ABB Standard Macro: Complete Parameter List 115

This document provides a summary of the default macro for an ABB Standard drive. The macro includes a 2-wire control connection with analog inputs for frequency and current references. It allows selection of 3 constant speeds using digital inputs and provides relay outputs for drive status like ready, running and fault conditions. The macro uses default parameter values and provides an example connection diagram.

Uploaded by

Nguyen Danh Huy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views1 page

ABB Standard Macro: Complete Parameter List 115

This document provides a summary of the default macro for an ABB Standard drive. The macro includes a 2-wire control connection with analog inputs for frequency and current references. It allows selection of 3 constant speeds using digital inputs and provides relay outputs for drive status like ready, running and fault conditions. The macro uses default parameter values and provides an example connection diagram.

Uploaded by

Nguyen Danh Huy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

102 ACS550-02/U2 User’s Manual

ABB Standard macro


This is the default macro. It provides a general purpose, 2-wire I/O configuration,
with three (3) constant speeds. Parameter values are the default values defined in
section Complete parameter list on page 115.
Connection example:
X1
1…10 kohm 1 SCR Signal cable shield (screen)
2 AI1 External frequency reference 1: 0…10 V1
3 AGND Analog input circuit common
4 10V Reference voltage 10 V DC
5 AI2 Not used
6 AGND Analog input circuit common
7 AO1 Output frequency: 0…20 mA
8 AO2 Output current: 0…20 mA
9 AGND Analog output circuit common

10 24V Auxiliary voltage output +24 V DC


11 GND Auxiliary voltage output common
12 DCOM Digital input common for all
13 DI1 Start/Stop: Activate to start
14 DI2 Fwd/Rev: Activate to reverse rotation direction
15 DI3 Constant speed selection2
16 DI4 Constant speed selection2
17 DI5 Ramp pair selection: Activate to select 2nd acc/dec ramp pair
18 DI6 Not used

19 RO1C Relay output 1, programmable Note 1. The external reference is


Default operation: used as a speed reference if a vector
20 RO1A
Ready =>19 connected to 21 mode is selected.
21 RO1B
22 RO2C Note 2. Code:
Relay output 2, programmable
0 = open, 1 = connected
23 RO2A Default operation:
24 RO2B Running =>22 connected to 24 DI3 DI4 Output
25 RO3C Relay output 3, programmable 0 0 Reference through AI1
26 RO3A Default operation: 1 0 CONST SPEED 1 (1202)
27 RO3B Fault (-1) =>25 connected to 27 0 1 CONST SPEED 2 (1203)
(Fault => 25 connected to 26) 1 1 CONST SPEED 3 (1204)

Input signals Output signals Jumper setting


• Analog reference (AI1) • Analog output AO1: Frequency J1
ON

• Start, stop and direction (DI1,2) • Analog output AO2: Current AI1: 0…10 V
AI2: 0(4)…20 mA
ON

• Constant speed selection (DI3,4) • Relay output 1: Ready


• Ramp pair (1 of 2) selection (DI5) • Relay output 2: Running or
• Relay output 3: Fault (-1) J1
AI1: 0…10 V
1 2

ON

AI2: 0(4)…20 mA

Application macros