This document provides instructions for installing an inBIO46 0 system. It cautions the user to not power the system on before installation is complete. It recommends grounding all external devices, running wires through protective piping, and keeping exposed wire lengths short to avoid shorts or failures. The instructions then describe fixing the control panel track first before installing other components, and include an illustration of LED indicators and wire ports.

Uploaded by

Ibrahim Salem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
250 views2 pages

inBIO460 Installation Guide PDF

This document provides instructions for installing an inBIO46 0 system. It cautions the user to not power the system on before installation is complete. It recommends grounding all external devices, running wires through protective piping, and keeping exposed wire lengths short to avoid shorts or failures. The instructions then describe fixing the control panel track first before installing other components, and include an illustration of LED indicators and wire ports.

Uploaded by

Ibrahim Salem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SD Card Slot

3.Installation
inBIO46 0 Installa tion and Connection Guide After the following installation, fix the panel on the track first, and then install other components to original
positions. LINK
Version: 1.0 Date: June, 2011 Screws {
Auxiliary Input1 D
Control Panel Ethernet interface {
Auxiliary Input2 D
1.Cautions ACT {
Auxiliary Input3 D
Please pay attention to the following items. Mis-operation may lead to equipment failure even the personal injury. 1 {

SWITCH
Panel Track Dip switch Auxiliary Input4 D
1) Do not power on the system before the installation is completed. Do not carry on the install or repair operation at 2
{
EXT RS485 E
power on state. Thread holes
2) All external devices must be grounded.
1) Get through the thread hole 2) Fix the box 3) Install other components
PC RS485 interface
{ {
{
3) It is recommended that all wires should run through PVC or galvanized pipes. PWR
D Auxiliary output1

STATE
State Indicator
4) We recommend that the exposed part of all wires should be shorter than 4 mm, to avoid short circuit or communi-

RS485
4.LED Indicators and Wire Illustration
{

EXT
cation failure caused by unexpected contact of exposed wires. D Auxiliary output2 #1 Door
Exit Button D
5) It is recommended that the card reader and the exit button should be installed at height about 1.4-1.5m.
{
6) It is recommended to use the separated power supply for the control panel and the lock.
1) Meaning of LED indicators:
LINK indicator (green): Light always indicates TCP/IP communication is proper;
D Auxiliary output3
{#1 Door
Wiegand reader B
Description of normal working state: ACT indicator (yellow): Flash state indicates the data is in transmitting through TCP/IP communication. D Auxiliary output4
{

RS485
EXT RS485 indicator (yellow&green): Flash state indicates it is sending or receiving data through RS485 communication.
{#2 Door

PC
{
Power on the system, the power indicator (red) is on constantly i n normal working state, the run indicator (green) Exit Button D
PC RS485 indicator (yellow&green): Flash state indicates it is sending or receiving data through RS485 communication. C #1 Door {
is flashing, the communication indicator (yellow) is flashing in communicating state.
POWER indicator (red): Light always indicates the control panel is power on. #2 Door
Wiegand reader B

{
RUN indicator (green): Flash state indicates the system works normally.
2.Components CARD indicator (yellow): Flash state indicates card is punched on reader. C #2 Door { #3 Door
2) Recommended use of wires: Exit Button D

{
State Indicator Box Lock Hole Backup Battery Control Panel
Control Panel
A. Use 2-conducotor power cord.
B. Use 6-conductor wire between Wiegand reader and control panel (RVVP 6*0.5mm) (To choose the proper cord according C #3 Door
{ #3 Door
Wiegand reader B
Temper Switch
to the interface you connect, such as 6, 8, 10 cord.)

{{
C. Use 4-conducotor lock power cord (RVV 4*0.75mm) { #4 Door
1 D. Use 2-conducotor switch power cord (RVV 2*0.5mm) C #4 Door Exit Button D
Air Switch

Panel Track
2
E. Use 4-conducotor wire (RVVP 4*0.5mm)
3) The auxiliary input may be connected to infrared body detectors, alarm switches, etc.
A Lock Power
{ #4 Door
Wiegand reader B
Heat
Thread Hole Dissipation Hole Power Supply
4) The auxiliary output may be connected to door bells, alarms, etc. A Power of Control Panel {
Appearance of Panel Box Internal of Panel Box Get the Panel off the track 5) State Indicator is connected to the panel box, that is power indicator, run status indicator and communication status indicator.

1 2 3
5.DIP Switch Settings Stick the screw driver to the rectangular hole on the four corner of the panel back, push it from outside to inside. 8.Equipment Communication
After hearing the " click" sound, you can remove the case from the panel.
1) Number1-6 switch are used to set the control panel number in RS485 communication: It is adopted binary coding The following is “wet mode” lock connection with external power supply . The PC software can communicate with the panel according to the communication protocols (RS485 and TCP/IP) for data
and little endian, the address number setting by place these 6 switches are shown as figure below. Before setting FR107
exchange and remote management. The communication cable should be away from high-voltage lines as far as possible.
Do not keep the communication cable in parallel with power cords or bind them together.
the address, please keep the system power off. Place the corresponding switches to the desired status, and the Enlarged diagram
Diode of lock terminals 1. TCP/IP Communication Switch
address number should not be repeated in the network. + -
LOCK SEN
For example: Set the device number as 39 (39=1+2+4+32), the switches status is 111001, that is set number 1, 2, - +
GND LED
3 and 6 switches at “ON”. NO Lock NO 1# control panel 2# control panel n8 control panel
1
2) Number 7 switch is used to restore factory defaults: Switch it for three times within 10 seconds and restart the device, COM 2
3
4 PC
then all data will be cleared and the system restores factory default settings.

SWITCH
SWITCH

SWITCH
Diode NC
5
LOCK - +
3) Number 8 switch is used to set terminal resistance in RS485 communication: Switch it to“ON” status, that is add a +
PWR PWR PWR

- Jumper
+

STATE
STATE

STATE
Lock Power

RS485
RS485

RS485

EXT
EXT

EXT
terminal
terminal resistance of 120 ohm between 485+ and 485-.
FR107
-

RS485
RS485

RS485

PC
PC

PC
NC Lock
SWITCH

O
N
PWR
STATE

1 2 3 4 5 6 7 8 2. RS485 Communication
7.485 Reader (inBIO Reader) Connection
RS485
EXT

GND
485
RS485
PC

485-
32 485+ Converter
16 RS485 Terminal Resistance The control panel supports inBIO biometric verification reader and Wiegand reader. In use of inBIO reader, all operations
serial line
8 including storage, verification, etc. execute in control panel. No need to re-register the fingerprints for reader changing.
4
2 Restore Factory Settings Realize the real biometric reader connection. 485+ 485+ 485+
485- 485- 485-
1
inBIO reader connection: First of all, set the 485 address (device number) of reader by software, DIP switch or keypad. GND GND GND

PC
For reader 1, 2 (the odd number is for enter reader, and the even number is for exit reader), the and the door number is 1.
1# Control panel 2# Control panel 8# Control panel
Such as the 485 address is 1, 2, right figure connection, and etc. For more information, please refer to the user manual.
6.Lock Connection

O
N
1
SWITCH

SWITCH
SWITCH
1) The control panel provides lock control output interfaces. For NO lock, it is normal open when power is on, so

2
SWITCH

PWR

+12V
PWR PWR

STATE

3
STATE
STATE
GND

COM and NO terminals should be used. For NC lock, it is normal closed when power is on, so COM and NC

RS485
485-

EXT

RS485
RS485

EXT
EXT
485+

4
PWR

terminals should be used.

5
STATE

RS485

RS485
RS485

PC

PC
PC
RS485
EXT

6
2) The control panel supports “dry mode” and “wet mode” by using the jumper. For “wet mode”, short 2-3 and PC

7
8
RS485

4-5 terminals. The control panel and the lock use the separate power supply: One is connected with +12V and
PC

DIP Switch
GND of POWER interface (for the control panel), the other is connected with V+ and V- of LOCK interface
(for the lock). For the detailed settings of “dry mode” and “wet mode” , please refer to the Installation Guide. #1 Reader #2 Reader #8 Reader
1) Internationally accepted RVVP (shielded twisted-pair) wires should be used for communication to effectively avoid
The factory default is dry mode. interference. RS485 communication wires should be connected by means of bus cascade connection.
3) Considering of the consumption of the control panel, the Wiegand reader and the inBIO reader, t he standard 2) Considering stability of communication, it is recommended that the RS485 bus should be less than 600 meters.
power supply is 12V/3A . So we don't recommend the lock and the control panel use the common power supply. In inBIO reader connection, a single EXT485 interface can supply 500 mA (12V) current at most. so the entire current 3) One RS485 bus may hold 63 control panels, but it is not recommended to connect with less than 32 access control panels.
If it is necessary to use, we suggest to change the bigger one, such as 12V/5A.Except the power consumption consumption should be less than this max value. 4) In inBIO reader connection, if the reader and the control panel use the same power, it is recommended that the wire should
reserved, there are 2A current for the lock. For the common electrical lock (the standby current is 300mA, the For example, when you use the F11 reader (the standby current is less than 100mA, the max current is less than 120mA) be less than 100 meters. If you need to use in the longer distance, please use the separate power supply.
for inBIO reader connection, the max number is 4 F11 readers. For this panel, 2 readers can be connected at most. For 5) When the wire is longer than 300 meters, to enhance the stability of communication, it is necessary to keep
max current is 500mA), the max connected lock is 4.
number 8 switch of the first and the last control panel at “ON” status. That is add the RS485 terminal resistance
4) When the electrical lock is connected with the access control system, you need to parallel a Fr107 diode (equipped some of the devices with much bigger consumption, we suggest to use the separately power supply, to make sure the steady (120 ohm) of the two devices to the system. As shown in the figure above, turn number 8 of the DIP switches of
in the package) to prevent the self-inductance EMF affecting the system, do not reverse the polarities. operation. the 1# and 8# at "ON” status.
4 5 6