مشروع
مستشفى أطفال النصر لعالج األورام
          PUBLIC ADDRESS SYSTEM
             SPECIFICATIONS
مواصفات                                          توقيع المقاول
                                           اعمال التيار الخفيف 1
                                                                         مشروع
                                                          مستشفى أطفال النصر لعالج األورام
PART 1 - GENERAL
1.1      RELATED DOCUMENTS
A.       Drawings and general provisions of Contract, including General and Supplementary Conditions and
         Specification Sections, apply to this Section.
B.       Requirements of the following Division 16 Sections apply to this Section:
         1.  Basic Electrical Requirements.
1.2      SUMMARY
A.       This Section describes the Public Address System. The systems components as follow but are not
         limited to:
       1.       .Control console/microphone
       2.       AM/FM tuner
       3.       CD Player
       4.       Preamplifier .
       5.       Mixer Power amplifier
       6.       Central Rack and Cabinets
       7.       Wiring
       8.       Speakers.
       9.       Fire alarm interface and message recorder.
B.       Related Sections: The following Division 16 Section contains requirements that relate to this
         Section:
         1.     "Raceways", for raceways used for public address system cables.
         2.    "Electrical Boxes and Fittings", for boxes, cabinets, and fittings used with public address
               systems.
1.3      SYSTEM DESCRIPTION
A.       General: The Public Address System shall be a complete system for amplifying sound signals from
         input devices and distributing them to loudspeakers at various locations.
B.       System Performance Objectives: System is to be designed for Music Background and paging under
         normal conditions, Pre-Recorded messages via the digital announcer, CD player, Tuner are to be
         manually switched in, and are to have automatic priority over the AM/FM tuner. By using the
         microphone, operator is to have priority over audio or message cassette inputs within the system. In
         case of fire alarm the interface should be provided to over ride the system by a fire message coming
         from fire alarm system. Sound distribution to zones is to be controlled by zone selector controls.
     مواصفات                                                                                   توقيع المقاول
                                                                                         2 اعمال التيار الخفيف
                                                                           مشروع
                                                            مستشفى أطفال النصر لعالج األورام
C.       System Design Criteria: the performance criteria are to be achieved as summarised below:-
         -      Average sound pressure level: 85 dB with respective amplifiers set at 50% of maximum
                volume
         -      Uniformity coverage: within +/-5 dB
         -    Frequency response to be achieved in coverage area: 100 Hz – 15 kHz (+/-3 dB bandwidth).
1.4      SUBMITTALS
A.       General: Submit the following in accordance with Conditions of Contract and Division 1
         Specification Sections.
B.       Product data for each type of product specified.
C.       Shop drawings detailing Public Address System including, but not limited to the following:
         1.     Exact and final location of all equipment and apparatus
         2.     Block diagrams indicating the proposed interconnection of equipment.
         3.     Fabrication and assembly information
         4.     Rack arrangements.
         5.      Proposed mounting method for loudspeakers and other items of substantial weight.
D.       Wiring Diagrams detailing wiring for power, signal, and control differentiating clearly between
         manufacturer-installed wiring and field-installed wiring. Identify terminal numbers and wiring
         color codes to facilitate installation, operation, and maintenance.
E.       Maintenance data for materials and products, for inclusion in Operating and Maintenance Manual
         specified in Division 1 and Division 16 Section "Basic Electrical Requirements." Provide complete
         manual material concurrently with system submittal and provide updated final versions of manuals
         one month before completion of construction and final system turnover.
1.5      QUALITY ASSURANCE
A.       Installer Qualifications: Engage an experienced Installer who is a factory-authorized sales and
         service representative to perform the work of this Section. Refer to Division 1 Section "Definitions
         and Standards" for definition of experienced Installer. Upon request, submit evidence of such
         qualifications to the Engineer.
     مواصفات                                                                                    توقيع المقاول
                                                                                          3 اعمال التيار الخفيف
                                                                         مشروع
                                                          مستشفى أطفال النصر لعالج األورام
B.       Electrical Component Standard: Provide work complying with applicable requirements of NFPA 70
         "National Electrical Code."
C.       EIA Compliance: Comply with the following Electronics Industries Association Standards:
         1.    Public Address Systems
         2.    Loudspeaker, Dynamic Magnetic Structures, and Impedance
         3.    Racks, Panels, and Associated Equipment
         4.    Amplifiers for Public Address Equipment
         5.    Speakers for Public Address Equipment
         6.    Microphones for Public Address Equipment
1.6      DELIVERY, STORAGE, AND HANDLING
A.       Deliver products in factory containers. Store in clean, dry space in original containers. Protect
         products from fumes and construction traffic. Handle carefully to avoid damage.
PART 2 - PRODUCTS
2.1      MANUFACTURERS
A.       Available Manufacturers: Subject to compliance with requirements, manufacturers offering
         products that may be incorporated in the work include, but are not limited to the following:
B.       Manufacturers: Subject to compliance with requirements, provide products by one of the
         following:
               o   ITC                  (Italy)
               o FBT-Italy
               o BOUYER-France
               o Bosch
               o Or Approved Equal
2.2      SYSTEM REQUIREMENTS
A.       General: Provide complete and fully functional Public Address System using materials and
         equipment of types, sizes, ratings, and performances as indicated. Use materials and equipment
         that comply with referenced standards and manufacturers' standard design and construction in
         accordance with published product information. Coordinate the features of materials and
     مواصفات                                                                                    توقيع المقاول
                                                                                          4 اعمال التيار الخفيف
                                                                        مشروع
                                                         مستشفى أطفال النصر لعالج األورام
        equipment so they form an integrated system with components and interconnections matched for
        optimum performance of specified functions.
 B     Quality Products: High quality products, fully professional standard shall be provided for
this Contract.
C       Standard Products: The equipment provided shall be standard products of manufacturers
        regularly engaged in the manufacture of the products and shall essentially duplicate material and
        equipment that have been in satisfactory use for at least two years. In as far as possible, all
        components in the system shall be standard commercial design that comply with the
        requirements stated herein.
D       Standard Equipment Racks: Where multiple racks are required, such as amplification racks, these
        are to be configured as follows:-
        -      Identical layout of rack-mounting equipment, to ease documentation and maintenance.
        -      Use of identical equipment, such as standard amplifiers for example.
        -      Allow a minimum of 20% of unused space for future expansion, these being filled with
               blank panels.
        -      Meet the ventilation requirements specified elsewhere.
E       Adequate Ventilation: is to be provide for all equipment. At least one 1-3/4 in. perforated or
        louvered ventilation panel shall be mounted above and below each amplifier or between each
        amplifier when adjoining when adjoining one another vertically in a common equipment rack. In
        addition, ventilation panels shall be mounted at the top and bottom of the equipment rack to
        further facilitate connective cooling.
G       Physical Security: All equipment and components shall be firmly secured in place with all mounting
        supports.
H       Manufacturer's Installation Recommendations: Shall be adhered to unless explicitly in conflict with
        these specifications in which case the conflicts shall be brought to the attention of the Engineer for
        a decision.
J       Loudspeaker Cable Sizing: Submit drawings illustrating the proposed cable runs, the cable size
        utilized will provide no more than 0.5 dB insertion loss when used with the loudspeaker power
    مواصفات                                                                                    توقيع المقاول
                                                                                         5 اعمال التيار الخفيف
                                                                         مشروع
                                                          مستشفى أطفال النصر لعالج األورام
        distribution supplied: (calculated as a function of the DC-loop resistance of the cable and the
        nominal impedance of the loudspeaker load, transferred to the primary), a minimum size of
        0.9 mm diameter will be used in any case, to be increased as necessary in case of lengths being
        extended beyond what is expected.
K       Loudspeaker Distribution Circuits: Conductors, Loudspeaker circuits are to be untinned stranded
        copper. Each conductor is to BCE individually insulated and each cable shall be provided with an
        overall jacket. Each cable is to meet the Code requirement for the voltage level applied.
L       Cables providing common functions are to be color-coded identically and each cable shall be
        clearly, permanently, and logically marked at both ends with an appropriate cable designation.
        Labeling methods must be approved by the Engineer.
M       Termination is to be made with self-insulating mechanical connectors. All termination techniques
        must be approved by the Engineer.
N       Signal Earthing: The equipment cabinets will be earthed to a true earth providing less than 0.1
        ohm resistance between it and the system's electrical earth.
O       Interference Protection: All equipment shall be installed so as to prevent electromagnetic, electro-
        acoustic or other outside interference from causing anomalous system performance.
P       Nameplates inscribed in English are to be firmly affixed to each major equipment item. Each
        nameplate is to include the manufacturer's name, address, model or catalogue number, and a
        definition of the equipment type ("amplifier", equalizer", etc.). The Nameplates are to be labeled
        by means of silk-screening, engraving, or by "metal-photo" process.
Q       Fixed Equipment are to have all controls, indicators an cable termination points, clearly, logically
        and permanently labeled by silk-screening, engraving or other methods specified herein.
R       Portable Equipment: are to be marked with durable plastic tags to identify its function and the
        system or subsystem with which it is associated. This equipment shall be delivered when the
        installed system has been tested and accepted.
S       Alignment: All equipment is to be mounted square and plumb and in alignment with other building
        fixtures. Conflicts with other building elements must be addressed to the Engineer who will
        approve the resolution.
    مواصفات                                                                                     توقيع المقاول
                                                                                          6 اعمال التيار الخفيف
                                                                            مشروع
                                                             مستشفى أطفال النصر لعالج األورام
T         Touch-up Paint: From the manufacturers of the equipment is to be supplied and applied in the
          event that the equipment becomes marred during shipping, handling and/or installation and until
          the installation is accepted by the Engineer.
    2.3    PRODUCTS AND SYSTEMS
           OPERATION, DESIGN AND COMPONENTS
           OPERATION AND DESIGN
          SYSTEM DESCRIPTION: system is to provide a means of distributing multi-program sound, public
          announcements and paging/emergency calls.
          Sound is to be originated from three sources:
-                Radio tuner AM/FM
-                CD players
-         paging desks with zones as specified in BOQ .
          Three levels of priority are to be provided. A signal origination from a source of higher priority is to
          be silence all lower priority sources completely and transmit its signals. The order of priority,
          highest priority, first, is as follows:
          DESIGN PARAMETERS: system is to be designed for public address with uniform and acceptable
          level of speech intelligibility. Design shown on the Drawings is based on selected manufacturer's
          models which are to be checked for performance before implementation. Alternative system
          design is to be submitted to the Engineer for approval, with specification, characteristics, aiming
          and mounting positions of loudspeakers and full particulars of calculations and equipment
          selections. System design in public areas is to be based on the following criteria:
Average sound d pressure level:
Background sound. 75-85 (with local volume control)
Public address calls 85 dB
Emergency calls        85 dB
Uniformity coverage: within +/-3 dB
Frequency response to be achieved in coverage area 10 Hz -18 KHz + (+/- 3 dB bandwidth).
 MIXER, LINE DISTRIBUTION AND COMPRESSOR                             PREAMPLIFIERS
INPUT MIXER PREAMPLIFIER: completely integrated modules, 19-inch rack mounted, suitable for line level
        audio inputs. Printed boards (PCBs) are to allow different inputs e.g. balanced/unbalanced, in/out
        etc. Each module is to have sliding pre-
    مواصفات                                                                                        توقيع المقاول
                                                                                             7 اعمال التيار الخفيف
                                                                       مشروع
                                                        مستشفى أطفال النصر لعالج األورام
set logarithmic potentiometer, treble and bass tone control, VU meter and programmed priority operation
        between the inputs, using plugged in programmable priority board.
INPUT MIXER PREAMPLIFIER PERFORMANCE is to be at least as follows:
        Effective frequency
        Range (+/-3 dB)       :      50-20000 Hz
        Signal/noise ratio,
        All controls down
        (50-18000 Hz flat)    :      65dB
        Total harmonic distortion
        (Nominal loudspeaker
        Power, at 1000 Hz) :         less than 0. 1%
        Output level
        (Load impedance)      :      0 dB m/0.775 V (100 ohm)
        Input sensitivity     :
        Microphone            (1kohm)/1 mV (adjustable)
        Outputs         :                    2 lines, 600 ohm
        Power supply voltage :                        220 V, 50 Hz
        Ambient temperature          :                       40 deg. C.
         PAGING DESK
TYPE: paging desk is to be a desk-top microphone to provide all-call and individual zone paging for
       different zones as mentioned in BOQ.
         PAGING DESK: desk-top type, with stainless steel panel or finished compatible with the
         reception desk finishes, gooseneck microphone with built-in compression preamplifier, electro-
         chime unit, ten zone fluorescent-illuminated call push buttons, one all-call push button, one push
         button for chime and microphone control and master call (emergency on) busy indicator lamp.
         PRIORITY PROGRAMMING: programmable functions cascade priority as described before
         are to be provided for operation with other remote paging microphones.
         PUSH BUTTONS: locking, fluorescent illuminating type, with provision for inserting the label.
         CHIME UNIT is to give double audio signal, tone, different than other signaling tones in the
         building, upon pressing lock-down button. Upon completion of this signal, microphone is to be
         automatically switched in. Upon completion of public address/page, lock-down button is to be
         manually released and system is to automatically fade into normal input (background sound
         source).
         GOOSENECK MICROPHONE: dynamic cardioids type, having uniform frequency response
         from 60 Hz to 12000 Hz (+/-3 dB). Microphone is to be fully dust and moisture protected,
         designed specifically for speech reproduction and with at least the following performance:
         Nominal impedance 200 ohms
  مواصفات                                                                                    توقيع المقاول
                                                                                       8 اعمال التيار الخفيف
                                                                    مشروع
                                                     مستشفى أطفال النصر لعالج األورام
      Sensitivity (at 1000 Hz)     1.75 mV/Pa
      Output level 0 dB/600 ohm (balanced)
      S/N ratio not less than 60 dB
    Frequency response 100HZ to 20KHZ
      Ambient temperature ranges           0 to 45 deg. C.
CENTRAL RACKS AND CABINETS
      CENTRAL RACKS are to contain sound sources, input mixer modules, distribution
      preamplifiers, zone selector relay modules, power supply module, power amplifiers and output
      terminal panel. Racks are to be 19-inch standard frame racks. Equipment is to be mounted and
      designed for 19-inch rack mounting.
      CABINETS are to be 19-inch frame, with all panel mounting holes and spacing of racks are in
      conformity with EIA, totally enclosed, with side and rear panels removable, and cable entrance at
      rear, top or bottom. Surface finish is to be textured and of approved color. Frames are to be
      anodized aluminum sections. Each frame is to be provided with ventilation rack, including
      automatically operated fan with thermostatic control. Suitable ventilation openings are to be
      provided. Enclosure is to be IP 42 to IEC 144 for indoor installation.
      STORAGE: rack cabinets are to have storage drawers for cables and accessories.
      MAINS WIRING: equipment is to operate from 220 V, 50 Hz mains and is to be capable of
      continuous operation under any load conditions with variations of +/- 10% of nominal voltage.
      Mains wiring inside cabinet racks is to be totally segregated from low level signal wiring.
      ELECTRIC CONNECTIONS, other than those for low-level signals, are to be by push-on
      spade clips or multi-connector blocks.
      LOW-LEVEL SIGNAL WIRING: heavily braided, PE insulated screened cable, PVC sheathed with
      standard DIN plug connections. Amplifier output lines to be run within the cabinet racks are to
      be twisted pairs heavily screened with tinned copper braid. Hum-producing earth return loops
      are to be avoided.
      POWER SUPPLY: complete power supply unit is to be provided, independently fused on the
      live conductor, with mains front indicator light, on/off switch, cartridge-type fuse and fuse-
      holder with blown fuse indicator lamp.
      MONITOR PANEL: is to monitor sound signals at line-level or loudspeaker level as shown on
      schematic diagram. Unit is to contain position input-selector switch, volume control with on/off
      switch, VU meter and pilot lamp. Amplifier section is to have isolation transformer, power
      amplified with solid-state integrated circuits, and regulated power supply. Amplifier is to be
      capable of operation from 220V, 50 Hz a.c. line. Monitor speaker is to be compact type,
      mountable on monitor unit panel, with 10 watt power rating, uniform frequency response (60-
      15,00OHz) and is to provide, with one watt input, an 80 dB SPL at one meter.
      COMPRESSOR AMPLIFIER: transistorized, compressor-limiter amplifier, provide audio
      volume compression with adjustable controls and power "on" indicator lamp. The amplifier is to
      be fabricated on a printed circuit board for compactness. A screwdriver adjustable output level
      control is to be provided to vary to the output voltage. A combination variable compression
 مواصفات                                                                                  توقيع المقاول
                                                                                    9 اعمال التيار الخفيف
                                                                      مشروع
                                                       مستشفى أطفال النصر لعالج األورام
        control with power "on-off" switch is to be provided to vary the degree of compression. A VU
        meter is to be provided for compression level and output level monitoring. A screwdriver
        adjustable zero control is to be provided for
        Adjusting the VU meter to zero when meter switch is in compression position. The amplifier gain
        is to be 20 dB with a frequency response of + 1 1/2 dB between 50 and 16,000 Hz. The output of
        the compressor-limiter amplifier is to be 1.2 volts. The harmonic distortion is to be less than 2%
        at 30 dB of compression at 50 to 16,000 Hz. The hum and noise level shall be 70 dB of maximum
        compression with an attack time of then (10) milliseconds and an adjustable recovery time
        between I and 2 seconds. The amplifier is to provide an input impedance of 4,00 ohms nominal
        and an output impedance of 600 ohms nominal.
        TONE GENERATORS: solid state electronic oscillators which are to emit signals to the
        loudspeakers unlike and distinct from those produced by the fire alarm system horns. The tone
        generators are to be controlled by an interface unit which receive any of six signals (related to
        the area initiating the alert) from the medical team emergency call stations and transmit ten
        rounds of coded signal (also related to the area initiating the alert). Coded signals are to be
        groups of long and short bursts. Groups are to be recommended by the manufacturer and
        approved by the Engineer.
        POWER AMPLIFIER
        GENERAL: power amplifier is to be 19-inch rack mountable suitably designed for music
        distribution as well as public address announcement. Amplifiers are to be driven by line
        distribution amplifiers providing reliable parallel line-level audio feed such that malfunction of
        any single amplifier results only in one failure.
        INPUT LEVEL: to be adjustable with a preset potentiometer on front panel. Illuminated VU
        meter is to be mounted on front panel.
        OUTPUT: to be fully protected against failure due to mismatch, short circuits, thermal and
        electrical overloads, overdrive or eventual transients.
        PERFORMANCE: each power amplifier is to have at least the following performance:
        Effective frequency range 20 Hz to 20000 Hz
        Input: 0dBm line level        (0.775 V)
        Input impedance 100 k.ohm
        Output voltage
(Load impedance)      100 V (100 ohm)
               70 V (50 ohm)
               50 V (25 ohm)
        Signal/noise ratio
        (All controls closed) 90 dB
        Total harmonic distortion
        at 1000 Hz less than 1.0%
        Power supply          220V, 50 Hz.
 مواصفات                                                                                    توقيع المقاول
                                                                                     10 اعمال التيار الخفيف
                                                                  مشروع
                                                   مستشفى أطفال النصر لعالج األورام
     ADEQUATE VENTILATION is to be provided for power amplifiers. At least 44 mm
     perforated or louvered ventilation panel is to be mounted above and below each amplifier or
     between each amplifier when adjoining one another vertically in a common equipment rack. In
     addition, ventilation panels are to be mounted at the top and bottom of each equipment rack to
     further facilitate connective cooling.
     TAPE RECORDERS AND CD PLAYERS
     TAPE RECORDER TYPE: two units, rack mounted, high quality, auto-reverse/auto-stop, 4-
     track, mono/stereo type with speed tolerance of 10%, complying with IEC 94 or other approved
     standard and accepting standard cassettes through front panel selector switch.
     RECORDER HEADS AND MOTORS: recorder is to have separate heads for play, record and
     erase functions, three motors (two for fast winding in two directions and third for
     record/playback at two speeds), and noise reduction system.
     CONTROLS: recorder is to have fast wind and re-wind, playback, record and stop controls, two
     illuminated peak level indicators, pause control, resettable digital counter, level controls for
     recording and play-back, on-off switch, microphone/headphone sockets and radio sockets and
     radio and line inputs.
     PROTECTION is to be provided against input overloads to reproduce strong signals without
     distortion.
     EDIT/CUE FACILITY is to be provided to permit listening to tape during fast forward or
     backward winding and to identify particular parts of tape for editing.
     CHARACTERISTICS: minimum requirements are to be as follows:
     Signal/tape noise
     ratio at highest speed         65 dB
     crosstalk attenuation
     at 100 Hz better than 50 dB in stereo
                    better than 65 dB in mono
     distortion (max.)      from recording amplifier: 0.2%
                    at 1.5 V
                    from magnetic tape at 0 dB
                    recording level: 3%.
     inputs:
     ratio        input impedance 50 k-ohms,
                  sensitivity 8 mV to 1.2 V.
     line         input impedance 200 k-ohms,
                  Sensitivity 30 mV to 5 V.
     CD PLAYER TYPE: two units, rack mounted, high quality, with 5 disc changer capability each,
     capable of operating continuously.
     CD PLAYER PROGRAMMING: it should be possible to program the CD player to select from
     any CD at any order for continuous play.
مواصفات                                                                                توقيع المقاول
                                                                                11 اعمال التيار الخفيف
                                                                   مشروع
                                                    مستشفى أطفال النصر لعالج األورام
     LOUDSPEAKERS
     CEILING LOUDSPEAKERS: (to be suitable for false ceiling mounting) is to comprise a 100 V
     line matching transformer, high quality loudspeaker, metal front grille and mounting plate with
     locking clamps.
     The transformer is to deliver within +/- 1 dB of its full rated power over the frequency range 100
     Hz to 20 KHz with a maximum insertion loss not greater than 1.5 dB for the most unfavorable
     impedance combination. The primary tape is to be identified with 6-, and 1.5- watts of audio
     power and the secondary with 8 ohms. The loudspeaker is to have a nominal diameter of 175-
     180 mm and is to meet the specifications mentioned in BOQ.
     LOUDSPEAKER VOLUME CONTROL: local channel selector volume control with ON/OFF
     is to be provided in each state private office as shown on Drawings. The device is to flush
     mounted, complete with back box, emergency override relay and is to have the following
     performance characteristics:
     Power handling capacity 10,36,100 watt
     Nominal input voltage         100
     Number of volume control steps 10 x 2 dB
     Channel selector     4 channels.
     Pendant loudspeaker
      2.5” loudspeaker with transformer with the following characteristics:
           Mounting system : U bracket
           MAX power : (20)Watt
           Frequency response : 65 ~20.000 HZ
           Impedance : 8 OHM and 70 v
           Sensitivity 1W/1M : 90 dB
           Maximum SPL 1m : 90 dB
           Distribution pattern 87°V /164°H
           70-100 volt transformer
            PUBLIC ADDRESS SYSTEM CABLING
     CONDUITS AND RACEWAYS: to comply of the Specification.
     DC-CONTROL, MICROPHONE AND LINE-LEVEL CABLES: PE insulated, finely stranded tinned
     copper conductor, minimum of 1 mm diameter and PVC over-sheath. Microphone and line-level
     cables are to be shielded with copper braid to provide 100% shielding throughout the cable
     length. A cable shields will be insulated from the electrical conduit throughout their length.
     LOUDSPEAKER DISTRIBUTION CIRCUITS: PE insulated, stranded tinned copper
     conductors, with an overall PVC jacket. Cables are to meet the NEC code requirements for the
     voltage level applied.
     LOUDSPEAKER CABLE SIZING: submit drawings illustrating the proposed cable runs, the
     cable size proposed, and calculations demonstrating that the cable utilized will provide no more
     than 0.5 dB insertion loss when used with the loudspeaker power distribution supplied:
     (calculated as a function of the DC-loop resistance of the cable and the nominal impedance of
مواصفات                                                                                  توقيع المقاول
                                                                                  12 اعمال التيار الخفيف
                                                                         مشروع
                                                          مستشفى أطفال النصر لعالج األورام
         the loudspeaker load, transferred to the primary), a minimum size of 2.5 sq.mm. Will be used in
         any case, to be increased as necessary in case of lengths being extended beyond what is
         expected.
FIELD AND INSTALLATION WORK
         INSTALLATION
         GENERALLY: installation is to be in accordance with the applicable requirements described of
         the Specification.
         TESTING
         TESTS ON SITE: measure quality of sound distribution, sound pressure levels, dispersion
         angles and directivity over specified frequency range and carry out any other tests to prove
         system performance in accordance with the Specification.
         TEST AND MEASUREMENT EQUIPMENT: provide all test and measurement equipment
         for setting up the systems, adjusting gains, volumes and levels.
PART 3 - EXECUTION
3.1      EXAMINATION
A.       Examine conditions, with the Installer present, for compliance with requirements and other
         conditions affecting the performance of Public Address system work.
B.       Do not proceed until unsatisfactory conditions have been corrected.
3.2      INSTALLATION
A.       General: Install system in accordance with NFPA 70 and other applicable codes. Install equipment
         in accordance with manufacturer's written instructions.
B.       Wiring Methods: Install wiring in raceway except within consoles, desks, and counters. Conceal
         wiring.
C.       Impedance and Level Matching: Carefully match input and output impedances and signal levels at
         signal interfaces. Provide matching networks where required.
D.       Control Circuit Wiring: Install control circuits in accordance with NFPA 70 and as indicated. Provide
         number of conductors as recommended by system manufacturer to provide control functions
         indicated or specified.
E.       Install exposed cables parallel and perpendicular to surfaces or exposed structural members, and
         follow surface contours. Secure and support cables by straps, staples, or similar fittings so
         designed and installed as not to damage the cables. Secure cable at intervals not exceeding 75 cm
         and not more than 15 cm from every cabinet, box, or fitting.
F.       Wiring Within Enclosures: Provide adequate length of conductors. Bundle, lace, and train the
         conductors to terminal points with no excess. Provide and use lacing bars.
     مواصفات                                                                                   توقيع المقاول
                                                                                        13 اعمال التيار الخفيف
                                                                           مشروع
                                                            مستشفى أطفال النصر لعالج األورام
G.       Provide physical isolation from each other for line level, speaker, and power wiring. Run in
         separate raceways or provide 30 cm minimum separation where exposed or in same enclosure.
         Provide additional physical separation as recommended by equipment manufacturer.
H.       Splices, Taps, and Terminations: Make splices, taps, and terminations on numbered terminal strips
         in junction, pull, and outlet boxes, terminal cabinets, and equipment enclosures.
I.       Identification of Conductors and Cables: Use color coding of conductors and apply wire and cable
         marking tape to designate wires and cables so all media are identified in coordination with system
         wiring diagrams.
J.       Weatherproofing: Weatherproof units to be mounted out-of-doors or exposed to weather in any
         degree.
K.       Repairs: Wherever walls, ceilings, floors, or other building finishes are cut for installation , repair,
         restore, and refinish to original appearance.
3.3      EARTHING
A.       Provide equipment earthing connections for Public Address System as required or indicated.
         Tighten connections to comply with tightening torques specified in UL Standard 486A to assure
         permanent and effective earthing.
    A. Earthing equipment, conductor, and cable shields to eliminate shock hazard and to minimize to the
       greatest extent possible, earth loops, common mode returns, noise pickup, cross talk, and other
       impairments. Provide 5-ohm earth at main equipment location. Measure, record, and report
       earthing resistance.
3.4    FIELD QUALITY CONTROL
A.     Manufacturer's Field Services: Provide services of a factory- authorized service representative to
       supervise the field assembly and connection of components and the presetting, testing, and
       adjustment of the system.
B.     Presetting: Upon completing installation of the system, align, adjust, and balance the system and
       perform complete presetting. Determine, through presetting, the conformance of the system to
       the requirements of the Drawings and Specifications. Correct deficiencies observed in presetting.
       Replace malfunctioning or damaged items with new, and retest until materials satisfactory
       performance and conditions are achieved.
C.       Testing: Upon completion of presetting, notify the Engineer a minimum of 10 days in advance of
         acceptance test performance. Schedule and conduct tests in his presence. Provide a written
         record of tests results.
D.       Operational Test: Perform an operational system test to verify conformance of system to these
         Specifications. Perform tests that include originating program and page material at microphone
     مواصفات                                                                                      توقيع المقاول
                                                                                           14 اعمال التيار الخفيف
                                                                          مشروع
                                                           مستشفى أطفال النصر لعالج األورام
         outlets, all preamplifier program inputs, and all other inputs. Observe sound reproduction for
         proper volume levels and freedom from noise.
E.       Signal-To-Noise Ratio Test: Measure the ratio of signal to noise of the complete system at normal
         gain settings using the following procedure:
         1.      Disconnect a microphone at the connector or jack closest to it and replace it in the circuit
                 with a signal generator using a 1,000-Hz signal. Replace all other microphones at the
                 corresponding connectors with dummy loads, each equal in impedance to the microphone
                 it replaces. Measure the ratio of signal to noise.
         2.      Repeat the test for each separately controlled zone of loudspeakers.
         3.      The minimum acceptance ratio is 50 dB.
F.       Distortion Test: Measure distortion at normal gain settings and rated power. Feed signals at
         frequencies of 50, 200, 400, 1,000, 3,000, 8,000, and 12,000, Hz into each pre-amp channel and
         measure the distortion in the power amplifier output. The maximum distortion at any frequency is
         3 percent total harmonics.
G.       Acoustic Coverage Test: Feed pink noise into the system using octaves centered at 4,000 and 500
         Hz. Use a sound level meter with octave band filters to measure the level at five locations in each
         zone. For spaces with seated audiences, the maximum permissible variation in level is plus or
         minus 2 dB and the levels between locations in the same zone and between locations in adjacent
         zones must not vary more than plus or minus 3 dB.
H.       Power Output Test: Measure the electrical power output of each power amplifier at normal gain
         setting at 50, 1,000, and 12,000 Hz. The maximum variation in power output at these frequencies
         must not exceed plus or minus 1 dB.
I.       Inspection: Make observations to verify that units and controls are properly labeled, and
         interconnecting wires and terminals are identified. Provide a list of final tap settings of speaker line
         matching transformers.
J.       Retesting: Rectify deficiencies indicated by tests and completely retest work affected by such
         deficiencies at Contractor's expense. Verify by the system test that the total system meets the
         Specifications and complies with applicable standards. Provide a written record of all retest results.
3.5      COMMISSIONING
A.       Train Owner's maintenance personnel in the procedures and schedules involved in operating,
         troubleshooting, servicing, and preventative maintenance of the system. Provide a minimum of
         three hours training.
B.       Schedule training with Owner through the Engineer, with at least 7 days advance notice.
C.       Occupancy Adjustments: When requested by the Engineer within one year of date of Substantial
         Completion, provide on-site assistance in adjusting sound levels, resetting matching transformer
     مواصفات                                                                                     توقيع المقاول
                                                                                          15 اعمال التيار الخفيف
                                                                       مشروع
                                                        مستشفى أطفال النصر لعالج األورام
      taps, and adjusting controls to suit actual occupied conditions. Provide up to three visits to the site
      for this purpose.
3.6   CLEANING AND PROTECTION
A.    Prior to final acceptance, clean system components and protect from damage and deterioration.
 مواصفات                                                                                      توقيع المقاول
                                                                                       16 اعمال التيار الخفيف