ENVIRONMENTAL
ENGINEERING II
(CE 4803)
Slide Credits:
PROF.DR ZULFIQAR ALI KHAN
LECTURE NO : 4
SEWER APPURTENENCE
SEWER APPURTENENCES
Appurtenances are those devices, other than
sewers, which are essential for the operation
of sewer systems. These include;
Manholes, Drop manholes
Inlets, Catch basins
Oil and grease traps
Flush tanks
Inverted siphons
Pumping station
SEWER APPURTENENCES
MANHOLES:
Purpose, spacing, locations have already been discussed. A
standard brick manhole sketch is shown in fig below.
SEWER APPURTENENCES
DROP MANHOLE:
When lateral or sub-mains join in a deeper sewer,
excavation will be saved by keeping the upper sewer
at a reasonable grade and making a vertical drop at
the manhole. This is known as “Drop Manhole”.
Fig: Drop Manhole
SEWER APPURTENENCES
INLETS:
An inlet is an opening into a storm or combined
sewer for entrance of storm sewage.
i. Curb Opening Inlet
SEWER APPURTENENCES
INLETS:
ii. Grate Inlet:
SEWER APPURTENENCES
INLETS:
iii. Catch Basins:
These are same as inlets but deeper enough
to store the settled grit which is then removed
periodically.
SEWAGE PUMPING STATION
Objectives:
To elevate and transport wastewater when;
Continuation of gravity flow is no longer feasible.
Basements of buildings are below the grade of the
sewer
Any obstacle lies in the path of sewer
Receiving stream is higher than the sewer
Sewage is to be delivered to an above ground
treatment plant.
COMPONENTS OF SEWAGE PUMPING STATION
1. Screens
2. Dry Well For installation of pumps
3. Wet Well For receiving wastewater
4. Pumps along with valves, pipes, motor,
control panel etc.
SEWAGE PUMPING STATION
DESIGN CONSIDRATIONS:
Pump suctions are usually larger than the discharge
(force main)
The smallest discharge pipe: 75 mm
The smallest suction pipe: 100 mm
Capacity of Pumps: Max Sewage Flow
No. of Pumps: Minimum two
Screens should be provided to remove particles
larger than 50 mm size.
Sump pump should be provided in dry well to pump
leakage water.
SEWAGE PUMPING STATION
Selection of Pumps for Sewage:
Centrifugal, Vertical, Non-clog Type
Impeller having 2 - 3 vanes
Speed 200 – 1200 RPM
Operating Conditions:
Pumps should be self-priming type or should
operate under positive suction head.
Each pump should have an individual intake.
SEWAGE PUMPING STATION
Operating Conditions: (cont…)
The pump must run for at least 2 minutes.
Cycle time must not be less than 5 minutes.
Cycle Time:
“It is the time between successive start-ups of the
motor pump”
The detention time in the wet well should,
preferably, be not more than 30 minutes.
SEWAGE PUMPING STATION
Design of Wet Well:
Design of wet well refers to the calculation of
operating volume of wet well. It is designed on
the basis of minimum cycle time.
Cycle Time = Time on + Time off
= Time to empty + Time to fill
Let V be the volume of wet well;
Cycle Time = V/(P – Q) + V/Q ………(1)
Where;
P = Pumping rate (constant)
Q = Sewage inflow (Variable)
SEWAGE PUMPING STATION
Design of Wet Well (Cont….)
To find minimum cycle time, differentiate eq-1
w.r.t. Q
dt/dQ = V/(P-Q)2 + V/Q2
for min. cycle time, dt/dQ = 0
0 = V/(P-Q)2 + V/Q2
Q = P/2
NOTE: Minimum cycle time will be reached when sewage folw rate is half of the
pumping rate.
SEWAGE PUMPING STATION
Design of Wet Well (Cont….)
Putting Q=P/2 in eqn-1 gives
tmin = V/(P-P/2) + V/(P/2)
tmin = 4V/P
V = (tmin x P )/4