PRODUCT-DETAILS
AF65-30-00-11
AF65-30-00-11 24-60V50/60HZ 20-60VDC
Contactor
General Information
Extended Product Type AF65-30-00-11
Product ID 1SBL387001R1100
EAN 3471523132610
Catalog Description AF65-30-00-11 24-60V50/60HZ 20-60VDC Contactor
AF65 contactors are used for controlling power circuits up to 690 V AC and 220 V DC.
They are mainly used for controlling 3-phase motors, non-inductive or slightly
inductive loads. AF... contactors include an electronic coil interface accepting a wide
control voltage Uc min. ... Uc max. Only four coils cover control voltages between
24...500 V 50/60 Hz or 20...500 V DC. AF contactors can manage large control voltage
variations. One coil can be used for different control voltages used worldwide without
Long Description any coil change. AF contactors have built-in surge protection and do not require
additional surge suppressors. The AF... series 1-stack 3-pole contactors are of the
block type design. - Main poles and auxiliary contact blocks: 3 main poles, front and
side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts
compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F
of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a wide range of
accessories is available.
Classifications
Object Classification Q
Code
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
UNSPSC 39121529
AF65-30-00-11 2
E-Number (Sweden) 3210042
Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 150 mm
Package Level 1 Depth / 150 mm
Length
Package Level 1 Height 97 mm
Package Level 1 Gross 1.07 kg
Weight
Package Level 1 EAN 3471523132610
Package Level 2 Units box 10 piece
Package Level 2 Width 250 mm
Package Level 2 Depth / 300 mm
Length
Package Level 2 Height 300 mm
Package Level 2 Gross 10.7 kg
Weight
Package Level 3 Units 240 piece
Certificates and Declarations (Document Number)
ABS Certificate ABS_15-GE1349500-PDA_90682247
BV Certificate BV_2634H36994A
CB Certificate CB_SE-96554
CCC Certificate CCC_2012010304589737
CCC_2015010304824714
Declaration of 1SBD250000U1000
Conformity - CE
DNV Certificate DNV-GL_TAE00001AF-3
DNV GL Certificate DNV-GL_TAE00001AF-3
EAC Certificate EAC_RU C-FR ME77 B03597
Environmental 1SBD250168E1000
Information
GL Certificate DNV-GL_TAE00001AF-3
Instructions and 1SBC101036M6801
Manuals
KC Certificate KC_HW02016-15003C
LR Certificate LRS_1300087E1
RINA Certificate RINA_ELE084013XG
RMRS Certificate RMRS_1802705280
RoHS Information 1SBD250000U1000
UL Certificate UL_20130926-E312527_14_1
UL Listing Card UL_E312527
Technical UL/CSA
Horsepower Rating (220 ... 240 V AC) Three Phase 25 hp
UL/CSA (440 ... 480 V AC) Three Phase 50 hp
(550 ... 600 V AC) Three Phase 60 hp
(120 V AC) Single Phase 5 hp
(200 ... 208 V AC) Three Phase 20 hp
(240 V AC) Single Phase 15 hp
Tightening Torque Control Circuit 11 IA
UL/CSA Main Circuit 35 IA
AF65-30-00-11 3
Environmental
Ambient Air Close to Contactor for Storage -60 ... +80 °C
Temperature Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Climatic Withstand Category B according to IEC 60947-1 Annex Q
Maximum Operating 3000 m
Altitude Permissible
Resistance to Vibrations 5 ... 300 Hz 3 g closed position / 3 g open position
acc. to IEC 60068-2-6
Resistance to Shock acc. Closed, Shock Direction: A 25 K40
to IEC 60068-2-27 Closed, Shock Direction: B1 25 K40
Closed, Shock Direction: B2 15 K40
Closed, Shock Direction: C1 25 K40
Closed, Shock Direction: C2 25 K40
Open, Shock Direction: B1 5 K40
RoHS Status Following EU Directive 2011/65/EU
Technical
Number of Main 3
Contacts NO
Number of Main 0
Contacts NC
Number of Auxiliary 0
Contacts NO
Number of Auxiliary 0
Contacts NC
Rated Operational Main Circuit 690 V
Voltage
Rated Frequency (f) Main Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
Thermal Current (I th )
Rated Operational (690 V) 40 °C 105 A
Current AC-1 (I e ) (690 V) 60 °C 90 A
(690 V) 70 °C 80 A
Rated Operational (220 / 230 / 240 V) 60 °C 65 A
Current AC-3 (I e ) (380 / 400 V) 60 °C 65 A
(415 V) 60 °C 65 A
(440 V) 60 °C 65 A
(500 V) 60 °C 55 A
(690 V) 60 °C 39 A
Rated Operational Power (220 / 230 / 240 V) 18.5 kW
AC-3 (P e ) (380 / 400 V) 30 kW
(415 V) 37 kW
(440 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
(400 V) 30 kW
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
Withstand Current (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 1 s -empty- A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical AC-1 600 cycles per hour
Switching Frequency AC-2 / AC-4 150 cycles per hour
AC-3 1200 cycles per hour
Rated Insulation Voltage acc. to UL/CSA 600 V
(U i ) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse 6 kV
Withstand Voltage (U imp
)
Maximum Mechanical 3600 cycles per hour
Switching Frequency
AF65-30-00-11 4
Rated Control Circuit 50 Hz 24 ... 60 V
Voltage (U c ) 50 Hz / 60 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Operate Time Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Connecting Capacity Rigid 1/2x 6 ... 3 5 m²
Main Circuit Flexible with Ferrule 1/2x 4 ... 35 m²
Flexible with Insulated Ferrule 1/2x 4 ... 35 m²
Connecting Capacity Flexible with Ferrule 1/2x 0.75 ... 2.5 m²
Control Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 m²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 m²
Rigid 1/2x 1 ... 2.5 m²
Wire Stripping Length Main Circuit 16 mm
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type Screw Terminals
Dimensions
Product Net Width 55 mm
Product Net Depth / 111 mm
Length
Product Net Height 125.5 mm
Product Net Weight 0.97 kg
Popular Downloads
Instructions and 1SBC101036M6801
Manuals
Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900
Categories
Low Voltage Products and Systems → Control Products → Contactors → Block Contactors