Geotechnical Design of Drilled Shafts Under Axial Loading
Geotechnical Design of Drilled Shafts Under Axial Loading
11.1 INTRODUCTION
The methods used to analyze and design drilled shafts under axial loading
have evolved since the 1960s, when drilled shafts came into wide use. The
design methods recommended for use today reflect the evolution of construc-
tion practices developed since that time.
11.2.1 Introduction
This chapter presents methods for computation of the capacity of drilled shafts
under axial loading. The methods for computation of axial capacity were
developed by O’Neill and Reese (1999).
The methods of analysis assume that excellent construction procedures
have been employed. It is further assume that the excavation remained stable,
and was completed with the proper dimensions, that the rebar was placed
properly, that a high-slump concrete was used, that the concrete was placed
in a correct manner, that the concrete was placed within 4 hours of the time
that the excavation was completed, and that any slurry that was used was
properly conditioned before the concrete was placed. Much additional infor-
mation on construction methods is given in O’Neill and Reese (1999). An-
other FHWA publication (LCPC, 1986), translated from French, also gives
much useful information.
323
324 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
While the design methods presented here have proved to be useful, they
are not perfect. Research continues on the performance of drilled shafts, and
improved methods for design are expected in the future. An appropriate factor
of safety must be employed to determine a safe working load. The engineer
may elect to employ a factor of safety that will lead to a conservative as-
sessment of capacity if the job is small. A load test to develop design param-
eters or to prove the design is strongly recommended for a job of any
significance.
The axial capacity of drilled shafts should be computed by engineers who are
thoroughly familiar with the limitations of construction methods, any special
requirements for design, and the soil conditions at the site.
Qult Qs Qb (11.1)
Qs ƒs As (11.2)
Qb qmax Ab (11.3)
where
Qult
axial capacity of the drilled shaft,
Qs
axial capacity in skin friction,
Qb
axial capacity in end bearing,
ƒs
average unit side resistance,
As
surface area of the shaft in contact with the soil along the side of
the shaft,
qmax unit end-bearing capacity, and
Ab area of the base of the shaft in contact with the soil.
triaxial tests, and the following equation is employed to compute the ultimate
value of unit load transfer at a depth z below the ground surface:
ƒs ␣ cu (11.4)
where
Qs 冕zbot
ztop
ƒszdA (11.5)
where
The peripheral areas over which side resistance in clay is computed are
shown in Figure 11.1. The upper portion of the shaft is excluded for both
compression and uplift to account for soil shrinkage in the zone of seasonal
moisture change. In areas where the depth of seasonal moisture change is
greater than 5 ft (1.5 m) or when substantial groundline deflection results
from lateral loading, the upper exclusion zone should be extended to deeper
depths. The lower portion of the shaft is excluded when the shaft is loaded
in compression because downward movement of the base will generate tensile
stresses in the soil that will be relieved by cracking of soil, and porewater
suction will be relieved by inward movement of groundwater. If a shaft is
loaded in uplift, the exclusion of the lower zone for straight-sided shafts
should not be used because these effects do not occur during uplift loading.
The value of ␣ is the same for loading in both compression and uplift.
328
Top Five Feet (1.5 Meters) Top Five Feet (1.5 Meters)
Noncontributing for Both Noncontributing for Both
Compression and Uplift Compression and Uplift
cu
␣ 0.55 for ⱕ 1.5 (11.6a)
pa
and
␣ 0.55 0.1 冉 cu
pa
1.5 冊 for 1.5 ⱕ
cu
pa
ⱕ 2.5 (11.6b)
where pa atmospheric pressure 101.3 kPa 2116 psf. (Note that 1.5 pa
152 kPa or 3,170 psf and 2.5 pa 253 kPa or 5290 psf.)
For cases where cu /pa exceeds 2.5, side resistance should be computed
using the methods for cohesive intermediate geomaterials, discussed later in
this chapter.
Some experimental measurements of ␣ obtained from load tests are shown
in Figure 11.2. The relationship for ␣ as a function of cu /pa defined by Eq.
11.6 is also shown in this figure. For values of cu /pa greater than 2.5, side
resistance should be computed using the recommendations for cohesive in-
termediate geomaterials, discussed later in this chapter.
When an excavation is open prior to the placement of concrete, the lateral
effective stresses at the sides of the drilled hole are zero if the excavation is
drilled in the dry or small if there is drilling fluid in the excavation. Lateral
stresses will then be imposed on the sides of the excavation because of the
fluid pressure of the fresh concrete. At the ground surface, the lateral stresses
from the concrete will be zero or close to zero. It can be expected that the
lateral stress from the concrete will increase almost linearly with depth, as-
suming that the concrete has a relatively high slump. Experiments conducted
by Bernal and Reese (1983) found that the assumption of a linear increase in
the lateral stress from fluid concrete for depths of concrete of 3.0 m (10 ft)
or more is correct. For depths greater than 3.0 m, the lateral stress is strongly
330 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
qmax N*c
c u (11.7)
where Ir is the rigidity index of the soil, which for a saturated, undrained
material ( 0) soil is expressed by
Es
Ir (11.9)
3cu
冋
qmax 0.667 1 0.1667
L
B册N*c
c u (11.10)
where:
cu Ir N*
c
where
Db
Nu 3.5 ⱕ9 for unfissured clay (11.12)
Bb
or from
Db
Nu 0.7 ⱕ9 for fissured clay (11.13)
Bb
In the expressions above, Db is the depth of the base of the bell below the
top of the soil stratum that contains the bell, but not counting any depth within
the zone of seasonal moisture change.
The unit uplift resistance should be applied over the projected area of the
bell, Au. The projected area is computed from
2
Au (B B2) (11.14)
4 b
Soil Profile. The soil profile is shown in Figure 11.3. The clay is overcon-
solidated. The depth to the water table was not given and is not needed in
making capacity calculations. However, the range of depth of the water table
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 333
20
Depth, ft
Clay 40
60
80
Figure 11.3 General soil description of Example Problem 1.
Loadings. The working axial load is 230 tons. No downdrag acting on the
shaft is expected, and vertical movement of the soil due to expansive clay is
not a problem. Effects due to lateral loading are also thought to be negligible.
The depth to the zone of seasonal moisture change is judged to be about 10
ft.
Factor of Safety. It is assumed that a load test has been performed in the
area, that the design parameters have been proven, and that the soil conditions
across the site are relatively uniform; therefore, an overall factor of safety of
2 was selected.
Ultimate Load. Using a factor of safety of 2, the ultimate axial load was
computed to be 460 tons.
Computations
SIDE RESISTANCE. For ease of hand computations, a constant value of ␣z equal
to 0.55 and an average cu of 2280 psf are assumed. However, the computer
program interpolates linearly the top and bottom values of cu with depth. The
hand computations are as follows:
Depth Interval, ft ⌬A, ft2 Avg. Effective Stress, tsf ␣Z ⌬Qs, tons
0–5 0 0
5–33.4 230.4 1.14 0.55 144.4
33.4–40 0 0
Qs 144.4
BASE RESISTANCE. The average undrained shear strength over two base di-
ameters below the base is 1.48 tsf, and the area of the base is 23.76 ft2.
By interpolation between the values of N* c shown in Table 11.2, N* c
8.81.
qmax N*
c cu (8.81) (1.48 tsf) 13.04 tsf
Ab 23.76 ft2
Qb (12.92 tsf) (23.76 ft2) 309.8 tons
TOTAL RESISTANCE
Qs 冕L
0
K⬘z tan c dA (11.16)
where
Equations 11.15 and 11.16 can be used in the computations of side resis-
tance in sand, but simpler expressions can be developed if the terms for K
and tan c are combined. The resulting expressions are shown in Eqs. 11.17
through 11.20.
Qs 冕L
0
⬘z dA (11.18)
336 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
N60
 (1.5 0.135兹z (ft)) or
15 (11.19b)
N60
 (1.5 .245兹z (m)) for N60 ⱕ 15
15
The design equations for drilled shafts in sand use SPT N60-values uncor-
rected for overburden stress. The majority of the load tests on which the
design equations are based were performed in the Texas Gulf Coast region
and the Los Angeles Basin in California. The N60-values for these load tests
were obtained using donut hammers with a rope-and-pulley hammer release
system. If a designer has N-values that were measured with other systems or
were corrected for level of overburden stress and rod energy, it will be nec-
essary to adjust the corrected N-values to the uncorrected N60 form for donut
hammers with rope-and-pulley hammer release systems before use in the de-
sign expressions of Eq. 11.19b and Table 11.4. Guidance for methods used
to correct SPT penetration resistances is presented in Chapter 3 of EM 1110-
1-1905.
The parameter  combines the influence of the coefficient of lateral earth
pressure and the tangent of the friction angle. The parameter also takes into
account the fact that the stress at the interface due to the fluid pressure of the
concrete may be greater than that from the soil itself. In connection with the
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 337
lateral stress at the interface of the soil and the concrete, the assumption
implicit in Eq. 11.17 is that good construction procedures are employed. See
Chapter 5 for further construction information. Among other factors, the
slump of the concrete should be 6 in. or more and drilling slurry, if employed,
should not cause a weak layer of bentonite to develop at the wall of the
excavation. The reader is referred to O’Neill and Reese (1999) for further
details on methods of construction.
The limiting value of side resistance shown in Eq. 11.17 is not a theoretical
limit but is the largest value that has been measured (Owens and Reese, 1982).
Use of higher values can be justified by results from a load test.
A comparison of  values computed from Eq. 11.19 and  values derived
from loading tests in sand on fully instrumented drilled shafts is presented in
Figure 11.4. As can be seen, the recommended expression for  yields values
that are in reasonable agreement with experimental values.
Equation 11.17 has been employed in computations of fsz, and the results
are shown in Figure 11.5. Three values of  were selected; two of these are
in the range of values of  for submerged sand, and the third is an approxi-
mate value of  for dry sand. The curves are cut off at a depth below 60 ft
(18 m) because only a small amount of data has been gathered from instru-
mented drilled shafts in sand with deep penetrations. Field load tests are
indicated if drilled shafts in sand are to be built with penetrations of over 70
ft (21 m).
It can be argued that Eqs. 11.17 and 11.18 are too elementary and that the
angle of internal friction, for example, should be treated explicitly. However,
the drilling process has an influence on in situ shearing properties, so the true
friction angle at the interface cannot be determined from a field investigation
that was conducted before the shaft was constructed. Furthermore, Eqs. 11.17
and 11.18 appear to yield an satisfactory correlation with results from full-
scale load tests.
The comparisons of results from computations with those from experi-
ments, using the above equations for sand, show that virtually every computed
value is conservative (i.e., the computed capacity is less than the experimen-
tally measured capacity). However, it is of interest that most of the tests in
sand are at locations where the sand was somewhat cemented. Therefore,
caution should be observed in using the design equations for sand if the sand
is clean, loose, and uncemented.
Either Eq. 11.15 or Eq. 11.17 can be used to compute the side resistance
in sand. The angle of internal friction of the sand is generally used in Eq.
11.15 in place of the friction angle interface at the interface of the concrete
and soil if no information is available. In some cases, only SPT resistance
data are available. In such cases, the engineer can convert the SPT penetration
resistance to the equivalent internal friction angle by using Table 11.3 as a
guide.
338 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
冉 冊冉 冊
vp tan ␦
L
B
Gavg
Ep
(11.24)
⌿ 再1 0.2 log10 冏 冏冎
100
(L/B)
(1 8 252) (11.25)
where
O’Neill and Reese (1999) examined Eq. 11.25 and concluded that typical
values of ⌿ fall into the range 0.74 to 0.85 for L/B ratios of 5 to 20. They
noted that Eq. 11.25 appears to overestimate ⌿ for L/B ratios larger than 20.
The value ⌿ can be taken conservatively to be 0.75 for design purposes.
L L
If L 10 m: qb 57.5 NSPT ⱕ 2.9 MPa (11.27)
10 m 10 m
L L
If L 32.8 ft: qb 0.60 NSPT ⱕ 30 tsf (11.29)
32.8 ft 32.8 ft
Soil Profile. The soil profile is shown in Figure 11.6. The water table is at a
depth of 4 ft below the ground surface.
Soil Properties. N60-values (blow counts per foot) from the SPT are included
in Figure 11.6.
Loadings. The working axial load is 170 tons, the lateral load is negligible,
and no downdrag is expected.
Factor of Safety. It is assumed that a load test has been performed nearby,
but considering the possible variation in the soil properties over the site and
other factors, an overall factor of safety of 2.5 is selected. The diameter will
be sufficiently small so that reduced end bearing will not be required. Con-
sequently, the global factor of safety can be applied to both components of
resistance.
Ultimate Load. The ultimate axial load is thus established as 2.5 170 tons
425 tons, since a global factor of safety (of 2.5) is used.
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 343
N60-Values
Depth, ft 0 10 20 30 40 50
0
20
Sand
40
60
Sand w/
Some
Limerock
80
Figure 11.6 General soil description of Example Problem 2.
Computations
SIDE RESISTANCE. Computations are performed assuming a total unit weight
of sand equal to 115 pcf. The hand computations are as follows:
BASE RESISTANCE. Computations for base resistance are performed using the
soil at the base of the shaft. At the 60-ft location, NSPT 21.
qb 0.60NSPT ⱕ 30 tsf
qb (0.6) (21) 12.6 tsf
344 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
Ab 7.07 ft2
Qb (7.07 ft2) (12.6 tsf) 89.1 tons
TOTAL RESISTANCE
Soil Profile. The soil profile is shown in Figure 11.7. The water table is at a
depth of 17 ft below the ground surface.
Loadings. The working axial load is 150 tons, no downdrag is expected, and
lateral loading is negligible. The depth to the zone of seasonal moisture
change is judged to be about 10 ft.
Silty Clay
20
32
N = 20
40
N = 25
Sand
60
N = 50
80 80
Figure 11.7 General soil description of Example Problem 3.
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 345
Factor of Safety. Soil conditions across the site are variable, and the foun-
dation is for a major and complex structure. An overall factor of safety of 3
was selected.
Ultimate Load. Using the factor of safety of 3, the ultimate axial load is
computed to be 450 tons.
Computations
SIDE RESISTANCE. Computations are performed assuming a total unit weight
of clay equal to 125 pcf and a total unit weight of sand equal to 115 pcf. For
ease of hand computations, an average value of  was selected for the sand
layer. The computations are as follows:
Avg. cu or
Soil Depth Interval, Effective Stress,
Type ft ⌬ A, ft2 tsf ␣Z or  ⌬Qs, tons
Clay 0–5 — (Cased) 0 0
Clay 5–32 254.5 0.81 0.55 113.4
Sand 32–59 254.5 1.887 0.589 282.9
Qs 396.3 tons
BASE RESISTANCE. Computations for base resistance are performed using the
soil at the base of the shaft. At the 59-ft location, NSPT 25.
TOTAL RESISTANCE
of 0.5 to 5.0 MPa (73 to 725 psi). The following intermediate geomaterials
usually fall within this category: argillaceous geomaterials (such as heavily
overconsolidated clay, hard-cohesive soil, and weak rock such as claystones)
or calcareous rock (limestone and limerock, within the specified values of
compressive strength).
Drilled shafts are attractive as a reliable foundation system for use in in-
termediate geomaterials. These geomaterials are not difficult to excavate, and
provide good stability and excellent capacity.
Two procedures for computation of side resistance in cohesive intermediate
geomaterials are presented by O’Neill and Reese (1999). One procedure is a
simplified version of a more detailed procedure developed by O’Neill et al.
(1996). Both procedures are presented in the following sections.
where ␣ (not equal in value to the ␣ for cohesive soils) is obtained from
Figure 11.8. The terms in the figure are defined as follows. Em is Young’s
modulus of the rock (i.e., the rock mass modulus), qu is the unconfined
strength of the intact material, and wt is the settlement at the top of the rock
socket at which ␣ is developed. The rock mass modulus can be estimated
from measurements of Young’s modulus of intact rock cores using Table 11.6.
The curves in Figure 11.8 are based on the assumption that the interface
friction angle between the rock and concrete is 30⬚. If the interface friction
is different from 30⬚, it should be modified using
tanrc
␣ ␣rc30⬚
or tan 30⬚ (11.31)
␣ 1.73␣rc30⬚ tan rc
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 347
To use Figure 11.8, the designer must estimate the horizontal pressure of the
fluid concrete acting at the middle of Layer i, n. If the concrete has a slump
of 175 mm (7 in.) or more and is placed at a rate of 12 m (40 ft) per hour,
then n at a depth z*i below the cutoff elevation up to 12 m (40 ft) can be
estimated from
n 0.65␥c z*
i (11.32)
is a joint effect factor that accounts for the presence of open joints that
are voided or filled with soft gouge material. The joint effect factor can be
estimated from Table 11.5.
qu,i is the design value for qu in Layer i. This is usually taken as the mean
value from intact cores larger than 50 mm (2 in.) in diameter. The possibility
of the presence of weaker material between the intact geomaterial that could
be sampled is considered through the joint effect factor, .
For a smooth rock socket in cohesive intermediate geomaterial, the side
resistance is computed using
a
(11.33)
If the rock socket has been roughened, the side resistance for a rough rock
socket in cohesive intermediate geomaterial is
ƒmax,i 0.8 冉 冉 冊册
⌬r
r
L⬘
L
0.45
qu,i (11.34)
where
ulation, is used to compute the axial capacity of drilled shafts socketed into
weak rock.
The direct simulation design model, based on an approximation of the
broad range of FEM solutions, is as follows:
Decide whether the socket of weak rock in which the drilled shaft is placed
requires subdivision into sublayers for analysis. If the weak rock is relatively
uniform, the behavior of axially loaded drilled shafts can probably be simu-
lated satisfactorily for design purposes using the simple procedure outlined
below. If there is significant layering of the weak rock in the depth range of
the socket, a load transfer function analysis should be modeled by a special
FEM, as recommended by O’Neill et al. (1996). Significant layering in this
respect will exist if the weak rock at the base of the shaft is considerably
stronger and stiffer than that surrounding the sides and/or if changes in the
stiffness and strength of the weak rock occur along the sides of the shaft.
Load transfer function analyses should also be conducted if sockets exceed
about 7.6 m (25 ft) in length.
Obtain representative values of the compressive strength qc of the weak
rock. It is recognized in practice that qu is often used to represent compressive
strength. Accordingly, qu will be used to symbolize qc in this criteria. When-
ever possible, the weak rock cores should be consolidated to the mean effec-
tive stress in the ground and then subjected to undrained loading to establish
the value of qu. This solution is valid for soft rocks with 0.5 qu 5.0 MPa
(73 qu 725 psi). The method also assumes that high-quality samples,
such as those obtained using triple-walled core barrels, have been recovered.
Determine the percentage of core recovery. If core recovery using high-
quality sampling techniques is less than 50%, this method does not apply,
and field loading tests are recommended to establish the design parameters.
Determine or estimate the mass modulus of elasticity of the weak rock,
Em. If Young’s modulus of the material in the softer seams within the harder
weak rock, Es, can be estimated, and if Young’s modulus of the recovered,
intact core material, Ei, is measured or estimated, then the following expres-
sion, can be used:
Em Lc
冘t 冘t
(11.35)
Ei ei
seams intact core segments
Es
In Eq. 11.32, Lc is the length of the core and 兺tseams is the summation of
the thickness of all of the seams in the core, which can be assumed to be
(1 rc) Lc, where rc is the core recovery ratio (percent recovery/100%) and
can be assumed equal to rc Lc. If the weak rock is uniform and without
significant soft seams or voids, it is usually conservative to take Em 115
qu. If the core recovery is less than 100%, it is recommended that appropriate
in situ tests be conducted to determine Em. If the core recovery is at least
350 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
50%, the recovered weak rock is generally uniform and the seams are filled
with soft geomaterial, such as clay, but moduli of the seam material cannot
be determined. Table 11.6 can be used, with linear interpolation if necessary,
to estimate very approximately Em /Ei. Use of this table is not recommended
unless it is impossible to secure better data.
The designer must decide whether the walls in the socket can be classified
as rough. If experience indicates that the excavation will produce a borehole
that is rough according to the following definition, then the drilled shaft may
be designed according to the method for the rough borehole. If not, or if the
designer cannot predict the roughness, the drilled shaft should be designed
according to the method for the smooth borehole.
A borehole can be considered rough if the roughness factor Rƒ will reliably
exceed 0.15. The roughness factor is defined by
Rƒ 冋 冉 冊册
⌬r
r
Lt
Ls
(11.36)
qu
ƒa (11.37)
2
tan rc
␣ ␣Figure 1.73 (␣Figure ) tan rc (11.39)
11.8
tan 30⬚ 11.8
If Em /Ei 1, adjust ƒa for the presence of soft geomaterial within the soft
rock matrix using Table 11.7. Define the adjusted value of ƒa as ƒaa. Em can
be estimated from the Em /Ei ratios based on RQD of the cores. In cases where
RQD is less than 50%, it is advisable to make direct measurements of Em in
situ using plate loading tests, borehole jacks, large-scale pressuremeter test,
or by back-calculating Em from field load tests of drilled shafts. The corre-
lations shown in Table 11.7 become less accurate with decreasing values of
RQD.
Estimate n, the normal stress between the concrete and borehole wall at
the time of loading. This stress is evaluated when the concrete is fluid. If no
other information is available, general guidance on the selection of n can be
n M ␥c zc (11.40)
where
The values shown in Fig. 11.10 represent the distance from the top of the
completed column of concrete to the point in the borehole at which n is
desired. Figure 11.10 may be assumed valid if the rate of placement of con-
crete in the borehole exceeds 12 m/hr and if the ratio of the maximum coarse
aggregate size to the borehole diameter is less than 0.02. Note that n for
slump outside the range of 125 to 225 mm (5 to 9 in.) is not evaluated. Unless
there is information to support larger values of n, the maximum value of zc
should be taken as 12 m (40 ft) in these calculations. This statement is pred-
icated on the assumption that arching and partial setting will become signif-
icant after the concrete has been placed in the borehole for more than 1 hour.
Note that Em increases with increasing qu, and the Poisson effect in the
shaft causes an increase in the lateral normal interface stresses as Em increases,
producing higher values of side load transfer at the frictional interface.
Determine the characteristic parameter n, which is a fitting factor for the
load-settlement syntheses produced by the finite element analyses. If the weak
rock socket is rough:
n
n (11.41)
qu
If the weak rock socket is smooth, estimate n from Figure 11.11. Note that
n was determined in Figure 11.11 for rc 30⬚. It is not sensitive to the
value of rc. However, ␣ is sensitive to rc, as indicated in Eq. 11.31.
If the socket has the following conditions—relatively uniform, and the soft
rock beneath the base of the socket has a consistency equivalent to that of
the soft rock along the sides of the shaft, 2 L/D 20, D 0.5 m, and 10
Ec /Em 500—then compute the load-settlement relation for the weak rock
socket as follows. Under the same general conditions, if the socket is highly
stratified and/or if the geomaterial beneath the base of the socket has a con-
sistency considerably different from that along the sides of the socket, use
the unit load transfer function version of this method described later.
Compute Qt (load still in the shaft at the top of the socket) versus wt
(settlement at the top of the socket) from Eq. 11.42 or Eq. 11.43, depending
on the value of n. These equations apply to both rough and smooth sockets.
Figure 11.11 Factor n for smooth sockets for various combinations of parameters.
354 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
D2
If Hƒ ⱕ n: Qt DLHƒƒaa q (11.42)
4 b
D2
If Hƒ n: Qt DLKƒƒaa q (11.43)
4 b
Equation 11.42 applies in the elastic range before any slippage has oc-
curred at the shaft–weak rock interface, and an elastic base response, as rep-
resented by the last expression on the right-hand side of the equation, also
occurs. Equation 11.43 applies during interface slippage (nonlinear response).
To evaluate Qt, a value of wt is selected, and Hƒ, which is a function of wt,
is evaluated before deciding which equation to use. If Hƒ n, evaluate Kƒ
and use Eq. 11.43; otherwise, use Eq. 11.42. Equations 11.44 and 11.45 are
used to evaluate Hƒ and Kƒ, respectively.
Em⍀
Hƒ w (11.44)
L⌫ƒaa t
(Hƒ n)(1 n)
Kƒ n ⱕ1 (11.45)
Hƒ 2n 1
where
⍀ 1.14 冉冊
L
D
0.5
0.05 冋冉 冊 册 冏 冏
L
D
0.5
1 log10
Ec
Em
0.44 (11.46)
⌫ 0.37 冉冊
L
D
0.5
0.15 冋冉 冊 册 冏 冏
L
D
0.5
1 log10
Ec
Em
0.13 (11.47)
Finally,
qb ⌳ w0.67
t (11.48)
where
⌳ 0.0134Em 冉 L/D
L/D 1 冊冋 200(兹L/D ⍀)(1 L/D)
L⌫ 册 (11.49)
Check the values computed for qb. If core recovery in the weak rock sur-
rounding the base is 100%, qb should not exceed qmax 2.5 qu. At working
loads, qb should not exceed 0.4 qmax.
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 355
Description of the Problem—Rough Socket. Consider the shaft and soil pro-
file shown in Figure 11.12. The user is asked to compute the load-settlement
relation for the socket and to estimate the ultimate resistance at a settlement
of wt 25 mm. The socket is assumed to be rough. The RQD for the sample
is 100%.
Computations
1. Since the core recovery and RQD are high, assume that Em 115 qu.
Note that Ec /Em 100%.
2. ƒaa ƒa 2.4/2 1.2 MPa, or 1200 kPa.
3. zc 6.1 m (depth from the top of the concrete to the middle of the
socket). Considering concrete placement specifications:
Overburden Layer
3.05 m (discounted)
Intermediate Geomaterial:
qu = 2.4 MPa, %Rec. = 100%
Interface: Rough, Unsmeared
Total Unit Weight = 20.4 kN/m
6.10 m Drilled Shaft:
Ec = 27.8 MPa
Unit Weight = 20.4 kN/m
Slump > 175 mm
Placement Rate > 12 m/hr
where wte signifies wt at the end of the elastic stage. (Note that the
elastic response occurs only up to a very small settlement in this
example.)
11. qb ⌳w0.67
t (Eqs. 3.50 and 3.51)
qb {[(115) (2400) (10/11)} {[200 (100.5 2.949) (11)]/[3.14 (6100)
0.651]}0.67 w0.67
t
Rough Socket
wt, mm Hƒ Kƒ Qs, kN qb, kPa Qb, kN Qt, kN
1 0.0541 0.0540 758.2 373.4 109.1 867.3
2 0.1082 0.1046 1466.9 594.2 173.6 1640.5
3 0.1623 0.1500 2103.7 779.7 227.9 2331.6
4 0.2164 0.1910 2679.1 945.4 276.3 2955.4
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 357
Note that
Figure 11.13 Computed axial load versus settlement for Example Problem 4.
compute the load-settlement relation for the socket and to estimate the ulti-
mate resistance at a settlement of wt 25 mm.
Computations
1. ƒa ƒaa ␣qu.
2. Referring to Figure 11.13, for n / p 1.13 and qu 2.4 MPa, we
have ␣ 0.12.
3. ƒa ƒaa 0.12(2400) 288 kPa.
4. qu / p 2400/101.3 23.7 and Em / n 115 (2.4) (1000)/114.5
2411.
5. From Figure 11.13, n 0.11.
6. ⍀ 2.949 (unchanged); ⌫ 0.651 (unchanged).
7. Hƒ {[l15(2400) 2.949)]/[3.14 (6100 mm)(0.651) 288]}wt
0.226 wt.
8. Kƒ 0.11 [(0.226 wt 0.11)(1 0.11)]/[0.226 wt 2(0.11) 1]
0.11 (0.226 wt 0.11)(0.89)/(0.226 wt 0.78).
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 359
Smooth Socket
wt qb Qb Qs Qt
mm Hƒ Kƒ kPa kN kN kN
1 0.23 0.213 373 109.1 717 826
2 0.45 0.357 594 173.6 1203 1377
3 0.68 0.457 780 227.9 1539 1767
4 0.91 0.530 945 276.3 1785 2061
5 1.13 0.586 1098 320.8 1972 2293
6 1.36 0.630 1240 362.5 2120 2482
7 1.58 0.665 1375 402.0 2239 2641
8 1.81 0.694 1504 439.6 2337 2777
9 2.04 0.719 1628 475.7 2420 2896
10 2.26 0.740 1747 510.5 2491 3001
11 2.49 0.758 1862 544.1 2551 3095
12 2.72 0.773 1974 576.8 2604 3181
13 2.94 0.787 2082 608.6 2650 3259
14 3.17 0.799 2188 639.6 2691 3331
15 3.40 0.810 2292 669.8 2728 3398
16 3.62 0.820 2393 699.4 2761 3460
17 3.85 0.829 2492 728.4 2791 3519
18 4.08 0.837 2590 756.9 2817 3574
19 4.30 0.844 2685 784.8 2842 3627
20 4.53 0.851 2779 812.2 2864 3676
21 4.75 0.857 2872 839.2 2885 3724
22 4.98 0.862 2692 865.8 2904 3770
23 5.21 0.868 3052 891.9 2921 3813
24 5.43 0.873 3140 917.7 2937 3855
25 5.66 0.877 3227 943.2 2953 3896
14. The numerical values for a smooth socket are graphed in Figure 11.13
in comparison with the values from a rough socket to illustrate the
effect of borehole roughness in this problem. Note again that qb 2.5
qu.
The value of ⌿ is taken to be 1.0 when (Ec /Em) (B/D)2 ⱖ 4, or 0.7 when
(Ec /Em) (B/D)2 4, unless field loading tests are performed. Ec and Em are
the composite Young’s modulus of the shaft’s cross section and rock mass,
respectively, B is the socket diameter, and D is the socket length.
冉
qmax 兹s 兹m兹s s qu 冊 (11.51)
Ds
d 1 0.4 ⱕ 3.4 (11.53)
B
3 cs /Bb
Ksp (11.54)
10兹1 300 ␦ /cs
where
The above equations are valid for a rock mass with spacing of disconti-
nuities greater than 12 in. (0.3 m) and thickness of discontinuities less than
0.2 in. (5 mm) (or less than l in. [25 mm] if filled with soil or rock debris)
and for a foundation with a width greater than 12 in. (305 mm). For sedi-
mentary or foliated rocks, the strata must be level or nearly so. Note that Eq.
11.52 is different in form from that presented in the Canadian Foundation
Engineering Manual in that a factor of 3 has been added to remove the
implicit factor of safety of 3 contained in the original form. Further, note that
the form of Eq. 11.53 differs from that in the first edition of the Manual.
where ⬘vi is the vertical effective stress at the middle of Layer i. The earth
pressure coefficient K0i and effective angle of internal friction of the gravel
⬘ can be estimated from field or laboratory testing or from
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 363
(11.56)
(11.57)
where N60,i is the SPT penetration resistance, in blows per foot (or blows per
300 mm), for the condition in which the energy transferred to the top of the
drive string is 60% of the drop energy of the SPT hammer, uncorrected for
the effects of overburden stress; and pa is the atmospheric pressure in the
selected system of units (usually 1 atmosphere, which converts to 101.4 kPa
or 14.7 psi).
⬘vb (11.58)
where N60 is the blow count immediately below the base of the shaft.
The value of qmax should be reduced when the diameter of the shaft Bb is
more than 1.27 m (50 in.). If the diameter of the shaft is between 1.27 and
1.9 m (50 to 75 in.), qmax,r is computed using
1.27
qmax,r q (11.59)
Bb (m) max
where
364 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
L
a 0.28Bb (m) 0.083 (11.61)
Bb
where
L depth of base below the ground surface or the top of the bearing
layer if the bearing layer is significantly stronger than the overlying
soils, and
sub average undrained shear strength of the soil or rock between the
elevation of the base and 2Bb below the base. If the bearing layer is
rock, sub can be taken as qu /2.
where
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 365
Figure 11.14 Engineering classification of intact rock (after Deere, 1968, by Horvath
and Kenney, 1979).
366 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
Peck, 1976, as presented by Horvath and Kenney, 1979). The figure shows
medium clay at the low range and gneiss at the high range. Concrete and
steel are also shown for reference. Several of the rock categories have com-
pressive strengths that are in the range of that for concrete or higher. As can
be expected, many of the design procedures for drilled shafts in rock are
directed at weak rock because strong rock could well be as strong as or
stronger than the concrete in the drilled shaft. In this situation, the drilled
shaft would fail structurally before any bearing capacity failure could occur.
Except for instances where drilled shafts were installed in weak rocks such
as shales or mudstones, there are virtually no occasions where loading has
resulted in failure of the drilled shaft foundation. An example of a field test
where failure of the drilled shaft was impossible is shown in Figures 11.15
and 11.16. The rock at the site was a vuggy limestone that was difficult to
core without fracture. Only after considerable trouble was it possible to obtain
the strength of the rock. Two compression tests were performed in the labo-
ratory, and in situ grout-plug tests were performed under the direction of
Schmertmann (1977).
The following procedure was used for the in situ grout-plug tests. A hole
was drilled into the limestone, followed by placement of a high-strength steel
bar into the excavation, casting of a grout plug over the lower end of the bar,
and pulling of the bar after the grout had cured. Five such tests were per-
Load
0 1 2 3 4 5 6 7 8 9
MN
200 400 600 800 1000
0 Tons
Test Shaft #1
2
0.1
Settlement
4 Test Shaft #2
0.2
6
0.3
8
mm
inches
Figure 11.15 Load-settlement curves for Test Shafts No. 1 and 2, Florida Keys.
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 367
Load
0 1 2 3 4 5 6 7 8 9
MN
2
10
Test Shaft #2
4
Test Shaft #1
6 20
8
30
10
12 40
14
50
Figure 11.16 Load-distribution curves for Test Shafts Nos. 1 and 2, Florida Keys.
formed over the top 10 ft of the rock. Side resistance ranged from 12.0 to
23.8 tons/ft2 (1.15 to 2.28 MPa), with an average of approximately 18.0 tons/
ft2 (1.72 MPa). The compressive strength of the rock was approximately 500
psi (3.45 MPa), putting the vuggy limestone in the lower ranges of the
strength of the chalk shown in Figure 11.14.
Two axial load tests were performed at the site on cylindrical drilled shafts
that were 36 in. (914 mm) in diameter (Reese and Nyman, 1978). Test Shaft
No. 1 penetrated 43.7 ft (13.3 m) into the limestone, and Test Shaft No. 2
penetrated 7.6 ft (2.32 m). Test Shaft No. 1 was loaded first, with the results
shown in Figures 11.15 and 11.16, and it was then decided to shorten the
penetration and construct Test Shaft No. 2. As may be seen in Figure 11.15,
the load-settlement curves for the two shafts are almost identical, with Test
Shaft No. 2 showing slightly more settlement at the 1000-ton (8.9-MN) load
(the limit of the loading system). The settlement of the two shafts under the
maximum load is quite small, and most of the settlement (about 0.10 in., 2.5
mm) was due to elastic shortening of the drilled shafts.
The distribution of load with depth, determined from internal instrumen-
tation in the drilled shafts, for the maximum load is shown in Figure 11.16.
As may be seen, no load reached the base of Test Shaft No. 1, and only about
368 GEOTECHNICAL DESIGN OF DRILLED SHAFTS UNDER AXIAL LOADING
60 tons (530 kN) reached the base of Test Shaft No. 2. The data allowed a
design for the foundations to be made at the site with confidence; however,
as indicated, it was impossible to find the ultimate values of load transfer in
side resistance and in end bearing because of the limitations of the loading
equipment in relation to the strength of the rock. The results are typical for
drilled shafts that are founded in rock that cannot develop the ultimate values
of load transfer.
A special program of subsurface exploration is frequently necessary to
obtain the in situ properties of the rock. Not only is it important to obtain the
compressive strength and stiffness of the sound rock, but it is necessary to
obtain detailed information on the nature and spacing of joints and cracks so
that the stiffness of the rock mass can be determined. The properties of the
rock mass will normally determine the amount of load that can be imposed
on a rock-socketed drilled shaft. The pressuremeter has been used to inves-
tigate the character of in situ rock, and design methods have been proposed
based on such results.
An example of the kind of detailed study that can be made concerns the
mudstone of Melbourne, Australia. The Geomechanics Group of Monash Uni-
versity in Melbourne has written an excellent set of papers on drilled shafts
that give recommendations in detail for subsurface investigations, determi-
nation of properties, design, and construction (Donald et al., 1980; Johnston
et al., 1980a, 1980b; Williams, 1980; Williams et al., 1980a, 1980b; Williams
and Erwin, 1980). These papers imply that the development of rational meth-
ods for the design of drilled shafts in a particular weak rock will require an
extensive study and, even so, some questions may remain unanswered. It is
clear, however, that a substantial expenditure for the development of design
methods for a specific site could be warranted if there is to be a significant
amount of construction at the site.
Williams et al. (1980b) discussed their design concept and stated: ‘‘A sat-
isfactory design cannot be arrived at without consideration of pile load tests,
field and laboratory parameter determinations and theoretical analyses; ini-
tially elastic, but later hopefully also elastoplastic. With the present state of
the art, and the major influence of field factors, particularly failure mecha-
nisms and rock defects, a design method must be based primarily on the
assessment of field tests.’’
Other reports on drilled shafts in rock confirm the above statements about
a computation method; therefore, the method presented here must be consid-
ered to be approximate. Detailed studies, including field tests, are often
needed to confirm a design.
The procedure recommended by Kulhawy (1983) presents a logical ap-
proach. The basic steps are as follows.
1. The penetration of the drilled shaft into the rock for the given axial
load is obtained by using an appropriate value of side resistance (see
the later recommendation).
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 369
2. If the full load is taken by the base of the drilled shaft, the settlement
of the drilled shaft in the rock is computed by adding the elastic short-
ening to the settlement required to develop end bearing. The stiffness
of the rock mass is needed for this computation.
3. If the computed settlement is less than about 0.4 in. (10 mm), the side
resistance will dominate and little load can be expected to reach the
base of the foundation.
4. If the computed settlement is more than about 0.4 in. (10 mm), the bond
in the socket may be broken and the tip resistance will be more
important.
Kulhawy (1983) presents curves that will give the approximate distribution
of the load for Steps 3 and 4; however, the procedure adopted here is to
assume that the load is carried entirely in side resistance or in end bearing,
depending on whether or not the computed settlement is less or more than
0.4 in.
The recommendations that follow are based on the concept that side resis-
tance and end bearing will not develop simultaneously. The concept is con-
servative, of course, but it is supported by the fact that the maximum load
transfer in side resistance in the rock will occur at the top of the rock, where
the relative settlement between the drilled shaft and the rock is greatest. If
the rock is brittle, which is a possibility, the bond at the top of the rock could
fail, with the result that additional stress is transferred downward. There could
then be a progressive failure in side resistance.
Note that the settlement will be small if the load is carried only in side
resistance. The settlement in end bearing could be considerable and must be
checked as an integral part of the analysis.
The following specific recommendations are made to implement the above
general procedure:
1. Horvath and Kenney (1979) did an extensive study of the load transfer
in side resistance for rock-socketed drilled shafts. The following equation is
in reasonable agreement with the best-fit curve that was obtained where no
unusual attempt was made to roughen the walls:
where
QST L
c (11.65)
AEc
where
QST I
w (11.66)
BbEm
where
1.1
1.0
0.9
0.8
Influence Factor Ip
0.7 Q
Settlement
0.6 L Econcrete
0.5
B Emass
0.4 10
0.3
0.2 50
100
0.1 5000
0 2 4 6 8 10 12 20
Embedment Ratio L/B
Figure 11.17 Elastic settlement influence factor as a function of embedment ratio
and modular ratio (after Donald et al., 1980).
the intact rock by using the RQD. As may be seen, the scatter in the data is
great but the trend is unmistakable.
5. The bearing capacity of the rock can be computed by a method pro-
posed by the Canadian Geotechnical Society (1978):
qa Ksp qu (11.67)
3 cs /Bb
Ksp (11.68)
10兹1 300 ␦ /cs
where
For the equations for the design of drilled shafts in rock to be valid, the
construction must be carried out properly. Because the load-transfer values
are higher for rock, the construction requires perhaps more attention than does
construction in other materials. For example, for the load transfer in side
resistance to attain the allowable values, there must be a good bond between
the concrete and the natural rock. An excellent practice is to roughen the
sides of the excavation if this appears necessary. There may be occasions
when the drilling machine is underpowered and water is placed in the exca-
vation to facilitate drilling. In such a case, the sides of the excavation may
11.6 DESIGN EQUATIONS FOR AXIAL CAPACITY IN COMPRESSION AND IN UPLIFT 373
be ‘‘gun barrel’’ slick, with a layer of weak material. Roughening of the sides
of the excavation is imperative.
Any loose material at the bottom of the excavation should be removed
even though the design is based on side resistance.
Another matter of concern with regard to construction in rock is whether
or not the rock will react to the presence of water or drilling fluids. Some
shales will lose strength rapidly in the presence of water.
Soil Profile. The soil profile is shown in Figure 11.19. Only a small amount
of water was encountered at the site during the geotechnical investigation.
Soil Properties. The dolomite rock found at the site had a compressive
strength of 8000 psi, and the RQD was 100%. Young’s modulus of the intact
rock was estimated as 2.0 106 psi, and the modulus of the rock mass was
identical to this value. Assume that the spacing of discontinuities is about 7
ft and that the thickness of the discontinuities is negligible.
Construction. The excavation can be made dry. A socket can be drilled into
the strong rock and inspected carefully before concrete is poured.
Loading. The lateral load is negligible. The working axial load is 300 tons.
No downdrag or uplift is expected.
Depth, ft
Clay
Dolomite
No evident joints
Hand Computations. Assuming that all load is transferred in end bearing and
using the method proposed by the Canadian Geotechnical Society (1978):
qa Ksp qu
qa (0.5)(8000) 4000 psi
QB (4000)( /4)(42)2 5.54 106 lb 2771 tons
the results of the load test may be used to reduce the size of the foundation
shafts to obtain a more economically efficient design.
the drilling of the technique shafts before they submit their bids for shaft
construction. Observation of the technique shafts allows the interested con-
tractors to observe the local conditions to determine the tools and equipment
required to complete the job successfully. Use of technique shafts has reduced
claims for changed conditions on many projects.
Figure 11.20 Computed axial capacity versus measured axial capacity (from Isen-
hower and Long, 1997).
PROBLEMS 377
PROBLEMS
P11.1. Compute the axial capacity of drilled sand in sand. The shaft di-
ameter is 3 ft and the length is 50 ft.
The soil profile is: