Discipline:           Engineering (Electrical)                                                      Category:                       Standard
High Voltage Cable Selection
                    Guide
                                                             PDS 14
                                                              Applicability
                                 ARTC Network Wide                    9       CRIA (NSW CRN)
                                                           Primary Source
                                               RIC Standard EP 20 10 00 02 SP version 1.0
                                                         Document Status
Version            Date Reviewed                Prepared by               Reviewed by               Endorsed                 Approved
1.3                1 September 2010             Standards                 National Bridges          Exec Manager             CEO
                                                                          & Structures Eng          SS&P 23/09/2010
                                                                          / Mgr Standards
                                                       Amendment Record
Version            Date Reviewed               Clause          Description of Amendment
1.1                5 January 2005                               Reformatted to ARTC Standard
1.2                11 March 2005               Disclaimer       Minor editorial change
1.3                1 September 2010            2, 6             Replaced reference to superseded NSW Standard BSS 02 with
                                                                applicable Australian Standard for tunnel fire safety
                                               © Australian Rail Track Corporation Limited 2010
                                                                 Disclaimer:
This document has been prepared by ARTC for internal use and may not be relied on by any other party without ARTC’s prior written consent. Use
                              of this document shall be subject to the terms of the relevant contract with ARTC.
ARTC and its employees shall have no liability to unauthorised users of the information for any loss, damage, cost or expense incurred or arising by
    reason of an unauthorised user using or relying upon the information in this document, whether caused by error, negligence, omission or
                                                        misrepresentation in this document.
                                               This document is uncontrolled when printed.
   Authorised users of this document should visit ARTC’s intranet or extranet (www.artc.com.au) to access the latest version of this document.
Engineering (Electrical) Standard
PDS 14 High Voltage Cable Selection Guide
                                                                                                                  Contents
Contents
          1     Scope and Application............................................................................. 3
          2     References.............................................................................................. 3
          3     Introduction ........................................................................................... 3
          4     Preferred cable Sizes and Applications ................................................... 4
          5     Continuous Ratings................................................................................. 5
                5.1    11 kV Cables .................................................................................... 5
                5.2    33kV Cables ..................................................................................... 6
          6     Cables for use in Tunnels and Underground Stations .............................. 7
          7     Conditions used in Determining Current Ratings .................................... 7
Version 1.3                             Date of last revision: 1 September 2010                                 Page 2 of 7
                    This document is uncontrolled when printed. See ARTC Intranet for latest version.
Engineering (Electrical) Standard
PDS 14 High Voltage Cable Selection Guide
                                                                                                    Scope and Application
1             Scope and Application
              This publication sets out continuous ratings of common high voltage ac cables used by the
              Australian Rail Track Corporation.
              This publication is a guide for the selection of cables and cable configurations to suit particular
              applications.
              This publication also defines the preferred cable sizes to be used in order to reduce and
              rationalise the number of different size cables in service.
              The requirements of this publication are to be met for the future selection of all high voltage
              cables.
2             References
              •   AS3008.1 Electrical installations - Selection of cables – Cables for alternating voltages up to
                  and including 0.6/1kV – Typical Australian installation conditions
              •   AS/NZS 1660. - Test methods for electric cables, cords and conductors
                  Method 5.2: Fire tests – Smoke density
                  Method 5.4: Fire tests – Determination of degree of acidity of gases evolved during the
                  combustion of materials taken from electric cables by measuring pH and conductivity
                  Method 5.6: Fire tests - Test for combustion propagation
              •    Applicable Australian Standard for tunnel fire safety
              •   BS EN 50268-1 Common test methods for cables under fire conditions - Measurement of
                  smoke density of cables burning under defined conditions.
              •   International Electrotechnical Commission Publication IEC 20A, 1978.
              •   Olex Cables - High Voltage XLPE Insulated Cables 08/82.
              •   CMA Power Cables - Paper Insulated, Lead and Aluminium Sheathed Cables up to 19/33kV
                  dated 12/2/87.
              •   EP 20 01 00 01 SP - 1500 Volt DC Cable Ratings. (RailCorp publication)
3             Introduction
              Cable manufacturers usually provide continuous current rating data for cables direct buried, in
              buried ducts and in air (in shade) conditions.
              ARTC cables are often exposed to direct sun and installed in elevated steel troughing which
              directly affects the current rating of the cable. This standard provides current rating data for the
              aforementioned conditions.
Version 1.3                               Date of last revision: 1 September 2010                             Page 3 of 7
                      This document is uncontrolled when printed. See ARTC Intranet for latest version.
Engineering (Electrical) Standard
PDS 14 High Voltage Cable Selection Guide
                                                                                   Preferred cable Sizes and Applications
4             Preferred cable Sizes and Applications
              The preferred 11kV and 33kV cable sizes to be used for future work are listed in Table 1. The
              rationalisation of the cables sizes minimises spare parts requirements.
                      TABLE 1 - PREFERRED CABLE SIZES, CABLE CONSTRUCTION AND APPLICATION
        VOLTAGE         AREA        INSULATION         CABLE CONSTRUCTION                            APPLICATION
                        35          XLPE               Single core, stranded compacted copper,       Short cable runs
                                                       XLPE insulated, natural, dry cure CCV/VCV,    between electrical
                                                       copper wire screen, PVC sheath, HDPE          equipment.
                                                       oversheath, metre mark.
                        95          XLPE               3 core, stranded compacted copper, XLPE       Feeder cable.
                                                       insulated, natural, dry cure CCV/VCV,
        6.35/11kV                                      individual copper wire screen, PVC sheath,
                                                       HDPE oversheath, metre mark.
                        150         XLPE               3 core, stranded compacted copper, XLPE       Feeder cable.
                                                       insulated, natural, dry cure CCV/VCV,
                                                       individual copper wire screen, PVC sheath,
                                                       HDPE oversheath, metre mark.
                        50          XLPE               Single core, stranded compacted copper,       AC switchgear to
                                                       XLPE Insulated, natural, dry cure             rectifier transformer.
                                                       CCV/VCV, copper wire screen, PVC sheath,
                                                       HDPE oversheath, metre mark.
                        150         XLPE               Single core, stranded compacted copper,       AC switchgear to
                                                       XLPE insulated, natural, dry cure CCV/VCV,    rectifier transformer.
                                                       copper wire screen, PVC sheath, HDPE
                                                       oversheath, metre mark.                       Feeder cable.
                        150         XLPE               3 core, stranded compacted copper, XLPE       Feeder cable.
                                                       insulated, natural, dry cure CCV/VCV,
                                                       individual copper wire screen, PVC sheath
                                                       HDPE oversheath, metre mark.
        19/33kV         185         Paper              Single core, stranded compacted copper,       Feeder cable.
                                                       paper insulated ,MIND,lead sheath, PVC
                                                       oversheath, metre mark.
                        185         Paper              3 core, stranded compacted copper, paper      Feeder cable.
                                                       insulated, MIND, HSL, steel wire armour,
                                                       PVC oversheath, metre mark.
                        240         XLPE               Single core, stranded compacted copper,       Feeder cable.
                                                       XLPE insulated, natural, dry cure CCV/VCV,
                                                       copper wire screen, PVCsheath, HDPE
                                                       oversheath, metre mark.
                        300         XLPE               Single core, stranded compacted copper,       Feeder cable.
                                                       XLPE insulated, natural, dry cure CCV/VCV,
                                                       copper wire screen, PVC sheath, HDPE
                                                       oversheath, metre mark.
Version 1.3                              Date of last revision: 1 September 2010                              Page 4 of 7
                     This document is uncontrolled when printed. See ARTC Intranet for latest version.
Engineering (Electrical) Standard
PDS 14 High Voltage Cable Selection Guide
                                                                                                            Continuous Ratings
5             Continuous Ratings
5.1           11 kV Cables
              11kV cables used on the ARTC system shall have minimum continuous current ratings as listed
              in Table 2. The preferred cables sizes for future use are unshaded for easy identification.
                               TABLE 2 - 11kv CABLES - CONTINUOUS CURRENT RATINGS IN AMPS
                                 Cores               Continuous Current Rating In Amps
        Insulation Type          Area      No.       Direct       In Buried     In Air in    In Air         In Elevated
                                 mm2                 Buried       Ducts         Shade        in Sun         Steel Troughing
                                                                                                            in Sun
                 XLPE              35         1         175           150           180          160                120
                 XLPE              35         3         165           145           160         150                 120
                 XLPE              50         1         205           175           215         180                 150
                 XLPE              50         3         195           170           190         175                 145
                 XLPE              95         1         290           250           320         250                 200
                 XLPE              95         3         270           240           275          230                200
                 XLPE              150        1         370           320           420         330                 260
                 XLPE              150        3         345           305           360          310                260
                 XLPE              240        1         475           410           560         420                 340
                 XLPE              240        3         440           385           480         390                 340
              Paper / Lead         25         3          90            80           75           75                  65
              Paper / Lead         50         1         170           155           160         155                 120
              Paper / Lead         50         3         160           140           140         140                 120
              Paper / Lead         95         1         250           255           245         250                 180
              Paper / Lead         95         3         240           205           210         210                 180
              Paper / Lead         150        1         325           285           325         290                 230
              Paper / Lead         150        3         305           255           280         265                 230
Version 1.3                                 Date of last revision: 1 September 2010                                Page 5 of 7
                        This document is uncontrolled when printed. See ARTC Intranet for latest version.
Engineering (Electrical) Standard
PDS 14 High Voltage Cable Selection Guide
                                                                                                         Continuous Ratings
5.2           33kV Cables
              33kV cables used on the ARTC system shall have minimum continuous current ratings as listed
              in Table 3. The preferred cables sizes for future use are unshaded for easy identification.
                               TABLE 3 - 33KV CABLES - CONTINUOUS CURRENT RATINGS IN
                            Cores                   Continuous Current Rating In Amps
    Insulation Type         Area          No.       Direct     In          In Air     In Air     In Elevated
                            mm2                     Buried     Buried      in         in Sun     Steel Troughing
    XLPE                         50          1        205         180        225        180                145
    XLPE                         50          3        190         170        195        170                145
    XLPE                         95          1        290         255        330        255                  -
    XLPE                         95          3        270         240        280        240                205
    XLPE                        150          1        370         325        430        350                275
    XLPE                        150          3        340         305        370        310                260
    XLPE                        240          1        475         415        570        440                355
    XLPE                        240          3        440         390        485        425                340
    XLPE                        300          1        530         460        650        500                400
    XLPE                        300          3        485         430        550        470                375
    XLPE                        400          1        590         520        740        590                445
    XLPE                        400          3        540         480        620        530                  -
    XLPE                        500          1        650         570        830        600                490
    HSL Paper / Lead          0.20 in.2      3        255         225        210        210                140
                                      2
    HSL Paper / Lead          0.25 in.       3        285         255        250        235                155
                                      2
    Gas / Paper / Lead        0.25 in.       3        310         280          -          -                  -
                                      2
    Gas / Paper /             0.25 in.       3        310         280          -          -                  -
    Aluminium
    Paper / Lead                 95          1        235         200        225        200                  -
    Paper / Lead                 95          3        225         195        200        195                  -
    Paper / Lead                150          1        305         250        295        260                155
    Paper / Lead                150          3        285         255        260        265                155
    Paper / Lead                185          1        345         280        340        290                175
    Paper / Lead                185          3        315         270        295        280                170
    Paper / Lead                240          1        395         320        400        350                  -
    Paper / Lead                240          3        365         325        350        340                  -
    Paper / Lead                300          1        445         355        455        400                235
    Paper / Lead                300          3        405         360        395        380                220
    Paper / Lead                400          1        510         395        530        450                  -
    Paper / Lead                500          1        560         435        600        500                300
Version 1.3                              Date of last revision: 1 September 2010                                 Page 6 of 7
                     This document is uncontrolled when printed. See ARTC Intranet for latest version.
Engineering (Electrical) Standard
PDS 14 High Voltage Cable Selection Guide
                                                                        Cables for use in Tunnels and Underground Stations
6             Cables for use in Tunnels and Underground
              Stations
              Cables for installation in tunnels or underground stations must have a low smoke, low toxicity,
              halogen free, flame retardant oversheath suitable for installation in damp situations. The
              oversheath shall comply with the current version of AS 1660 Part 5.2, 5.4, 5.6 and the
              applicable Australian Standard for tunnel fire safety.
              Smoke Emission
              When a sample of the complete cable is tested in accordance with BS EN 50268-1:2000, the
              values for the light transmittance shall not fall below 60% at any time during the test.
              Note:      “MEGALON” is unsuitable for prolonged immersion in water or water saturated soils.
7             Conditions used in Determining Current Ratings
              The conditions used in determining the continuous current ratings in the tables are:
              General
                  Max. allowable Core Temperature:               XLPE insulated cables 900C
                                                                 Paper Insulated cables 700 C
                  Buried Cables:                                 Soil Temperature (Ambient)          25°C
                                                                 Soil Thermal Resistivity 1.2 K.m/W
                                                                 Depth of Burial 800mm
                                                                Duct Diameter 150mm
                  Cables in Air:                                 Air Temperature (Ambient)           40°C
                                                                 Solar Radiation 1000W/m2
                                                                 Cable Emissivity           0.7
                                                                Steel Trough Emissivity 0.3
                                                                Trough Size        150mm x 150mm
Version 1.3                                 Date of last revision: 1 September 2010                            Page 7 of 7
                        This document is uncontrolled when printed. See ARTC Intranet for latest version.