Goedhart® air coolers

Goedhart® FeZn air coolers

AIR COOLERS FOR


COOLING & FREEZING
APPLICATIONS
Kelvion – 70 branches and More than 4,000
a ­tribute to sales partners ­employees
Lord Kelvin worldwide ­worldwide
Lord Kelvin (1824 – 1907) formulated
the laws of thermodynamics

EXPERTS IN
HEAT EXCHANGE -
SINCE 1920
Welcome to Kelvion. As successor to the GEA Heat Exchangers We are highly committed to earning your trust:
Group, we continue to break new ground, making discerning We want to win your trust with everything we do and convince
customers more successful than ever with our integrated heat you with the solutions we offer. With this high aim in mind, we
exchanger solutions. invest our extensive know-how, our great precision, and our
passion in everything we do: including product development,
Our solutions for your applications: manufacturing, installation, and after-sales support.
We offer our customers one of the world’s largest product
portfolios in the field of heat exchangers. It includes individual Seeing things from the customer perspective:
­solutions for practically all conceivable applications and com- Your specific requirements count – and nothing else. Whatever
plex environmental conditions: plate heat exchangers, shell and we offer you, it must meet these requirements. Our entire way
tube heat exchangers, finned tube heat exchangers, modular of thinking and working is geared towards this aim. Our custo-
cooling tower systems, and refrigeration heat exchangers. mers truly appreciate this: after all, this is how we make their
companies more efficient.
Your markets are our markets, too:
The markets in which you and we together operate are among We are at your service.
the most important in the world: energy, the oil and gas in- Kelvion – Experts in Heat Exchange.
dustry, the chemical industry, marine applications, food and
beverages, climate and environment. We provide every single
market segment with solutions of outstanding efficiency, safety,
and sustainability.
GOEDHART®
AIR COOLERS

4
Do not settle for compromise, but go for the best cooling Extensive theoretical and practical project analysis by
solution to suit your situation. That is the philosophy which our professional sales engineers will determine which
Kelvion makes himself hard. Since 1935 we develop, configuration, materials, and level of engineering best
produce and deliver worldwide air coolers, air cooled fit your program requirements. Additionally, you can use
condensers and composite systems for (semi) industrial the innovative ‘Goedhart Product Catalogue (GPC), the
applications and various markets. Our products are perfect digital design program for all commercial and customized
for projects requiring a technical demand and involving industrial air coolers and air-cooled condensers.
a great deal of flexibility in terms of design, dimensions
and accessories. Also our products are suitable for
all thinkable cooling system types and methods. For what level of engineering you choose; Your are with
Goedhart in good hands in the field of refrigeration
To achieve the most optimal and cost efficient air cooler and freezing. This brochure provides information
system we are using three levels of engineering: on FeZn series, a customized product.

• Commercial products: standard cooling Do you have any further questions, we are happy to
systems available in different fixed sizes; help you personally. We thank you in advance for the
• Customized products: custom made cooling interest you have shown in Kelvion and its products.
systems built from standard modules;
• Designed to order products: extensive
cooling systems and applications developed
especially for the niche market.

5
PRODUCT FAMILY
Goedhart® air coolers and condensers

COMMERCIAL PRODUCTS

Goedhart® FC38S Goedhart® FC38L Goedhart® FC38D Goedhart® PAC


Cu/Al
Freons, CO2, Coolants

CUSTOMIZED PRODUCTS

Goedhart® VCI Goedhart® VCe Goedhart® VNS Goedhart® DVS Goedhart® BC50
Cu/Al Goedhart® BC50XF
Freons, CO2, Coolants

Goedhart® VRB Goedhart® VRe Goedhart® VRS Goedhart® DRS Goedhart® BR50
StSt/Al Goedhart® VRZ Goedhart® BR50XF
StSt/StSt
NH3, CO2, Coolants

Goedhart® ZFB Goedhart® ZGB Goedhart® DZS


FeZn Goedhart® ZFZ Goedhart® ZGZ
NH3, CO2, Coolants

DESIGNED TO ORDER & OEM PRODUCTS

Goedhart® KB.v Goedhart® TN.s Goedhart® PLK.s Goedhart® AU.s


Goedhart® KB.h Goedhart® TN.p Goedhart® PLK.p Goedhart® AU.p

Cu/Al
StSt/Al
StSt/StSt Goedhart® LLK.s Goedhart® DL.v Goedhart® SLK Goedhart® DU.s
FeZn Goedhart® LLK.p Goedhart® DL.h Goedhart® DU.P

APPLICATION DRIVEN DESIGNS

Agricultural Fruit & vagetable Distribution centres Meat processing Penthouse


storages
Cu/Al
StSt/Al
StSt/StSt
FeZn Test facilities Marine sector Cooling & freezing
tunnels
Leisure High pressure (CO2)

CO2

AIR COOLED CONDENSERS & DRY COOLERS

Goedhart® KOAL-C Goedhart® KOAL-S Goedhart® KOAD-S


Cu/Al
Freons, CO2, Coolants

Goedhart® INAL-S
StSt/Al
NH3, CO2, Coolants

6
LIFE IS EASY
THE GOEDHART
SELECTION PROGRAM

The Goedhart selection program provides an electronic catalogue and exclude models which may not be relevant for your needs.
covering the majority of product ranges offered by Kelvion. The range of You can start a selection by clicking the Start button, fill in the
products available to you is very broad with many options. This software required heat exchanger data in the input area and produce PDF
provides the fastest and easiest way to select the most appropriate or Word files of your selection results. Also it is possible to print a
product for your specific needs. This selection program run on the latest drawing of the selected unit and make your choice belonging to
versions of Windows (including both 32-bit and 64-bit versions of Vista, your selected unit. The program normally operates using SI units.
Windows 7, Windows 8 and Windows 10).
What is important to you? - You can decide which features of the
All four product types (Coolers, Condensers and Glycol Coolers) are product are most important for each application: energy efficiency,
available in a single program. The Goedhart selection program is an footprint (physical size) and price. You adjust the slider controls
easy to use selection tool for contractors, consultants and every to indicate the relative importance to you of each of these three
other thinkable user and gives you access to many advantages such elements. You can also choose to display all possible models, or
as: just the ‘top 10’ which best meet your selection criteria. Once the
• Multilangual selected models are displayed, the ‘best’ options in each category
• Pre-select buttons to application (energy efficiency, footprint and price) will be on top of the table.
• Spare parts
• Selections including drawings Quality , Support and Website - Trained staff will advise you through every
• An extensive list of accessories step of the selection process. Our customer service continues passes the
• Accurate capacities: During your selection a product delivery, and we are always on hand to advise on any issues.
sophisticated capacity calculation program Keep up to date with our products and latest news
optimizes the circuits to the design conditions by visiting the website, www.kelvion.com
• Selections possible on several criteria such as capacity,
price, fan variations like noise and speed etc.

If you know the model number or the range you require (for example
Goedhart® VCI-p 63457), you can type this into the Start area of the
Goedhart selection program. This will make the selection faster
7
GOEDHART®
FEZN SERIES

STANDARD CUSTOMIZED INNOVATION


For all FeZn models and series of the Goedhart® air We can not emphasize often enough that we can meet our
coolers your schedule of requirements is leading. “customized production” philosophy to every customer
Depending on the application, our sales team searches requirements. Common customer requirements lead to
for the optimal configuration in close cooperation innovation of our products. A good example is the energy
with the customer. You have a free choice in: efficient Goedhart® VRe range in the stainless steel / aluminium
• dimensions version of our air coolers and air-cooled condensers
• Air direction
• blow-through or draw-through
• model: with feet of suspension profiles
• cooling system: natural (NH3 and C02)
and synthetic refrigerants
• materials: copper tubes/aluminium fins, Stainless
steel tubes/aluminium fin, Stainless steel tubes and
fins or steel tubes and fins / hot dipped galvanized
• accessories: eg defrost, coatings

LEVEL OF ENGINEERING -
‘CUSTOMIZED PRODUCTS’
The custom-made cooling systems built from standard
product components are so-called “Level 2 Flexible products”.
Within this level of engineering, you can choose from air
coolers consisting of copper tubes with aluminum fins (Cu
/ Al 50x50), stainless steel tubes with aluminum fins (St / Al
50x50), stainless steel tubes and fins (St/St / Al 50x50) and
hot dipped galvanized steel tubes and fins (FeZn 60x60).
8
AVAILABLE FEZN MODEL RANGES

Type Tube configuration Description Cooling system

Single blow-through / draw-


Goedhart® through air cooler for industrial NH3, CO2, dx and pump
60x60
ZFB / ZFZ cooling and freezing applications system, coolants
Ceiling mounted

Single blow-through / draw-


Goedhart® through air cooler for industrial NH3, CO2, dx and pump
60x60
ZGB / ZGZ cooling and freezing applications system, coolants
Ceiling & floor mounted

Dual discharge air cooler for


Goedhart® NH3, CO2, dx and pump
60x60 working room applications
DZS system, coolants
Ceiling & floor mounted (depends on size)

9
Goedhart® FeZn air coolers

BALANCED
AIR FLOW

FAN SYSTEM SPECIFICATIONS


Because of the flexible construction of the Goedhart® air Fan data
cooler, in principle it is possible to deliver with different fans. 1x230V-AC : till -25°C environment temperature
We selected a standard fan range of Ziehl Abegg (we reserve 3x400V-AC : till -40°C environment temperature
the right to alter the manufacturer) which fits perfectly on the (between -40°C en -50°C environment
Goedhart® flexible air coolers. The fans can be supplied in both temperature on request)
blow-through and draw-through executions. Against an extra 1x230V-EC : till -25°C environment temperature
price stainless steel guards and EC-fans are available. 3x400V-EC : till -35°C environment temperature

Fan execution Tension : 1x230V-50Hz (60Hz on request)


The fans meet the ErP2015 directive. The fans have very good : 3x400V-50Hz
aerodynamic features because of the special impeller geometry. : 3x400V or 3x460V-60Hz
This special impeller geometry gives the fan a low noise level Protection class : IP44 / IP54
and a high efficiency. Color : RAL9005 (black)
Speed controlling : 3 phase : 2 speeds by D-Y reconnection
: frequency controller with all-pole
sinus filter
: 1 phase : phase-control
: transformator
10
The motors are standard executed with a thermo contact and
must be connected to prevent motor damages. 1,30

correction factor
1,25

correctiefactor
The maximum allowable working data in the table and on the 1,20
name plate of the fans are to operate in an air temperature of 1,15
+20 °C (air density of ρ = 1,2 kg/m3). For air temperatures lower 1,10
then +20 °C, the current amperage can be calculated by using 1,05
the diagram multiplication factor, suitable thermal overloads can 1,00
then be selected. In our Goedhart GPC selection program also 0,95
the values in the working point are indicated. -40 -35 -30 -25 -20 -15
Frequentieregelaar -10 -5 0 5 10 15 20
luchttemperatuur / air temperature [°C]
Ventilator 2

Frequentieregelaar All-polig Ventilator 1


sinusfilter

SOUND DATA Frequency controller


The mean sound pressure (LpA @ 3m ± 2 dB (A)) each air Fan 2
cooler is a calculated indication value according to the EN13487
standard parallel pipe. Kelvion uses the fan manufacturer’s sound All-pole
Frequency controller Fan 1
power level (LwA) at the inlet side of the fan. Changes to or by sinus filter

the fan or the product, affect the sound, in these cases consult
the manufacturer for the new indication value. In critical sound Frequenzumrichter
requirements, we advise you to consult an expert. Ventilator 2

Frequenzumrichter All-polig U2
Ventilator 1
Sinusfilter

Convertisseur de fréquence
Ventilateur 2

Convertisseur de Filtre sinus Ventilateur 1


fréquence all-pole

DATA ON THE NAME PLATES


Regulador de la frecuencia
Ventilador 2
Three phase - 50Hz Three phase - 60Hz
D Y Regulador de la
frecuencia
D Y
Filtro de seno
all-pole
D Ventilador 1
LwA (+/-2dB(A))

LwA (+/-2dB(A))
level each fan

level each fan


Sound power
Fan diameter

Sound power
Regolatore di frequenza
Nominal

Nominal

Nominal
Tension

Speed

Speed

Speed
power

power

power

Ventilatore 2
FLC

FLC

FLC

mm V min-1 Watt A min-1 Watt Regulatore


A di dB(A) Filtro sinusoidale
dB(A) min-1 Watt A
Ventilatore 1 dB(A)
frequenza all-pole
4 pole (n=1500 min-1 nom.)
450 3x400/690 1350 540 1,10 1020 360 0,66 75 70 1560 880 1,40 79
500 3x400/690 1340 840 1,45 940 540 0,96 78 73 1480 1200 2,00 80
560 3x400/690 1290 1150 2,10 890 680 1,20 82 74 1430 1550 2,70 85
630 3x400/690 1360 1500 2,70 1100 1100 Taajuussäädin
1,80 86 83 1640 2900 4,60 92
Tuuletin 2
6 pole (n=1000 min-1 nom.)
450 3x400/690 900 180 0.50 630 100 0.24 66 59 1020 280 0,60 69
500 3x400/690 880 290 0.74 590 150 0.36
Taajuussäädin 68 57
Sinisuodatin 970 440 0,90 1
Tuuletin 71
560 3x400/690 870 340 0.70 630 210 0.38 73 66 980 540 0,88 76
630 3x400/690 900 620 1,25 720 440 0,72 74 69 1040 1000 1,55 76

Single phase - 50 Hz Single phase - 60 Hz


LwA (+/-2dB(A))

LwA (+/-2dB(A))
level each fan

level each fan


Sound power

Sound power
Fan diameter

Nominal

Nominal
Tension

Speed

Speed
power

power
FLC

FLC

mm V min-1 Watt A dB(A) min-1 Watt A dB(A)

4 pole (n=1500 min nom.)-1

450 1x230 1390 600 2,90 76 1430 820 3,50 75


500 1x230 1240 720 3,20 77 1260 1000 4,40 77
6 pole (n=1000 min-1 nom.)
500 1x230 900 270 1,25 74 900 380 1,75 75

Mentioned data are for each fan according the supplier of the fans

11
GOEDHART®
ZFB/ZFZ
AIR COOLERS
Cooling and Freezing

The range Goedhart® ZFB/ZFZ single discharge ceiling mounted Casing


are suitable for cooling and freezing applications. The fans are • Construction for ceiling mounting
arranged for blow-through air configuration and draw-through • Casing material of galvanized sheet steel (not painted)
(please state which is required when ordering). • Bend/header protection by end covers, easy removed for
maintenance
Coil block • Standard refrigerant connections are positioned on the left hand
Tube configuration : 60x60 mm straight side of the unit when looking with the direction of the airflow
Fin spacing : 6, 8, 10 and 12mm • Hinged drip tray prepared
Material : 22 mm o.d. steel tubes • Possible defrost by hot gas spiral or electric defrost
: Steel fins elements will be fixed to the bottom side of the coil
Treatment : Hot dipped galvanized • Stainless steel fasteners

The Goedhart® ZFB / ZFZ coil block is standard build from steel Goedhart® ZFB / ZFZ features
end plates, tubes and fins and will be hot dipped galvanzed • For cooling and freezing applications
totally. Standard refrigerant connections are positioned on the left • Steel tubes and fins, hot dipped galvanised
hand side of the unit when looking with the direction of the airflow. • Blow-through or draw-through execution possible
All coolers are pressure tested to 40 bar (lower by cooling • Consisting of 406 models
mediums) and are supplied with a light over pressure charge. • Capacity range from 3,1 to 87,0kW.(NH3 Pump system, SC2)
Suitable for NH3- pumpcirculation (ratio 2/4), CO2, HFK’s and • EC fan technology possible
coolants. • Fans not standard wired to a junction box (optional)
• Suitable for NH3 pump system, CO2, HFK’s and coolants
• Goedhart® ZFB / ZFZ delivered on a wooden frame for easy
mounting
• Optimized cooling circuits
• A wide variety of accessories and options available (page. 18)
12
1 Range : Goedhart® ZF

2 Air direction : B=blow Z=draw

1 2 3 3 Rows deep : 4 ,6, 8, 10

Goedhart® ZF B 6 3 45 7 4 Number of fans : 1 - 4

5 Fan diameter : 450, 560, 630 mm


4 5 6

6 Fin spacing : 6, 8, 10, 12 mm

GOEDHART® ZF-FAN DATA


D Y D Y D
LwA (+/-2dB(A))

LwA (+/-2dB(A))
Fan diameter

level each fan

level each fan


Sound power

Sound power
Nominal

Nominal

Nominal
Tension

Speed

Speed

Speed
power

power

power
FLC

FLC

FLC

mm V min-1 Watt A min-1 Watt A dB(A) dB(A) min-1 Watt A


THREE PHASE - 50HZ THREE PHASE - 60HZ
450 3x400/690 1350 540 1,10 1020 360 0,66 75 70 1560 880 1,40 79
500 3x400/690 1340 840 1,45 940 540 0,96 78 73 1480 1200 2,00 80
560 3x400/690 1290 1150 2,10 890 680 1,20 82 74 1430 1550 2,70 85
630 3x400/690 1360 1500 2,70 1100 1100 1,80 86 83 1640 2900 4,60 92
450 3x400/690 900 180 0.50 630 100 0.24 66 59 1020 280 0,60 69
500 3x400/690 880 290 0.74 590 150 0.36 68 57 970 440 0,90 71
560 3x400/690 870 340 0.70 630 210 0.38 73 66 980 540 0,88 76
630 3x400/690 900 620 1,25 720 440 0,72 74 69 1040 1000 1,55 76
SINGLE PHASE - 50HZ SINGLE PHASE - 60HZ
450 1x230 1390 600 2,90 80 76 1430 820 3,50 75
500 1x230 1240 720 3,20 81,5 77 1260 1000 4,40 77
500 1x230 900 270 1,25 71,5 74 900 380 1,75 75

Mentioned data are for each fan according the supplier of the fans

13
GOEDHART®
ZGB/ZGZ
AIR COOLERS
Cooling and Freezing

The range Goedhart® ZGB/ZGZ single discharge floor or ceiling Casing


mounted are suitable for cooling and freezing applications. The • Construction for ceiling and floor mounting
fans are arranged for blow-through air configuration and draw- • Casing material of galvanized sheet steel (not painted)
through (please state which is required when ordering). • Bend/header protection by end covers, easy removed for
maintenance
Coil block • Standard refrigerant connections are positioned on the left hand
Tube configuration : 60x60 mm straight side of the unit when looking with the direction of the airflow
Fin spacing : 6, 8, 10 and 12mm • Possible defrost by hot gas spiral or electric defrost
Material : 22 mm o.d. steel tubes elements will be fixed to the bottom side of the coil
: Steel fins • Stainless steel fasteners
Treatment : Hot dipped galvanized
Goedhart® ZGB / ZGZ features
The Goedhart® ZGB / ZGZ coil block is standard build from steel • For cooling and freezing applications
end plates, tubes and fins and will be hot dipped galvanzed • Executed with legs (for floor or ceiling mounting)
totally. Standard refrigerant connections are positioned on the left • Blow-through or draw-through execution possible
hand side of the unit when looking with the direction of the airflow. • Consisting of 552 models
All coolers are pressure tested to 40 bar (lower by cooling • Capacity range from 4,1 to 181,0kW. (NH3 pump system, SC2)
mediums) and are supplied with a light over pressure charge. • EC fan technology possible
Suitable for NH3- pumpcirculation (ratio 2/4), CO2, HFK’s and • Fans not standard wired to a junction box (optional)
coolants. • Suitable for NH3 pump system, CO2, HFK’s and coolants
• Separate inner and outer drip tray
• Optimized cooling circuits
• A wide variety of accessories and options available (page 18)
14
1 Range : Goedhart® ZG

2 Air direction : B=blow Z=draw

3 Rows deep : 4 ,6, 8, 10, 12


1 2 3

4 Number of fans : 1 - 6
Goedhart® ZG B 6 3 45 7
5 Fan diameter : 450, 560, 630 mm
4 5 6
6 Fin spacing : 6, 8, 10, 12 mm

GOEDHART® ZG-FAN DATA


D Y D Y D
LwA (+/-2dB(A))

LwA (+/-2dB(A))
Fan diameter

level each fan

level each fan


Sound power

Sound power
Nominal

Nominal

Nominal
Tension

Speed

Speed

Speed
power

power

power
FLC

FLC

FLC

mm V min-1 Watt A min-1 Watt A dB(A) dB(A) min-1 Watt A


THREE PHASE - 50HZ THREE PHASE - 60HZ
450 3x400/690 1350 540 1,10 1020 360 0,66 75 70 1560 880 1,40 79
500 3x400/690 1340 840 1,45 940 540 0,96 78 73 1480 1200 2,00 80
560 3x400/690 1290 1150 2,10 890 680 1,20 82 74 1430 1550 2,70 85
630 3x400/690 1360 1500 2,70 1100 1100 1,80 86 83 1640 2900 4,60 92
450 3x400/690 900 180 0.50 630 100 0.24 66 59 1020 280 0,60 69
500 3x400/690 880 290 0.74 590 150 0.36 68 57 970 440 0,90 71
560 3x400/690 870 340 0.70 630 210 0.38 73 66 980 540 0,88 76
630 3x400/690 900 620 1,25 720 440 0,72 74 69 1040 1000 1,55 76
SINGLE PHASE - 50HZ SINGLE PHASE - 60HZ
450 1x230 1390 600 2,90 80 76 1430 820 3,50 75
500 1x230 1240 720 3,20 81,5 77 1260 1000 4,40 77
500 1x230 900 270 1,25 71,5 74 900 380 1,75 75

Mentioned data are for each fan according the supplier of the fans

15
GOEDHART®
DZS
AIR COOLERS
Spread air diffusion
The range Goedhart® DZS dual discharge air coolers are Casing
especially suitable for cooling and working room applications. The casing will be delivered in 2 executions
The height of the aircooler is low, so the maximum space in the Goedhart® DZS I:
chill room can be utilised. The air direction is blow-through. only suitable for mounting to the ceiling. It is concerning the
smaller types of the DZS range. The limitation of this range is
Coil block chosen to ensure ease of handling during installation. Executed
Tube configuration : 60x60 mm straight with hinged drip trays.
Fin spacing : 6, 8, 10, 12 and 15mm
Material : 22 mm o.d. steel tubes Goedhart® DZS II:
: Steel fins is provided with feet and is suitable for both floor and ceiling
Treatment : Hot dipped galvanized mounting. It is concerning the bigger types of the DZS range.
The feet construction is specially designed to reduce
The Goedhart® DZS coil block is standard build from steel end transmission
plates, tubes and fins and will be hot dipped galvanzed totally. of cold to a minimum. Hinged drip trays are not possible.
Standard refrigerant connections are positioned on the left hand side
of the unit when looking with the direction of the airflow. • Casing material of galvanized sheet steel (not painted)
All coolers are pressure tested to 40 bar (lower by cooling • Bend/header protection by end covers, easy removed for
mediums) and are supplied with a light over pressure charge. maintenance
Suitable for NH3- pumpcirculation (ratio 2/4), CO2, HFK’s and • Possible defrost by hot gas spiral or electric defrost
coolants. elements will be fixed to the bottom side of the coil
• Stainless steel fasteners
The fans are mounted to the outside of the air cooler. The fans
are as standard not wired on a junction box to the connection Goedhart® DZS features
side. Wiring is available against an extra price. • For cooling and working room applications
• Low coil height
• Consisting of 294 models
• Capacity range from 2,2 to 159,0kW (NH3 pump system)
• EC fan technology possible
• Optimized cooling circuits
• A wide variety of accessories and options available (page 18)
16
1 Range : Goedhart® DZS

2 Rows deep : 4 ,6, 8, 10

1 2 3 3 Number of fans : 1 - 6

Goedhart® DZS 6 3 45 7 4 Fan diameter : 400, 450, 560, 630 mm

5 Fin spacing : 6, 8, 10, 12, 15 mm


4 5

GOEDHART® DZS-FAN DATA


D Y D Y D
LwA (+/-2dB(A))

LwA (+/-2dB(A))
Fan diameter

level each fan

level each fan


Sound power

Sound power
Nominal

Nominal

Nominal
Tension

Speed

Speed

Speed
power

power

power
FLC

FLC

FLC

mm V min-1 Watt A min-1 Watt A dB(A) dB(A) min-1 Watt A


THREE PHASE - 50HZ THREE PHASE - 60HZ
450 3x400/690 1350 540 1,10 1020 360 0,66 75 70 1560 880 1,40 79
500 3x400/690 1340 840 1,45 940 540 0,96 78 73 1480 1200 2,00 80
560 3x400/690 1290 1150 2,10 890 680 1,20 82 74 1430 1550 2,70 85
630 3x400/690 1360 1500 2,70 1100 1100 1,80 86 83 1640 2900 4,60 92
450 3x400/690 900 180 0.50 630 100 0.24 66 59 1020 280 0,60 69
500 3x400/690 880 290 0.74 590 150 0.36 68 57 970 440 0,90 71
560 3x400/690 870 340 0.70 630 210 0.38 73 66 980 540 0,88 76
630 3x400/690 900 620 1,25 720 440 0,72 74 69 1040 1000 1,55 76
SINGLE PHASE - 50HZ SINGLE PHASE - 60HZ
450 1x230 1390 600 2,90 80 76 1430 820 3,50 75
500 1x230 1240 720 3,20 81,5 77 1260 1000 4,40 77
500 1x230 900 270 1,25 71,5 74 900 380 1,75 75

Mentioned data are for each fan according the supplier of the fans

17
18
Accessories and options for Goedhart® air coolers

FLEXIBLE SOLUTIONS
FOR YOUR
APPLICATIONS
Accessoiries
Goedhart® Goedhart® Goedhart®
ZFB / ZFZ ZGB / ZGZ DZS
Blow-through X X X
Draw-through X X X
Hotgas defrost X X X
Water defrost X X X
Integrated secundair defrost circuit X X
Anti-condensation heating driptray X X X
Fan heating X X X
Hinged fans X X X
Hinged drip tray X X X
Insulated drip tray X X X
Insulated fan plate X
Polyester drip tray X X X
Plastic air throw streamer* X X
Sock connection* X X
Sock connection with air straightner* X X
Guide vane on fan* X X
Defrost sock * X X
Diffusor X X
Diffusor with air operated damper X X

Options
Electrical defrost X X X
Insulation disks X X X
Feet for floor mounting X X
Suction hoods over the fan X X
Suction hood fin side * X X
Fans 60Hz X X X
Fans EC X X X
Fans 1x230V X X
Coolants X X X
Pump system X X X
CO2 X X X
Other casing material X X X
Other fin spacings X X X
Fins Almg X X X
Fins Goldlack X X X
*=Only draw-through air coolers (Goedhart® ZFZ and Goedhart® ZGZ)

19
20
DEFROST SYSTEMS
For room temperatures where ice-build up can be expected
and where the coil can not be defrosted by the room air, an
defrost system is available. Water defrost
On top of the coil block a removable water defrost tray is
Heating section mounted. The height of the water defrost tray is 80 mm,
The air cooler can be carried out with a heating section with which increases the total height of the air cooler. The
electric heating elements to heat up again dehumidified air standard discharge head of the water in the water defrost
The heating section is compared to the air flow placed after tray is 25 mm, the maximum speed in the water supply line
the coil block. The heating elements can be placed with is 5m / sec. For an optimal functioning of the water defrost,
holders against the coil block or completely integrated in the the temperature of the defrost water must be between + 15
casing. ° C and at + 30 ° C. The water defrost tray is executed with
handles, easy for disassemble and cleaning.
Hot gas defrost
The coil block is as standard suited for hot gas defrost ( hot
gas supply through the suction header). Against an extra
price the drip tray can be provided with a copper hot gas
spiral. This is enclosed in aluminium profiles that are rigidly
secured to the under side of the aluminium inner drip tray.
As a result, a very good heat transfer is realized. As with
electric defrost a distinction is made with light defrost (room
temperature around 0 ° C) and heavy defrost.

FAN HEATING
The fan fan heating prevents ice build-up between
the fan impeller and fan bellmouth during the defrost
cycle. This prevent damaging of the fan. Connection box
Fan Heating

We advise to use fan heating as option on your air


cooler when the room temperature <-10 °C

Delivery
• Is mounted and connected to a junction box
• Can also be retrofitted

Execution other fan diameters


Fan Heating
Connection box

Power at
fan diameter
230V
mm kW
450 0,31
500 0,31
560 0,48
630 0,48

Execution 400 mm fan

21
DEFROST SOCKS
(Draw-through air coolers)
The defrost socks may be used at draw-
through air coolers and optimizes defrosting
in particular freezing applications.
In the cooling phase and activated fans, the defrost
sock is inflated. In the defrost phase, when the fans
are turned off, the defrost sock close the the fan hole
and supports the defrost process of the coil block.

Execution
Suitable for food industry, 100% polyester endless
fiber, washable at 40 ° C, suitable for temperatures
-60 to 110 ° C, very flexible, Fire resistance E
(EN13501-1: 2003), double stitched, tear resistant. Standard execution
100

Advantage
The defrost sock prevent draw in the air cooler during the
defrost process. The heat remains in the air cooler and
ensures that the defrosting time is considerably shortened.

inside
inside
Goedhart ZFZ / ZGZ
ØA

ØB
fan diameter Connection A B L
mm mm mm mm mm
450 500 515 380 760 80
500 550 565 425 835 100
560 650 665 480 925 L
630 637 650 540 1030

PREPARED FOR TEXTILE


HOSES
With textile/PVC air hoses, the air flow can be optimized
• Applications in work and production
• Sensitive refrigerated products (eg
flowers, cheese ripening)

Advantages
By using air hoses a very even distribution
of air at low air speed is possible.
• Lower absenteeism through draft-free workplaces
• Optimal climate for sensitive products
• No condensation, because of the breathable
fabric no dew point exceedance occurs.

Goedhart® ZFZ / ZGZ


fan diameter Connection
mm mm
450 500
500 550
560 637
630 637

Attention!!
When selecting the air cooler, you need to take pressure loss into account.

22
23
24
Tempera
0 5 10 15 min.
Tijdverloop van de ontdooiing

SUCTION HOOD

Temperatuur in de luchtkoeler
(Draw-through air coolers)
The suction hood is applied when used for freezing 0°C
applications from -18 ° C. It supports the alternate
Ontdooiverloop zonder ontdooisok en aanzuigkap *
defrost fot the air cooler in the freezing room. The
suction hood is carried out with 13 mm insulation.
• The suction hood is equal to the 0 10 20 30 40 min.
casing Material of the air cooler. Tijdverloop van de ontdooiing
• Suction hood is supplied separately
and is easy to assemble
Defrost progress with defrost sock and suction hood *
Advantages (in combination with a defrost sock) Defrost progress without defrost sock and suction hood *

Temperature in the air cooler


The defrost sock and suction hood prevent draw in
the air cooler during defrosting. The heat remains
on this way in the cooler and that means: 0°C

• Shorten the defrosting time by over 50%


• Significant energy savings
• No frost formation on the ceiling of the room and
to the products with minimum vapor formation 0
5
10
15
20 30 40 min.
Time progress of defrosting

NOTE:
Due to extra external pressure, the air volume and the capacity of the air cooler changes:

• When using a defrost sock the air volume is reduced with -10% and the capacity with -5%
• When using a defrost sock and suction hood the air volume is reduced with -20% and the capacity with -10%
• Per fan is 1 defrost sock is needed. Defrost socks are delivered assembled

PLASTIC AIR THROW


STREAMER
(Draw-through air coolers)
The Ziehl Abegg fan on a draw-through FeZn air
cooler can be executed with a plastic air throw
streamer for an improved air throw. Available on
fan diameters 450, 500, 560 and 630 mm.

Advantage
The air throw streamer gives a improved air throw
Also suitable on air coolers with stainless steel casing

25
Temperatuur in de luchtkoe
0°C

0 5 10 15 min.

SUCTION HOOD OVER THE


Tijdverloop van de ontdooiing

FANS
(Blow-through air coolers)

Temperatuur in de luchtkoeler
The suction hood over the fans is applied when used
for freezing applications from -18 ° C. It supports the
alternate defrost fot the air cooler in the freezing room. It 0°C

is possible to execute the suction with 13 mm insulation. Ontdooiverloop zonder ontdooisok en aanzuigkap *

• The material of the suction hood is equal


to the casing material of the air cooler.
• Suction hood is supplied separately 0 10 20 30 40 min.
Tijdverloop van de ontdooiing
and is easy to assemble

Advantages (in combination with a diffor with damper)


Ontdooiverloop met ontdooisok en aanzuigkap *
The diffusor with damper and suction hood prevent Ontdooiverloop zonder ontdooisok en aanzuigkap *

draw in the air cooler during defrosting. The heat

Temperatuur in de luchtkoeler
remains on this way in the cooler and that means:
• Shorten the defrosting time by over 50% 0°C

• Significant energy savings


• No frost formation on the ceiling of the room and
to the products with minimum vapor formation
5 15
0 10 20 30 40 min.
Tijdverloop van de ontdooiing

NOTE!
Due to extra external pressure, the air volume and the capacity of the air cooler changes:

• When using a diffusor with damper the air volume is reduced with -10% and the capacity with -5%
• When using a diffusor with damper and suction hood over the fans the air olume is reduced with -20% and the capacity with -10%

AIR DIFFUSOR WITH AIR


OPERATED DAMPER
(Blow-through air coolers)
The air diffusor with air opereted damper may be used
at blow-through air coolers and optimizes defrosting in
particular freezing applications. In the cooling phase and
activated fans, the air operated damper is blown open.
In the defrost phase, when the fans are turned off, the air
operated damper close the the fin side of the coil block
and supports the defrost process of the coil block.

Execution
The damper is air operated and has few mechanical
parts. The damper is delivered in open possition
to prevent damage during transport.

Advantage
The air diffusor with air operated damper prevent
draw in the air cooler during the defrost process.
The heat remains in the air cooler and ensures that
the defrosting time is considerably shortened. In
addition, the diffusor provides improved air throw.

26
27
LIFTING INSTRUCTIONS
Lifting instructions are supplied with every product. Lifting
and moving heat exchangers must be carried out by
skilled personnel. Safety must always be assured. Contact
www.kelvion.com www.kelvion.com

us if in doubt about any lifting or moving instruction.

These instructions must always be followed in order to


guarantee safety and to prevent any damage occurring to
our product.

Heat exchangers mounted on a wooden frame can be


unloaded by a forklift truck. When doing so, stacked heat
exchangers may only be lifted off one at a time. A crane
can also be used for unloading by positioning slings under
the wooden frame.

Heat exchangers with transport legs must be unloaded


using a crane with a balancer (see lifting instructions).

© Kelvion | All rights reserved. 02/2017

28
29
GLOBALLY
ACTIVE
AND STILL
CLOSE BY
No matter where your market is, regardless of country, we are
never far away. We are always happy to answer any questions you
may have and meet your requirements. Even the largest, most
successful project begins with an initial, profitable conversation.
We look forward to hearing from you.
30
Global production
footprint
Global sales
and service

Just scan this QR code with your smartphone or


visit our website at: www.kelvion.com – there
you will find a highly competent contact in your
immediate vicinity.

31
www.kelvion.com

You might also like