NEPAL NATIONAL BUILDING CODE
NBC 107 : 1994
               PROVISIONAL RECOMMENDATION ON
                         FIRE SAFETY
NBC107V0.RV8                                   12 May 1994
                              His Majesty's Government of Nepal
                    Ministry of Physical Planning and Works
         Department of Urban Development and Building Construction
                                 Babar Mahal, Kathmandu, NEPAL
                                                2060
     NEPAL NATIONAL BUILDING CODE
                                       NBC 107 : 1994
               PROVISIONAL RECOMMENDATION ON
                         FIRE SAFETY
This publication represents a standard of good practice and therefore
takes the form of recommendations. Compliance with it does not confer
immunity from relevant legal requirements, including bylaws
                 >L % sf] ;/sf/ -dlGqkl/ifb\_ sf] ldlt @)^).$.!@ sf] lg0f{ofg';f/ :jLs[t
NBC107V0.RV8                                                                               12 May 1994
                        His Majesty's Government of Nepal
                    Ministry of Physical Planning and Works
         Department of Urban Development and Building Construction
                         Babar Mahal, Kathmandu, NEPAL
                                     2060
NBC107V0.RV8                                                         12 May 1994
                                                  i
Preface
This Nepal Standard was prepared during 1993 as part of a project to prepare a draft National Building
Code for Nepal.
In 1988 the Ministry of Housing and Physical Planning (MHPP), conscious of the growing needs of
Nepal's urban and shelter sectors, requested technical assistance from the United Nations Development
Programme and their executing agency, United Nations Centre for Human Settlements (UNCHS).
A programme of Policy and Technical Support was set up within the Ministry (UNDP Project
NEP/88/054) and a number of activities have been undertaken within this framework.
The 1988 earthquake in Nepal, and the resulting deaths and damage to both housing and schools, again
drew attention to the need for changes and improvement in current building construction and design
methods.
Until now, Nepal has not had any regulations or documents of its own setting out either requirements
or good practice for achieving satisfactory strength in buildings.
In late 1991 the MHPP and UNCHS requested proposals for the development of such regulations and
documents from international organisations in response to terms of reference prepared by a panel of
experts.
This document has been prepared by the subcontractor's team working within the Department of
Building, the team including members of the Department and the MHPP. As part of the proposed
management and implementation strategy, it has been prepared so as to conform with the general
presentation requirements of the Nepal Bureau of Standards and Metrology.
The subproject has been undertaken under the aegis of an Advisory Panel to the MHPP.
The Advisory Panel consisted of :
       Mr. UB Malla, Joint Secretary, MHPP                                                 Chairman
       Director General, Department of Building
        (Mr. LR Upadhyay)                                                                   Member
       Mr. AR Pant, Under Secretary, MHPP                                                   Member
       Director General, Department of Mines & Geology
        (Mr. PL Shrestha)                                                                   Member
       Director General, Nepal Bureau of Standards & Metrology
        (Mr. PB Manandhar)                                                                  Member
       Dean, Institute of Engineering, Tribhuvan University
        (Dr. SB Mathe)                                                                      Member
       Project Chief, Earthquake Areas Rehabilitation &
        Reconstruction Project                                                              Member
       President, Nepal Engineers Association                                               Member
       Law Officer, MHPP (Mr. RB Dange)                                                     Member
       Representative, Society of Consulting Architectural &
        Engineering Firms (SCAEF)                                                           Member
       Representative, Society of Nepalese Architects (SONA)                                Member
       Deputy Director General, Department of Building,
        (Mr. JP Pradhan)                                                          Member-Secretary
                                                 ii
The Subcontractor was BECA WORLEY INTERNATIONAL CONSULTANTS LTD. of New
Zealand in conjunction with subconsultants who included :
       Golder Associates Ltd., Canada
       SILT Consultants P. Ltd., Nepal
       TAEC Consult (P.) Ltd., Nepal
       Urban Regional Research, USA
Principal inputs to this Standard came from :
       Mr. YK Parajuli, TAEC
       Mr. JR Pokharel, TAEC
Revisions and Updated to this code came from :
        Mr. Purna P. Kadariya, DG, DUDBC
        Mr. Kishore Thapa, DDG DUDBC
        Mr. Mani Ratna Tuladhar, Sr. Div. Engineer, DUDBC
        Mr. Jyoti Prasad Pradhan, Ex. DDG, DOB
        Mr. Bhubaneswor Lal Shrestha, Ex. DDG, DOB
        Mr. Uttam Shrestha, Architect, Architects’ Module Pvt. Ltd.
        Mr. Manohar Lal Rajbhandhari, Sr. Structural Engineer, MR Associates
        Mr. Amrit Man Tuladhar, Civil Engineer, DUDBC
                                                                         iii
                                                        TABLE OF CONTENTS
Preface................................................................................................................................................ i
0          Foreword................................................................................................................................ iv
1          Scope...................................................................................................................................... 1
2          Interpretation........................................................................................................................ 1
           2.1        General....................................................................................................................... 1
           2.2        Terminology............................................................................................................... 1
3          Types of Construction and Appliances................................................................................ 1
           3.1        Fire Places.................................................................................................................. 1
           3.2        Fire Extinguishers..................................................................................................... 2
4          Fire Zones.............................................................................................................................. 2
5          General Requirements.......................................................................................................... 2
           5.1        Provision of a Proper Access.....................................................................................                2
           5.2        Provision of Wide Doors...........................................................................................               2
           5.3        Provision of Fire Escape Ways.................................................................................                   2
           5.4        Provision of Open Space...........................................................................................               3
6          Exit Requirements................................................................................................................. 3
           6.1        General Requirements.............................................................................................. 3
           6.2        Number of Exits......................................................................................................... 3
                      6.2.1 Stairs.................................................................................................................. 3
                      6.2.2 Fire Escapes...................................................................................................... 3
                      6.2.3 Exit Doors......................................................................................................... 4
7          Access to a Building............................................................................................................... 4
8          Lightning Arresters/Conductors.......................................................................................... 4
9          References.............................................................................................................................. 4
                                            iv
0.   Foreword
     0.1   This Standard covers the basic requirements for fire safety in the design of ordinary
           buildings.
     0.2   This Standard, with due consideration to the severe limitations on the issue of fire
           protection in Nepali conditions, takes a modest approach. It deals only with the
           minimum requirements of exits from and access to ordinary residential buildings from
           the fire safety point of view. Designers are encouraged, wherever possible, to
           incorporate higher levels of fire safety in their designs by following other relevant
           reference, Standards or Codes.
                                                      1
1        Scope
         1.1     This Standard provides fundamental requirements for fire safety in ordinary buildings.
                 These requirements do not necessarily cover the fire safety provisions needed for other
                 buildings. For the design of such other buildings, other relevant Codes and Standards
                 which might be followed have been suggested.
2        Interpretation
         2.1     General
                 2.1.1    In this Standard the word "shall" indicates a requirement that is to be adopted in
                          order to comply with the Standard, while the word "should" indicates
                          recommended practice.
                 2.1.2    Commentary clauses are prefaced by the letter C and the number of the
                          appropriate clause subject to comment.
                 2.1.3    Words implying the singular also include the plural and vice-versa where the
                          context requires it.
         2.2     Terminology
                 For the purpose of this Standard, the following definitions shall apply, unless
                 inconsistent with the context :
                 IMPORTANT BUILDINGS means those buildings which either house facilities
                 essential before and after disaster (eg, hospitals, fire and police stations,
                 communication centres, etc), or which by their very purpose have to house several
                 persons at one time (eg, cinema halls, schools, convention centres, etc), or will have
                 national and international importance (eg, palaces, etc), or which house hazardous
                 facilities (eg, toxic or explosive facilities, etc).
                 ORDINARY BUILDINGS are the buildings, which do not come under the category
                 of important buildings. They include commercial and office buildings.
3        Types of Construction and Appliances
         3.1     Fire Places
                 All buildings having a kitchen should be provided with a fireplace and a chimney in
                 order to reduce the possibilities of the occurrence of accidental fire. Open hearths
                 should be discouraged and eliminated wherever possible. Timber construction should
                 not be placed near the fire place, nor should it remain exposed in the vicinity of fire.
                 Such surfaces should remain encased by plaster, whether of mud or other binders,
                 suitable for the purpose.
NBC107V0.RV8                                                                                       12 May 1994
                                                    2
         3.2    Fire Extinguishers
                Occupants are encouraged to install appropriate portable fire extinguishers in their
                building.
                Where open hearth or kerosene stoves are used for cooking, sufficient water should be
                stored in containers for emergency use in case of fire.
4        Fire Zones
         In urban areas, the demarcation of fire zones should be carried out in consultation with the
         relevant municipal authority as and when deemed necessary.
         These shall conform to the requirements specified by the Department of Urban
         Development and Building Construction or any other agency responsible for developing and
         demarcating such fire zones.
5        General Requirements
         All buildings shall be designed in such a way that they can contribute to the containment of a
         fire and thus reduce its spread to other buildings.
         5.1    Provision of a Proper Access
                Every building should have an access as defined by Architectural Design
                Requirements (NBC 206) and should be wide enouth to enable the fireman to easily
                approach to the building site.
         5.2    Provision of Wide Doors
                The entry door shall be as defined by Architectural Design Requirements (NBC 206)
                and should be sufficiently wide and tall so that easy access in available to the fire man.
         5.3    Provision of Fire Escape Ways
                All buildings should have sufficient ways as defined by Architectural Design
                Requirements (NBC 206) so as to allow the rapid evacuation of all occupants in the
                event of fire, if any. In addition to the main entrance, the side and/or rear entrance
                shall be incorporated in the design.
                The set back and/ or open space shall conform to the planning and building by-laws
                adopted by the concerned and authorized territorial authority.
         5.4    Provision of Open Space
                The front entrance should have enough open space as defined by Architectural Design
                Requirements (NBC 206) so that a number of people can gather and contribute in
                extinguishing the fire, if any.
NBC107V0.RV8                                                                                     12 May 1994
                                                     3
6        Exit Requirements
         6.1   General Requirements
               An exit normally shall consist of either a doorway, corridor or passageway to an
               internal staircase, to an external staircase, to a verandah leading to the street, to the roof
               of a building, or to the street. The exit may also lead to another building in the
               neighbourhood. The exit should :
               a)      be able to allow the evacuation of all the occupants in a relatively short time;
               b)      meet the minimum requirements as to size;
               c)      be free of any obstructions and shall not provide any resistance to movement;
               d)      be clearly visible, preferably with proper signs;
               e)      be continuous and shall not intrude into private space.
         6.2   Number of Exits
               6.2.1   Stairs
                       The number of stairs in any building, especially when it exceeds 500 square
                       metres in plinth area, shall be a minimum of two, one internal and the other an
                       external fire escape. Additional stairs shall be provided in proportion to any
                       increase in the plinth area.
                       In the case of residential buildings, the minimum width of the stairs shall be 90
                       cm. For other buildings, the minimum width shall be 1.5 m. The distance
                       from any point in a passageway to a staircase in a building shall not exceed 20
                       metres.
               6.2.2   Fire Escapes
                       Every building more than five storeys high shall have a separate fire escape
                       having a minimum width of 75 cm. The fire escape shall have a minimum
                       tread width of 20 cm and each riser shall be not more than 19 cm high. The
                       number of risers per flight shall not be more than 15. Such a fire escape shall
                       carry users towards an open space.
               6.2.3   Exit Doors
                       Exit doors shall open to a passageway or to a corridor.
                       They should open outwards, but without restricting the movement of people
                       passing outside the door.
                       The maximum distance of such an exit doorway from any point in a passage
                       shall be 20 m.
NBC107V0.RV8                                                                                        12 May 1994
                                                    4
                          The exit doorway shall neither be smaller than 90 cm in width, nor 180 cm in
                          height.
7        Access to a Building
         It shall comply with all applicable zoning requirements and by-laws of the local planning and
         building authority.
         The access leading to a building should preferably be by a road at least four metres wide, and
         no such road should lead to a dead end. The road should not have such sharp or restricted
         turns that the passage of a fire engine is made difficult in the event of fire.
8        Lightning Arresters/Conductors
         There have been many incidents in Nepal when lightning strikes have resulted in fire in
         buildings and a consequential loss of life and property. The need to install lightning
         arresters/conductors is therefore important.
         A lightning arrester shall be located in the highest part of every building and it shall be
         connected by a conductor to an earth rod buried in the earth. The lightning arrester shall be so
         located that as much as possible of the building lies inside the surface of an imaginary cone
         having a vertex angle of 45 degrees and its apex at the top of the arrester.
9        Referances
                  National Building Code of India 1983, Part IV, Bureau of Indian Standards, New
                   Delhi.
                  United Building Code (UBC), Part VII, Chapters 33 & 37, USA.
                  MV Lisitsyan and EC Pronin, "Architectural Design for Dwelling Houses", Moscow,
                   1990 (available in Russian and English).
NBC107V0.RV8                                                                                     12 May 1994