VS–DSS SERIES
VERTICAL DISTRIBUTOR STORAGE SYSTEM
Chart’s VS-DSS (Distributor Storage System) Series of vertical
bulk storage stations are engineered for superior
performance, durability and value. Equipped with our
proprietary Composite Super InsulationTM (a light-weight
system offering better thermal performance than Perlite), the
VS-DSS series provides reduced product losses and a slower
rate of pressure rise during periods of non-use. Backing up
this performance is a competitive 2-year vacuum warranty.
Available in the 1500, 3000, and 6000 gallon (5700, 11,400, and
23,000 liter) models, the VS-DSS series features the industry
standard thermal performance. The modular plumbing
system has been selectively optimized to meet the flow
requirements of a complete range of liquid or gas
applications. With a comprehensive set of plumbing features,
each circuit has been carefully designed to match the
demands placed on these vessel sizes. Dual safety relief
devices are standard, and tank mounted vaporizers are
optional on 1500 gallon sizes.
PRODUCT ADVANTAGES
• Sizes, pressures and configurations to meet most
applications
• Backed by our standard 2-year vacuum warranty
• Leg design provides better access to anchor bolts for
quicker installation
• Lower tare weight reduces freight and pad costs
• Long-life urethane paint system
• Plumbing built in accordance with ASME B31.3 code
and leak tested at 1.1 times the MAWP
• Inner vessel designed and built to ASME Section VIII
Division 1 code
VS–DSS SERIES
VERTICAL DISTRIBUTOR STORAGE SYSTEM
Model Gross Capacity Net Capacity MAWP* Flow Capacity** Diameter Height Weight*** NER % /day NER % /day
Gal Liters Gal Liters psig bar SCFH Nm3/hr in mm in mm lbs. Kg in O 2 / Ar in N 2
VS 1500SC-DSS 1,640 6,208 1,580 5,981 250 17.2 9,000 237 66 1,676 196 4,978 6,200 2,818 .35 .56
VS 3000SC-DSS 3,150 11,924 3,030 11,470 250 17.2 18,000 473 86 2,184 228 5,791 12,800 5,806 .25 .40
VS 6000SC-DSS 6,010 22,750 5,770 21,842 250 17.2 18,000 473 86 2,184 383 9,728 21,500 9,752 .15 .24
* MAWP - Maximum Allowable Working Pressure ** Flow capacity rating down to a 20% contents level with a maximum fall off in tank operating pressure of 15 psi (1 bar)
*** Weights are for ASME designs (NER) = Normal Evaporation Rate
Nomenclature
A Top Fill C-1 Connection, Aux Liquid PSV-1B Pressure Safety Valve, Inr Ves
K B Bottom Fill C-2 Connection, Aux Vapor S-1 Strainer, Pressure Building
FA H J
C Aux Liquid C-3 Connection, Secondary Aux Liq TSV-2 Thermal Safety Valve, Fill
HCV-5
VR-1 G
D Gas Use C-4 Connection, Secondary Aux Vapor TSV-3 Thermal Safety Valve, Economizer
E Liquid Phase CV-1 Check Valve, Fill TSV-4 Thermal Safety Valve, PB Circuit
VP-1
F Vapor Phase CV-3 Check Valve, Economizer VP-1 Vacuum Port
FC-1 Connection Fill VR-1 Vacuum Readout, Outer Vessel
G Full Trycock
B HCV-1 Valve, Bottom Fill
E C D H Vent
HCV-2 Valve, Top Fill NOTE: Optional valves (not shown)
J Aux Vapor
HCV-3 Valve, PB Inlet HCV-18 Valve, Liquid W/drawal (from C-1)
K Economizer
HCV-4 Valve, Full Trycock HCV-19 Valve, Vapor Return (from C-2)
HCV-5 Valve, Vacuum Gauge Tube HCV-21 Valve, Sec Aux Liquid (fom C-3)
C-2
HCV-8 C-1 HCV-7 Valve, Fill Line Drain HCV-22 Valve, Sec Aux Vapor (from C-4)
HCV-10 HCV-20
HCV-9 HCV-13 HCV-8 Valve, LI-1 Vapor Phase
PCV-3 HCV-9 Valve, LI-1 Equalization * Dashed lines represent optional components
LI-1
PSV-1B
HCV-4 PI-1 VAP HCV-10 Valve, LI-1 Liquid Phase C-8 Connection, Customer Houseline
PSE-1B HCV-16B
HCV-11 Valve, PB Outlet CV-2 Check Valve, Houseline
HCV-2 HCV-1 PI-2 CV-2 HCV-12 Valve, Vapor Vent HCV-16A Valve, Relief Line Purge
C-8 HCV-31
HCV-15 TSV-8 HCV-13 Valve, Vaporizer Inlet HCV-16B Valve, Relief Line Purge
S-2 HCV-3 HCV-32 HCV-15 Safety Relief Selector Valve HCV-20 Valve, Economizer Vent
C-4 TSV-2 C-3 HCV-30
PSE-1A HCV-16A HCV-7
CV-1
HCV-17 Valve, Economizer HCV-30 Valve, Inlet Houseline
TSV-4 PCV-5
HCV-12 S-1 LI-1 Level Indicator, Inner Vessel HCV-31 Valve, Bypass Houseline
FC-1
PSV-1A HCV-11 PBC-1 Pressure Building Coil, Inr Ves HCV-32 Valve, Outlet Houseline
PCV-1 PCV-2 CV-3 HCV-17 PCV-1 Pressure Control Valve, Inr Ves PCV-3 Pressure Control Valve,Econo Vent
TSV-3
PCV-2 Pressure Control Valve, Econo PCV-5 Pressure Control Valve, Houseline
PBC-1
PI-1 Pressure Indicator, Inner Vessel PI-2 Pressure Indicator, Houseline
Dashed lines indicate optional equipment. PSE-1A Pressure Safety Element, Inr Ves S-2 Strainer, Fill
PSE-1B Pressure Safety Element, Inr Ves TSV-8 Thermal Safety Valve, Houseline
PSV-1A Pressure Safety Valve, Inr Ves VAP Vaporizer, Product Withdrawal
Chart Inc. ©2020 Chart Inc.
U.S. : 1-800-400-4683 P/N 14388368
Worldwide: 1-952-758-4484 www.chartindustries.com