 6779.00 — 15 j — — —
400 A 82455 k 11505.00 82455R 16200.00 — — H82455 15975.00 — — — — —
600 A DTU426 20355.00 DTU426R 20595.00 — — — — — 125 — — 50
a Refer to page 7-31 for additional motor application data. The starting current of motors or more than standard horsepower may require the use of fuses with appropriate time delay
characteristics.
b Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
c For switching dc, use two switching poles.
d If used on corner grounded delta systems, install neutral and use outer switching pole for ungrounded conductors.
e Use outer switching poles.
f Maximum rating.
g 240 Vac only.
h Neutral included with device.
i Suitable for use as service equipment.
j Hp rating applies only to H82454.
k 250 V dc rated.
Line
Load
Line
Load
Line
Load
200 E 82444 n 6143.00 82444R n 8130.00 82444DS n 15105.00 H82444 ljn 7143.00 — — — — — — — —
400 A 82445 mn 12578.00 82445R m 16800.00 — — H82445 m 16845.00 — — — — — — — —
SAFETY SWITCHES
600 A DTU466 n 20355.00 DTU466R n 23475.00 — — — — — 125 — 250 — 350 50 —
Line
60 F — — — — — — DTU662AWK p 8474.00 — 20 — 50 — 60 10 30
Line 100 F — — — — — — DTU663AWK p 12735.00 — 40 — 75 — 75 20 50
Load
3
a Refer to page 7-31 for additional motor application data. The starting current of motors or more than i Maximum Hp is 60 for corner grounded delta systems.
standard horsepower may require the use of fuses with appropriate time delay characteristics. j 480 Vac maximum only, 250Vdc.
b If used on corner grounded delta systems, install neutral and use outer switching pole for ungrounded k Standard Hp rating.
conductors. l Not suitable for use as service equipment.
c For switching dc, use two switching poles. m 600 Vac max.
d Use outer switching poles. n 250 V dc rated.
e Maximum Hp is 15 for corner grounded delta systems. o Std.—Using fast acting one time fuses. Max.—Using dual element time delay
f Maximum Hp is 30 for corner grounded delta systems. fuses.
g Use 75oC #4 Cu or #2 Al conductors only. (Non-fusible switches have max rating unless noted.)
h Use 75oC #1 Cu conductors only. p Complete rating on switch is NEMA 3R or 12.
For 3R applications, remove drain screw from bottom endwall.
q H82 ... and H92 ... devices are NEMA 12 only, intended for use indoors only.
r Not UL Listed.
s Copper lugs not listed or available.
Table 3.39: Electrical Interlocks (For Electrical Interlock Contact Ratings, see Supplemental Digest page 2-4.)
Factory-Installed
Switch Field-Installed Electrical Interlock Kit Cat. No. c $ Price $ Price Adder Per Switch
30–100 A Type DT, DTU (Series F) EIK1, EIK2 dh 311.00 905.00e
200 A Type 82000 and DTU (Series E) f g — 1113.00e
400 A Type 82000 EK400DTU2 260.00 —
600 A Type DTU (Series A) DS200EK2D 438.00 —
c Electrical interlock kit catalog numbers with “1” suffix indicate one normally open and normally closed contact; “2” indicates two normally open and two
normally closed contacts. See page 3-10 for electrical interlock ratings.
d 30–100 A Type DT, DTU (Series F) switches contain (2) separate switching mechanisms. Each mechanism will accept an electrical interlock. Some
applications may therefore require (2) electrical interlocks.
e 30–100 A Type DT, DTU (Series F) switches with factory-installed electrical interlocks installed are UL Listed and interlocks are furnished with 2 N.O. /2
N.C. contacts installed in both “ON” positions. To order, add suffix EI to standard catalog number.
f Electrical interlock EK400DTU2 can be added to 4-pole Type 82000 switches in the field.
g Type 82000 and DTU switches are available with electrical interlock factory-installed only. Not UL listed. Electrical interlocks are furnished with 2
N.O./N.C. contacts and are installed in both “ON” positions. To order, add suffix EI to standard switch catalog number.
h Double throw switches 92251, 92351, and 92451 are not available with factory or field installed electrical interlocks.
Table 3.40: Service Grounding Kit (Required for service equipment use.)
Terminal Data
Switch Field-Installed Service Grounding Lug Kit Cat. No. $ Price
AWG/kcmil
30–100 A Type DT, DTU (Series F) Included Included std.
30 A Type 92,000 DT30SG (4) 14–4 Cu/Al 29.40
200 A Type 82000 and DTU (Series E) DT100SG (3) 14–1/0 Cu/Al 30.00
PKOGTA2 (4) 10–2/0 Cu or
400 A Type 82000 55.00
(2 required) (4) 6–2/0 Al
600 A Type 82000 (Series A) DS468GKD 6–250kcmil 309.00
Table 3.46: Terminal Lug Data for Types 82,000 and for A and E-Series DTU devices g
Wire Range Wire Bending Space
Wires per Lug Wire Range Optional Compression Lugs
Load Amperes Per NEC Table 373-6
Phase AWG/kcmil Field-Installed
AWG/kcmil
Diagram 1 12–2 Al
30 A (Series T4) h 1 14–8 Al/Cu or —
Line 14–2 Cu
200 1 6–300 Al/Cu 6–300 Al/Cu VCEL030516H1 i
1 1/0–600 Al/Cu
Fusible 400 or or 1/0–600 Al/Cu —
Single Throw 2 1/0–300 Al/Cu
Switch or 600 2 250–500 Al/Cu 250–500 Al/Cu —
SAFETY SWITCHES
o
Circuit g 200–600 A switches suitable for 75 C conductors.
h 30 A switches suitable for 60oC or 75oC conductors.
Breaker i Hubbell Versa-Crimp™ catalog numbers.
Fusible
Single Throw
Switch or
Circuit
Breaker
Line 3
Diagram 2
W/H D
Table 3.48: 30, 200–600 A Types 82,000 and E-Series DTU devices, NEMA 1 and
3R—Approximate Dimensions
H W W/H D
Cat. No. Series
in. mm in. mm in. mm in. mm
W/H
DTU224NRB a E1 32.50 826 20.63 524 24.00 610 10.63 270
W D 82254 a E1 30.88 784 15.75 400 19.63 499 9.75 248
82254NW a E1 30.88 784 20.00 508 23.88 607 11.75 298
82344 a E2 30.88 784 20.00 508 23.88 607 11.75 298
82344RB a E1 32.50 826 20.63 524 24.00 610 10.63 270
82354 E1 30.88 784 20.00 508 23.88 607 11.75 298
92251 T4 10.00 254 8.00 203 9.75 248 4.75 121
82344DS E1 30.88 784 20.00 508 23.88 607 11.75 298
DTU324N E1 32.50 826 24.50 622 26.25 667 10.63 270
H
DTU324NRB E1 32.50 826 24.50 622 26.25 667 10.63 270
H82344 E2 32.50 826 24.50 622 26.25 667 10.63 270
H82444 a E2 32.50 826 30.21 767 33.61 854 10.63 270
H82454 E3 32.50 826 30.21 767 33.61 854 10.63 270
82454 E3 38.00 965 29.62 753 33.02 839 10.63 270
82444 E3 38.00 965 29.62 753 33.02 839 10.63 270
NEMA 1 82454R a E3 38.00 965 29.62 753 33.02 839 10.63 270
82444R E3 38.00 965 29.62 753 33.02 839 10.63 270
H82254 E3 32.50 826 24.50 622 26.25 667 10.63 270
H82354 E3 32.50 826 24.50 622 26.25 667 10.63 270
82444DS a E3 38.00 965 29.62 753 33.02 839 10.63 270
82255 a A1 38.50 978 26.10 663 29.51 750 10.63 270
82255R A1 39.00 991 26.62 676 30.02 763 10.63 270
82345a A1 38.50 978 26.10 663 29.51 750 10.63 270
82345DSa A1 39.00 991 26.62 676 30.02 763 10.63 270
W/H
82345Ra A1 39.00 991 26.62 676 30.02 763 10.63 270
82355 a A1 38.50 978 26.10 663 29.51 750 10.63 270
W D
82355R a A1 39.00 991 26.62 676 30.02 763 10.63 270
82445 A1 38.50 978 30.10 765 33.50 851 10.63 270
82445R A1 39.00 991 30.21 767 33.61 854 10.63 270
82455 a A1 38.50 978 30.10 765 33.50 851 10.63 270
82455R A1 39.00 991 30.21 767 33.61 854 10.63 270
H82255 A1 39.00 991 26.62 676 30.02 763 10.63 270
H H82345 A1 39.00 991 26.62 676 30.02 763 10.63 270
H82355 A1 39.00 991 26.62 676 30.02 763 10.63 270
H82445 A1 39.00 991 30.21 767 33.61 854 10.63 270
H82455 A1 39.00 991 30.21 767 33.61 854 10.63 270
DTU326 A1 63.31 1608 23.66 601 24.46 621 8.88 226
DTU426 A1 63.31 1608 27.00 686 27.80 706 8.88 226
DTU—200 A DTU366 A1 63.31 1608 23.66 601 24.46 621 8.88 226
NEMA 3R DTU466 A1 63.31 1608 27.00 686 27.80 706 8.88 226
DTU326R A1 63.76 1619 23.66 601 24.46 621 8.88 226
DTU426R A1 63.76 1619 27.00 686 27.80 706 8.88 226
DTU366R A1 63.76 1619 23.66 601 24.46 621 8.88 226
DTU466R A1 63.76 1619 27.00 686 27.80 706 8.88 226
SAFETY SWITCHES
DTU366AWK A1 63.76 1619 23.66 601 24.46 621 8.88 226
a 250 V dc rated.
Put over 100 years of Schneider Electric’s experience as PV disconnect applications. It is compact and available in
a global specialist in energy management to work on your both a 100 and 200 amp non-fusible versions. IEC 60947-
photovoltaic (PV) project. The Square D™ 1000 Vdc 1 and 3 certified (file 136861) and UL 98 certified (file
disconnect switch is the perfect solution for your 1000 Vdc E343341).
Easy to Install
Preconfigured solar solution
Familiar enclosed safety switch design
Suitable for both grounded and ungrounded PV
Table 3.49: 1000 Vdc Photovoltaic Heavy Duty Disconnect Switch Pricing and Accessories
Factory Installed Accessories
NEMA 1, 3R, 12, 3 3 Wire
and IP63 Electrical Interlock Electrical Interlock Viewing Terminal Blocks Ground
System Single Contacta Two Contactsb Windows (Copper)c Height Width Depth
Lugd
(in.) (in.) (in.)
$ Price No. Suffix $Adder
Price No. Suffix $ Price No. $ Price No. $ Price No. $ Price
Amperes Cat. No. Adder Suffix Adder Suffix Adder Suffix Adder
3 Pole Groundede
Three-Pole (Grounded System)
Connector
100 REHU393IP 1672.00 EI 452.00 EI2 496.00 VW 150.00 TBC 409.00 GL 263.00 22.13 18.63 8.75
Line
Connector
Load
PE
200 REHU394IP 2246.00 EI 452.00 EI2 496.00 VW 175.00 TBC 409.00 GL 263.00 22.13 18.63 8.75
4 Pole Ungrounded
100 REHU493IP 2507.00 EI 452.00 EI2 496.00 VW 150.00 — — GL 263.00 29.00 18.63 8.75
SAFETY SWITCHES
Connector
PE 200 REHU494IP 3965.00 EI 452.00 EI2 496.00 VW 175.00 — — GL 263.00 29.00 18.63 8.75
a Order EIK1PV for single contact field-installed kit $311.00. SN20CPV for field-installed kit $246.00.
b Order EIK2PV for double contact field-installed kit $355.00. d Order REHGND KIT for field installable kit $100.00.
c Accommodates (2) 250 max Cu or (1) 1/0 max Cu wiring; Order e Terminal blocks standard with 3 pole switches; accommodates (2) 1/0
max Al/Cu or (2) 6 max Al/Cu wiring.
Schneider Electric gives the Photovoltaic market place the most comprehensive one stop shop
for Residential and Light Commercial Photovoltaic Balance of System components. Schneider
Electric's Inverters, and Square D brand DC and AC disconnect switches and Load Centers are
ideal solutions to your Balance of Systems requirements. See the Balance of System solution
chart below for your single phase PV system.
Table 3.50: PV Balance of System Solution Package—Grid Tie
System Voltage Kilowatts Amps DC Disconnect Inverter AC Disconnect Load Center Product
200 A Enclosed Switch Dimensions (inches) 600 Vdc 5.0 100 HU363RB 878-5001 D223NRB QONQ42MS400
For internal 600 Vdc PV combiner box switches please see our offering of 9422 For our 600 Vdc PV switch offering please see digest pages 3-5–3-6.
switches 600 Vdc UL98 listed in digest pages 8-14.
3-22 DE1
Discount © 2012 Schneider Electric
Schedule All Rights Reserved
String Combiner Boxes Dimensions
Class 3140 / Refer to Catalog 3100CT0901
www.schneider-electric.us
Square D PV string combiner boxes are used to integrate multiple PV strings into one output
circuit. Its tough exterior and safety features protect wiring from weather and overcurrent. The
exterior coating ensures low operating temperatures and longer life of internal components.
The specially engineered enclosure is designed to provide dust tight and rain tight protection;
it meets or exceeds NEMA® 3R, 12, and 4 requirements. Traditional Square D visible blade
switch architecture confirms disconnection, while touch-safe interior shielding protects
against accidental contact with live components.
Features
Flexible
• Vertical, horizontal, and angled mounting options
• Flexible installation with top, bottom, and side entry
• Substantial wire-bending space
Robust
• Dust tight and rain tight engineered enclosure for outdoor use
• UV-resistant white exterior coating to reduce solar gain by 35%
• Meets or exceeds NEMA 3R, 12, and 4 requirements
Safe
• Square D traditional visible blade switch architecture for confirmation of disconnect
• Touch-safe interior shielding guards against accidental contact with current-carrying components
• Seismic-certified 100–400 amp string combiner boxes for earthquake safety
• Optional integrated 2.5 kV surge arrestor to protect PV electronics from lightning strikes
Listings
• UL 1741
• Switches tested to UL98B
• CSA C22.2 Spec 107.1
Table 3.51: 600 Vdc Photovoltaic Combiner Boxes
Maximum Wire Range (AWG/kcmil—Copper Only) Outside Dimmensions
Number Continuous Maximum Continuous
Catalog Input DC Output PV Module Input List Output Height Width Depth
Input Output Circuit Number
Numbera Circuits Current Isc Rating Current Price $ of Ground Ground
Circuit
(Max.) (Max.) (Amps) Per String (+ and -) Conductors In Out in. mm in. mm in. mm
(+ and -)
(Amps) (+ or -)
REHSC126100 12 100 838.00 #12–#6 #6–1/0 1 #6–2/0 20.78 528 14.50 368 6.13 156
REHSC166200 16 200 1067.00 #12–#6 #6–300 MCM 1 #14–4 Or #6–2/0 27.78 706 20.25 514 6.13 156
10.4 13
REHSC246300 24 300 1378.00 #12–#6 1/0–300 2 2X #14–#12 #6–2/0 35.78 909 20.25 514 6.13 156
REHSC326400 32 400 2226.00 #12–#6 1/0–300 2 #6–2/0 35.78 909 20.25 514 6.13 156
a For factory installed surge protection device add the suffix “S” to the catalog number.
SAFETY SWITCHES
Number Continuous Maximum Continuous
Catalog Input DC Output PV Module Input List Output Height Width Depth
Input Output Circuit Number
Numbera Circuits Current Isc Rating Current Price $ of Ground Ground
Circuit
(Max.) (Max.) (Amps) Per String (+ and -) Conductors In Out in. mm in. mm in. mm
(+ and -)
(Amps) (+ or -)
REHSC126100DU 12 100 1438.00 #12–#6 #6–1/0 1 #6–2/0 31.00 787 19.00 483 9.00 229
REHSC166200DU 16 200 1899.00 #12–#6 #6–300 MCM 1 #14–4 Or #6–2/0 31.00 787 25.00 635 9.00 229
10.4 13
REHSC246300DU 24 300 3035.00 #12–#6 1/0–300 2 2X #14–#12 #6–2/0 41.00 1041 25.00 635 10.50 267
REHSC326400DU 32 400 3883.00 #12–#6 1/0–300 2 #6–2/0 41.00 1041 25.00 635 10.50 267
a For factory installed surge protection device add the suffix “S” to the catalog number.
3
blocking diodes from physical damage resulting from lightning induced transients. The SPD
device uses Metal Oxide Varistor (MOV)/Gas-Filled Spark Gap (GSP) protection circuits for
longer life and no current leakage. The devices are UL1449 ed 2 compliant Low Voltage
TVSS. The SP are available as factory installed by adding the suffix “S” to the combiner box
catalog number or as kits a kit: REHTYPE2SP.
Table 3.53: 600 Vdc Type 2 Surge Protection Device
Nominal Maximum List Price $
Discharge Discharge Operating
Catalog Network Operating
Current Current Temperature; Factory
Number Voltage Current Kit
per 20 per 20 Celsius Installed
micro sec micro sec
Typical String Combination Box Dimensions REHTYPE2SP 600 Vdc 20kA 40kA <0.1nA -40 to +85 337.00 490.00