SELECTION TABLE FOR STARTER / RELAY / FUSE / CABLE FOR DOL
MOTORS
HP 3 Phase KW Approxi DOL Typical Typical
415 V 415 V Full Starter / Back up Cable
50 HZ 50 HZ oad Curre Contractor HRC Fuse size
in Amps. Capacity in APMS sq.mm AL
in Amps.
0.50 0.40 1.0 12 6 1.5/2.5
0.75 0.55 1.5 12 6 1.5/2.5
1.0 0.75 2.0 12 10 1.5/2.5
1.5 1.1 2.6 12 10 1.5/2.5
2.0 1.5 3.5 12 15 1.5/2.5
3.0 2.25 5.0 16 20 1.5/2.5
4.0 3.0 6.2 16 20 1.5/2.5
5.0 3.75 7.5 16 25 2.5
6.0 4.5 9 16 25 2.5
7.5 5.6 11 16 25 4.0
10 7.5 14 16 35 4.0
12.5 9.3 18 30 50 6.0
15 11 21 30 50 6.0
17.5 13 24 30 63 10.0
20 15 28 30 63 10.0
25 18.5 35 38 80 16
30 22 40 70 100 25
35 26 47 70 125 25
40 30 55 70 125 25
45 33.5 60 70 160 35
50 37.5 66 70 160 35
60 45 80 105 160 50
75 56 100 105 200 70
90 67.5 120 170 250 95
100 75 135 170 250 95
150 112 200 400 350 185
200 150 275 400 500 300/400
225 170 300 400 600 300/400