model CD-85, CD-86
industrial control damper
                                                                                                                                                                                   triple-V blade
                                             Application                                                                  Ratings
                                               CD-85 and CD-86 control dampers employ a rugged channel
                                               frame and triple-V blades for automatic air control and manual               Damper                     Maximum System                  Maximum System
                                               balancing in medium to high pressure and velocity applications.               Width                    Pressure with seals            Pressure without seals
                                             Standard Construction
                                                                                                                           32" (813)                   15.0 in. wg (3.8 kPa)            20.0 in. wg (5.0 kPa)
                                                                                                                           42" (1067)                  15.0 in. wg (3.8 kPa)            15.0 in. wg (3.8 kPa)
                                               Frame: 8" ¥ 2" ¥ 12 ga. (203 ¥ 51 ¥ 2.8) galvanized steel channel.          60" (1219)                   7.0 in. wg (1.8 kPa)             7.0 in. wg (1.8 kPa)
                                               Blades: 73/4" ¥ 12 gauge (197 ¥ 2.8) galvanized steel — triple-
                                                  V. Parallel (model CD-85) or opposed (model CD-86) action.
                                                                                                                          Max. Damper                  Maximum Damper                    Maximum System
                                               Axles: 1" (25) diameter plated steel.                                         Width                          Height                           Velocity
                                               Linkage: Concealed in frame.                                                60" (1524)                       68"   (1727)                 6000   fpm   (30.5   m/s)
                                                                                                                           44" (1118)                       96"   (2438)                 6000   fpm   (30.5   m/s)
                                               Bearings: Stainless steel sleeve-type, pivot in bushing, press fit          60" (1524)                       80"   (2032)                 5000   fpm   (25.4   m/s)
                                                 into frame.
                                                                                                                           50" (1270)                       96"   (2438)                 5000   fpm   (25.4   m/s)
                                               Control Shaft: 1" ¥ 6" (25 ¥ 152) round drive axle with shaft               60" (1524)                       86"   (2184)                 4000   fpm   (20.3   m/s)
                                                 support bracket and bearing mounted to damper frame with                  50" (1270)                       96"   (2438)                 4000   fpm   (20.3   m/s)
                                                 factory mounted/welded manual locking quadrant.
                                               Minimum Size: CD-85 (one blade): 6" ¥ 8" (152 ¥ 178)                       Leakage: 18.5 cfm/ft2 @ 20.0 in. wg. (0.09 m3/s/ m2 @ 5.0 kPa) with low
                                                    CD-85 or CD-86 (two blades): 6" ¥ 12" (152 ¥ 305)                        leakage seals.
                                                                                                                                    16.0 cfm/ft2 @ 15.0 in. wg. (0.08 m3/s/ m2 @ 3.8 kPa) with low
                                               Maximum Size: 48" ¥ 72" (1219 ¥ 1829) with seals                              leakage seals.
                                                             60" ¥ 96" (1524 ¥ 2438) without seals                                  11.0 cfm/ft2 @ 7.0 in. wg. (0.06 m3/s/ m2 @ 1.8 kPa) with low
                                                                                                                             leakage seals.
                                             Options
                                                                                                                          Temperature: –65°F to 250°F (–54°C to +121°C) with no seals.
                                             o Factory installed external mount actuator:
                                               o 24 VAC   o 120 VAC   o 230 VAC                                                    –40°F to 250°F (–40°C to +121°C) with EPDM seals.
                                               o Pneumatic   o Modulating
                                             o Stainless steel jamb seals.
                                             o Low leakage blade edge seals (includes flexible metal jamb
                                               seals): o PVC   o Silicone
                                             o Stainless steel construction:
                                               o 304   o 316
                                                                                                                                                      H*
                                             o Vertical mounted blades with thrust washers.
                                             o Bolt holes in damper frame:
                                               o One side   o Both sides
                                                                                                                                        †
                                                                                                                                            2" (51)
                                                                                                                                             Std.
Control Dampers CD85/CD86 (1/2) April 2014
                                                              8" (203)                          8" (203)                                                              W*
                                                               Std.                              Std.
                                                                          2" (51) Std.                     2" (51) Std.
                                                                                                                                                                               Model CD-86
                                                                                                                                                                     *Damper dimensions furnished
                                                                                                                                                                           approximately net I.D..
                                                             CD-85                             CD-86
                                                                                                                                                  †
                                                                                                                                                      211/16" when equipped with frame mounted bearings.
                                             Information is subject to change without notice or obligation.                                                NOTE: Dimensions in parentheses ( ) are millimeters.
                                             POTTORFF ®                  5101 Blue Mound Road, Fort Worth, Texas 76106                                                                      www.pottorff.com
CD-85 and CD-86 Bolt Hole Dimensions
                  E                      M
                                                                 J                       Dimension                              Description
                                                                                     M __________ inches                       Hole Diameter
                                                                                     E __________ inches     Centerline of Bolt Hole From Inside Edge of Frame
                                                                 K
                                                                                     F __________ inches                 First/Last Hole in Head/Sill
                                                                                     G ___ @ ___(x) inches         Number of Holes/Spacing in Head/Sill
                                                                                     J __________ inches                   First/Last Hole in Jamb
                                                                                     K ___ @ ___(z) inches          Number of Holes/Spacing in Jamb
                                         G
                   F
Airflow Performance Data
   Pressure Loss vs. Velocity                                                                                 Pressure Limitations
      Figure 5.3 — Ducted Inlet and Outlet                                                  Without Seals                           With Seals
                                                  Pressure drop testing was
                                                  performed in accordance with
                                                  AMCA Standard 500-D using
                                                  Figure 5.3 — Ducted Inlet and
                                                  Outlet. All data has been
                                                  corrected to represent air
                                                  density of 0.075 lb/ft. Actual
                                                  pressure drop in any ducted
                                                  HVAC system is a combination
                                                  of many elements. This
                          42 x 42
                                                  information, along with analysis
                                                  of other system influences,
                                                  should be used to estimate
                                                  actual pressure losses for a
                                                  damper installed in a given
                                                  HVAC system.
                                                                                                                                                                           Control Dampers CD85/CD86 (1/2) April 2014
             5D                     6D                                                                         Velocity Limitations
                                                                                                                                                     4000 fpm
                                                                                                                                                     (20.3 m/s)
     Ducted Inlet and Outlet                                                                                              6000 fpm                   5000 fpm
     AMCA Figure 5.3 Illustrates a fully ducted                                                                            (30.5 m/s)                (25.4 m/s)
     damper. This configuration represents the
     lowest pressure drop of the three test
     configurations because entrance and exit
     losses are minimized by straight duct runs
     upstream and downstream of the damper.
Information is subject to change without notice or obligation.                                                      NOTE: Dimensions in parentheses ( ) are millimeters.
POTTORFF ®               5101 Blue Mound Road, Fort Worth, Texas 76106                                                                            www.pottorff.com