System Power Requirements
DAA2-5025/DAA2-5070 Digital Audio Amplifier
Protected Premises: AMP-ING-P1 Date:
Address:
City: State: Zip:
Prepared By: Phone:
Address: Email:
City: State: Zip:
AC Branch Current Requirements 1,17 AMPS @ 220/240 VAC
Current required by source to power the fire
alarm system.
Secondary Load Requirements 15,80 Amp Hours
Total Secondary Load from the calculation table below.
Current Draw Time (hours) Total (AH)
Secondary Standby Load Required Standby Time
x
0,500 A 24 hours 12,00
Secondary Alarm Load Required Alarm Time (hours)
x
2,325 A 0,500 hours 1,16
Total Secondary Load 13,16
Derating factor x 1,2
Secondary Load Requirements 15,80 AH
Battery Selection 18 Amp Hours
Select batteries from the list below.
18 AH BAT-12180 Battery (12 volt)
Two Four (two 12VDC sets in parallel)
VERDADERO
Page 9 of 11
Battery Distribution Chart
Shows amp-hour distribution of your selections.
Spare Battery Capacity
Spare Battery Capacity
Secondary Alarm Load 12%
8%
Secondary Standby Load
Secondary Alarm Load
Secondary Standby
Load
80%
Comments
1. Battery size exceeds FACP capacity. BB-26 or other external battery box
2. Selected battery size meets secondary load requirements.
3. The selected batteries (18AH) are within the charger range of this power supply (12-200AH).
Spare Battery Capacity 2,20 Battery Selection (AH) - Secondary Load Requirements (AH)
Secondary Standby Load 14,40 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 1,40 Secondary Alarm Load (AH) * Derating Factor
Page 10 of 11
Device Current Draw
DAA2-5025/DAA2-5070 Digital Audio Amplifier
Quantity x [device current draw] = total current draw per device (in amps)
Part Number Qty Secondary Non-Alarm Secondary Alarm
DAA2-5025 with FFT Riser 1 x [0,40000] = 0,40000 x [0,50000] = 0,50000
BDA-25V (Backup) 1 x [0,10000] = 0,10000 x [0,22500] = 0,22500
SPSCR110 1 x [0,00000] = 0,00000 x [0,03200] = 0,03200
Total (Amperes): 0,5000 A 2,3250 A