165 kVA / 132 kW
POWERED by CUMMINS
APD165C-6
60 Hz.
1800 rpm.
DIESEL GENERATING SET 480/277V, 440/254V, 380/220V, 220/127V- 60 Hz
MODEL APD165C-6
kVA 165
Standby
Power kW 132
Pf. 0.8 kVA 150
Prime
kW 120
Standby : Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046 .
Prime : Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,ISO 3046.
High quality, reliable and complete power unit
Compact design
Easy start and maintenance possibility
Every generating set is subject to a comprehensive test program which includes full load testing and
checking and providing of all control and safety shut down functions testing
Full engineered with a wide range of options and accessories: Canopy, sound proof canopy and on road trailer
Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
ENGINE
CUMMINS
Model 6BTAA5.9G2
Engine Power Output kWm 140
at rated rpm HP 187.74
Aspiration and Cooling Turbocharged & Intercooled
Total Displacement Litre 5.9
No. of Cylinders and Build 6 - Inline
Engine Speed rpm 1800
Bore and Stroke mmxmm 102x120
Compression Ratio 17.5:1
Governor Electronic
Fuel Consumption at full load L/hr 33.4
Fuel Tank Capacity Litre Open: 195/Canopy: 195
Oil Capacity Litre 16.5
Coolant Capacity Litre 27
Radiator Cooling Air m³/min 148
Air Intake – Engine m³/min 9
Exhaust Gas Flow m³/min 25
Heavy duty Cummins diesel engine Cooling radiator and fan
Four stroke, water cooled, turbocharged&Intercooled Starter battery (with lead acid) including Rack and
Direct injection fuel system Cables
Electronic Governor system Flexible fuel connection hoses and manual oil sump
12/24 V D.C. starter and charge alternator drain valve
Replaceable fuel filter, oil filter and dry element air filter Industrial capacity exhaust silencer and steel bellows
Jacket water heater(at automatic models)
Operation manuals and circuit diagram documents
ALTERNATOR
Design Brushless single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation System Class H
Standard Temperature Rise 125 - 163°C Continuous
Exciter Type Self Excited
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal blower fan
No load < 1.5%. Non distorting balanced
AC Waveform Total Harmonic Distortion
linear load < 5%
Telephone Influence Factor (TIF) <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) <2%
Brushless, single bearing system, flexible disc, 4 poles Impregnation with tropicalised epoxy varnish
Insulation class H Solid state Automatic Voltage Regulator
Standard degree of protection IP21 (*IP22/IP23 is availab.) Stator winding with 2/3 pitch for improved harmonics
Self-exciting and self-regulating
CONTROL SYSTEM
Control supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:
1. Auto Mains Failure Control Panel
Panel equipments:
Control with AMF module
Static battery charger
Emergency stop push button DSE 6020
a) Generating set control module DSE 6020 features:
The module is used to monitor main supply and c) Alarms:
starts and stops of a standby generating set Over and Under Speed
Micro-processor based design Low and High Battery Volt.
Automatic control of main and generator contactors Start and Stop Failure
Monitors engine performance and AC power output LED Charge fail
alarm indication Over Current
Front panel configuration of timers and alarm trip points Under / Over Generator Voltage
CAN and magnetic pick-up versions(specify on ordering) Low Oil Pressure
4 digital inputs/3 analogue inputs Emergency stop
6 outputs(4 configurable on Magnetic Pick-up, 6 configurable on High engine temperature
CANbus version)
Easy push button control d) LED Indications:
STOP/RESET - MANUAL - AUTO - TEST – START Mains available
Generator available
b) Metering via LED display: Mains on load
Generator Volts (L-L / L-N) Generator kVA Generator on load
Engine oil pressure (PSI-Bar) Generator kW
Generator Ampere (L1,L2,L3) Generator Cos (σ)
Engine temperature (°C&°F) 2. Power Outlet Terminal Board Mounted
Generator Frequency (Hz) on the Gen-set Base frame
Plant battery volts
Engine hours run
Mains Volts (Ph-Ph/Ph-N)
OPTIONAL EQUIPMENTS Panel
Charge ammeter
Diesel Engine Transfer Switch 3Pole
Oil heater Transfer Switch 4 Pole
Earth Fault ,single set
Alternator Accessories
3/4 Pole Output Circuit Breaker Bulk fuel tank
Anti-condensation Heater Automatic filling system
Fuel-water separator filter
Panel Low fuel level alarm
Charge ammeter Residential silencer
Transfer Switch 3Pole Enclosure or sound proof canopy
Transfer Switch 4 Pole Trailer
Earth Fault ,single set Manual oil drain pump
Tool kit for maintenance
CHASSIS
The complete gen-set is mounted as whole on a heavy-duty fabricated,
steel base frame
Antivibration pads are fixed between the engine/ alternator feet and the base frame
Base frame design incorporates an integral fuel tank (Up to 750 kVA)
The generating set can be lifted or carefully pushed/ pulled by the base frame
Dial type fuel gauge and drain plug on the fuel tank
Forklift pockets within base frame (up to 500kVA)
DIMENSIONS
OPEN TYPE
DIMENSIONS (LxWxH) mm 2150x1000x1482
DRY WEIGHT kg 1340
SOUND ATTENUATED TYPE
DIMENSIONS (LxWxH) mm 3321x1068x1732
DRY WEIGHT kg 1820
CANOPY
All canopy parts are designed with modular principles Exhaust silencer is protected against environment influences
Without welding assembly Thermally insulated engine exhaust system
Doors on each side Emergency stop push button is installed outside of the canopy
All metal canopy parts are painted by electrostatic Easy lifting and moving
polyester powder paint Easy maintenance and operation
Aksa Power Generation
Evren Mah.Gulbahar Caddesi 1.Sokak Gunesli-Istanbul-TURKEY
Tel:+90 212 478 66 66 Fax:+90 212 657 55 16 E-mail: aksa@aksapowergen.com
www.aksapowergen.com
Aksa Power Generation is a member of www.aksa.com.tr