GRE130 Catalog
GRE130 Catalog
2
GRE130
PROTECTION FUNCTIONS Zero Phase Sequence Overvoltage
Protection (ZPS)
Phase Overvoltage Protection GRE130 provides ZPS protection with two independent
GRE130 overvoltage protection provides three overvoltage thresholds. The two thresholds may be
independent overvoltage thresholds. The first and set for inverse time or definite time operation. The two
second thresholds may be set for inverse time or thresholds have a programmable reset feature,
definite time trip operation. The third threshold can be selectable for instantaneous or definite time operation.
programmed for definite time alarm operation. In the case of [APPL = 3PN] setting, the zero sequence
The first and second thresholds has a programmable voltage, V0 may either be calculated from the three
reset feature, selectable for instantaneous or definite measured phase voltages. At other setting, the V0
time operation. Each trip output can be inhibited by must be measured directly.
binary input. Each trip output can be inhibited by binary input.
1000.000 1000.000
1 000 .000
100 .000
100.000
100.000
Operating Time (secs)
Operating Time (secs)
Operating Time (secs)
10 .000
10.000
TMS = 10
TMS = 5
TM S = 10 1 .000
TMS =
10.000
TMS = 2 TMS = 5 TMS =
1.000
TMS = 1 TMS =
0 .100
TMS = 2 TMS =
TMS = 1
1 1 1
t
V Vs 1 TMS t
1 V Vs TMS t
V Vs 1 TMS
Figure 1 - IDMT curves for Overvoltage, Undervoltage and ZPS, NPS Overvoltage
3
GRE130
MONITORING FUNCTIONS
Under / Over frequency Protection
Trip Circuit Supervision
GRE130 underfrequency protection is provided to
maintain the balance between the power generation GRE130 provides a high-integrity trip circuit
capability and the loads. It is also used to maintain supervision scheme. Trip circuits can be monitored
the frequency within the normal range by load with the circuit breaker either closed or open using
shedding. two binary inputs as shown in Figure 3.
GRE130 overfrequency protection is provided to
protect synchronous machines from possible damage
due to overfrequency conditions.
4
GRE130
CB trip count. recorded data. Figure 4 shows the configuration of
CB status. typical displays from the RSM100 software.
Relay element output status.
Binary input and output status. Modbus and DNP3.0 Communications
GRE130 supports the Modbus and DNP3.0
Event Record communication protocol. These protocols are used for
Records are stored for the 200 most recent events, communication with a substation control and monitoring
time-tagged to 1ms resolution. The event record is system or automation system to be linked with SCADA
available on the relay front panel LCD and at a local or or regional control center, and are used to transfer
remote PC. Events are recorded as follows: measurand data, status data and general commands
Tripping operations. between the relay and the control system.
Alarms.
IEC 60870-5-103 Communications
Operation of protection elements.
Change of state of binary inputs / outputs. GRE130 supports the IEC60870-5-103
Change of relay setting. communication protocol. This protocol is used
Failure detected by automatic supervision. for communication with a substation control and
monitoring system and is used to transfer measured
Fault Record
data, status data and general commands between the
A relay trip initiates fault recording. Records are stored for relay and the control system via RS485.
the 5 most recent faults, time-tagged to 1ms resolution.
IEC 61850 Communication
The fault record is available on the relay front panel LCD
GRE110-402A and 422A can support data
and at a local or remote PC. Fault records include the communication according to the IEC 61850 standard via
following data: an optional communication port.
Date and time of trip operation.
Faulted phase. Relay Setting
Protection element responsible for trip.
The user can modify relay settings either using the front
Measured voltage data.
panel keypad or using the RSM100 software from a local
Disturbance Record PC. Password protection is available for added security.
The relay can record 4 analog and 32 binary signals, Two settings groups are provided, allowing the user to
initiated by relay tripping. The post-trigger recording time set one group for normal conditions, while the other
can be set, and the maximum number of records which group may be set to cover alternative operating
can be stored is dependent on the recording time conditions.
chosen. Using the RSM software, the user can create a settings
file on a PC (without being connected to a relay), and
USER INTERFACE
store the file ready for download to a relay at a later date.
Relay Front Panel
Binary Outputs
A user friendly interface is provided on the relay front
GRE130 provides four or eight user programmable
panel. A menu-based system provides for easy
binary output contacts for tripping and alarm. Each of the
programming of relay functions and access to real-time
programmable binary outputs is driven via a logic gate
and stored data. The front panel includes the following
which can be programmed for OR gate or AND gate
features.
operation. Further, each output has a programmable
16 character, 8-line LCD with backlight.
reset characteristic, settable for instantaneous drop-off,
14 LEDs (8 fixed display and 6 configurable).
delayed drop-off, or for latching operation. If latching
USB2.0 port for connection of local PC.
operation is selected then an operated relay must be
Local PC Connection reset by the user, either by pressing the RESET button,
The user can communicate with the GRE130 from a by energising a binary input which has been
local PC via the USB2.0 port on the front panel. Using programmed for ‘Remote Reset’ operation, or by a
RSM100 software, the user can view and modify communications command.
5
GRE130
Binary Inputs operation to a different settings group.
GRE130 provides two programmable binary inputs as General purpose alarm functions are also included. The
standard and a further four available as an option. Each user can define a text message for each alarm. Then
binary input is individually user-programmable for normal when inputs associated with that alarm are raised, the
or inverted operation and for delayed pick-up and/or defined text is displayed on the LCD.
drop-off. Each input can also be used to switch relay
PC DISPLAY
Data analysis
6
GRE130
TECHNICAL DATA
Ratings
AC voltage Vn: 110V
Frequency: 50/60Hz
Power supply: 110-250Vdc or 100-220Vac
(Operative range: 88–300Vdc / 88–264Vac)
48-110Vdc (Operative range: 38.4 – 132Vdc)
24-48Vdc (Operative range: 19.2 – 60.0Vdc)
Superimposed AC ripple on DC supply: maximum 12%
Power supply interruption: maximum 50ms at 110V
Binary input circuit DC voltage: For alarm indication
110-250Vdc (Operative range: 88 - 300Vdc)
48-110Vdc (Operative range: 38.4 - 132Vdc)
24-48Vdc (Operative range: 19.2 – 60.0Vdc)
For trip circuit supervision
Operative range: ≥38.4V (for 110Vdc rating)
≥88V (for 220/250Vdc rating)
≥19.2V (for 48Vdc rating)
≥9.6V (for 24Vdc rating)
Overload Ratings
AC voltage inputs: 2 times rated voltage continuous
Burden
AC phase voltage inputs: 0.1 VA (at rated voltage)
Power supply: 10W (quiescent), 15W (maximum)
Binary input circuit: 0.5W per input at 220Vdc
Overvoltage Protection (59)
1st, 2nd, 3rd Overvoltage thresholds: OFF, 10.0 – 200.0V in 0.1V steps
Delay type: DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
DO/PU ratio 10 - 98% in 1% steps
Reset Delay: Instantaneous, 0.1 – 300.0s in 0.1s steps
Undervoltage Protection (27)
1st, 2nd, 3rd Undervoltage thresholds: OFF, 5.0 – 130.0V in 0.1V steps
Delay type: DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay: Instantaneous, 0.1 – 300.0s in 0.1s steps
Zero Sequence Overvoltage (ZPS) Protection (59N)
1st, 2nd ZPS Overvoltage thresholds: OFF, 1.0 – 130.0V in 0.1V steps
st
Delay type (1 threshold only): DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay (1st threshold only): Instantaneous, 0.1 – 300.0s in 0.1s steps
Negative Sequence Overvoltage (NPS) Protection (47)
1st, 2nd NPS Overvoltage thresholds: OFF, 1.0 – 130.0V in 0.1V steps
Delay type (1st threshold only): DTL, IDMTL
IDMTL Time Multiplier Setting TMS: 0.05 - 100.00 in 0.01 steps
DTL delay: Inst, 0.01 - 300.00s in 0.01s steps
Reset Delay (1st threshold only): Instantaneous, 0.1 – 300.0s in 0.1s steps
7
GRE130
Frequency Protection (81U/O)
1st – 4th Under frequency 45.00 – 50.00 Hz in 0.01Hz steps (rated frequency: 50Hz)
54.00 – 60.00 Hz in 0.01Hz steps (rated frequency: 60Hz)
1st – 4th Under frequency 50.00 – 55.00 Hz in 0.01Hz steps (rated frequency: 50Hz)
60.00 – 66.00 Hz in 0.01Hz steps (rated frequency: 60Hz)
Frequency rate-of-change 0.1 to 9.9Hz/s in 0.1Hz/s steps
0.1 to 9.9Hz/s in 0.1Hz/s steps
Timer for stage 1st - 4th 0.00 – 100.00 s in 0.01 s steps
Frequency UV Block 40 – 100V in 1V steps
Accuracy
IDMTL Overvoltage Pick-up: 105% of setting 5%
All Other Overvoltage Pick-ups: 100% of setting 5%
Overvoltage PU/DO ratio: approx, 95% (settable for phase overvoltage)
IDMTL Undervoltage Pick-up: 95% of setting 5%
All Other Undervoltage Pick-ups: 100% of setting 5%
Undervoltage PU/DO ratio: approx, 105%
Over Frequency Pick-ups: 100% of setting 0.05Hz (setting: rated frequency - 5.00Hz)
Under Frequency Pick-ups: 100% of setting 0.05Hz (setting: rated frequency + 5.00Hz)
Frequency rate-of-change Pick-ups: 100% of setting 0.07Hz/s (setting: 5.00Hz/s)
Inverse Operate Time: IEC60255-127, 5% or 100ms
(OV; 1.2 G/Gs GD/Gs , UV; 0 G/Gs 1) GD = 300V
OV Definite Operate Time; DTL + 45ms (DT, input: ≥ 200% of setting)
UV Definite Operate Time; DTL + 45ms (DT, input: 80% of setting)
ZPS Definite Operate Time; DTL + 45ms (DT, input: ≥ 200% of setting)
NPS Definite Operate Time; DTL + 50ms (DT, input: ≥ 200% of setting)
Under/Over Frequency Operate Time DTL + 80-200ms (rated frequency: 50Hz)
DTL + 70-170ms (rated frequency: 60Hz)
Frequency rate-of-change Operate Time 190-300ms (rated frequency: 50Hz, input: ≥ 200% of setting)
160-250ms (rated frequency: 60Hz, input: ≥ 200% of setting)
Time delays includes operating time of trip contacts
Front Communication port - local PC (USB2.0)
Connector type: USB-Type B
Cable length: 5m (max.)
Rear Communication port - remote PC (RS485)
Connection: Multidrop (max. 32 relays)
Cable type: Twisted pair
Cable length: 1200m (max.)
Connector: Screw terminals
Isolation: 1kVac for 1 min.
Transmission rate: 19.2 kbps
Rear Communication port (Ethernet)
100BASE-TX RJ-45 connector
100BASE-FX SC connector
Binary Inputs
Operating voltage For signal detection
Typical 154Vdc (min. 110Vdc) for 220Vdc rating
Typical 77Vdc (min. 70Vdc) for 110Vdc rating
Typical 33.6Vdc (min. 24Vdc) for 48Vdc rating
Typical 16.8Vdc(min. 12Vdc) for 24Vdc rating
8
GRE130
For trip circuit supervision
≥88V for 220/250Vdc rating
≥38.4Vdc for 110Vdc rating
≥19.2V for 48Vdc rating
≥9.6V for 24Vdc rating
Binary Outputs
Number 4 or 8 (excluding Relay Fail contact)
Ratings Make and carry: 5A continuously
model 410 and 411; BO#1 and #2 Make and carry: 30A, 250Vdc for 0.5s (L/R40ms)
model 412: BO#1,#2,#5 and #6 Break: 0.1A, 250Vdc (L/R=40ms)
ENVIRONMENTAL PERFORMANCE
Test Standards Details
Atmospheric Environment
Temperature IEC 60068-2-1/2 Operating range: -20C to +60C.
IEC 60068-2-30 Storage / Transit: -25C to +70C.
Humidity IEC 60068-2-78 56 days at 40C and 93% relative humidity.
Enclosure Protection IEC 60529 IP52 (front), IP20 (rear), IP40 (top)
Mechanical Environment
Vibration IEC 60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC 60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC 60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC 60255-5 2kVrms for 1 minute between all terminals and earth.
IEEE C37.90.0 2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
High Voltage Impulse IEC 60255-5 Three positive and three negative impulses of
5kV(peak) for CT, Power Supply Unit (PSU), BI and BO
circuits; between terminals and earth, and between
9
GRE130
Test Standards Details
independent circuits
3kV (peak) for RS485 circuit; between terminals and earth
3kV (peak) for BO circuit; across normally open contacts
1.2/50s, 0.5J between all terminals and between all terminals
and earth.
Electromagnetic Environment
High Frequency IEC 60255-22-1 Class 3, 1MHz 2.5kV to 3kV (peak) applied to all ports in common
Disturbance / Damped IEC 61000-4-12 mode.
Oscillatory Wave IEEE C37.90.1 1MHz 1.0kV applied to all ports in differential mode.
Electrostatic IEC 60255-22-2 Class 3, 6kV contact discharge, 8kV air discharge.
Discharge IEC 61000-4-2
Radiated RF IEC 60255-22-3 Class 3, Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
Electromagnetic IEC 61000-4-3 and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450,
Disturbance 900 and 1890MHz.
Fast Transient IEC 60255-22-4 Class A, 4kV, 2.5kHz, 5/50ns applied to all inputs.
Disturbance IEC 61000-4-4,
IEEE C37.90.1
Surge Immunity IEC 60255-22-5, 1.2/50s surge in common/differential modes:
IEC 61000-4-5 HV, PSU and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted RF IEC 60255-22-6 Class 3, 10Vrms applied over frequency range 150kHz to 100MHz.
Electromagnetic IEC 61000-4-6 Additional spot tests at 27 and 68MHz.
Disturbance
Power Frequency IEC 60255-22-7 Class A, 300V 50Hz for 10s applied to ports in common mode.
Disturbance IEC 61000-4-16 150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Conducted and IEC 60255-25, Conducted emissions:
Radiated Emissions EN 55022 Class A, 0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
IEC 61000-6-4 0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 10m):
30 to 230MHz: <40dB
230 to 1000MHz: <47dB
European Commission Directives
89/336/EEC Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to generic
EMC standards EN 61000-6-2 and EN 61000-6-4.
73/23/EEC
Compliance with the European Commission Low Voltage
Directive is demonstrated according to product safety standard
EN 60255-27.
10
GRE130
ORDERING
Type:
Voltage Relay GRE130
Model:
- Model 410: Four pole
2 x BIs, 4 x Bos, 1 x Relay fail 410
6 x BIs, 4 x BOs, 1 x Relay fail 411
6 x BIs, 8 x BOs, 1 x Relay fail 412
Rating:
VT: 110V, f: 50/60Hz, 110-250Vdc or 100-220Vac 1
VT: 110V, f: 50/60Hz, 48-110Vdc 2
VT: 110V, f: 50/60Hz, 24-48Vdc A
Standard and language:
IEC (English) 0
ANSI (English) 1
Chinese 2
Communication:
RS485 1port (Modbus/IEC60870-5-103) 10
RS485 1port (Modbus/DNP3.0) 11
Following options can be equipped with Model 402
and 422 only 20
RS485 2ports (Modbus/IEC60870-5-103) 21
RS485 2ports (Modbus/DNP3.0) A0
100BASE-TX 1port (Modbus/IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) A1
100BASE-TX 1port (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0) B0
100BASE-TX 2ports (Modbus/IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) B1
100BASE-TX 2ports (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0) C0
100BASE-FX 1port (Modbus/IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) C1
100BASE-FX 1port (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0) D0
100BASE-FX 2ports (Modbus/ IEC61850)
+RS485 1port (Modbus/IEC60870-5-103) D1
100BASE-FX 2ports (Modbus/ DNP3.0)
+RS485 1port (Modbus/DNP3.0)
11
GRE130
TYPICAL APPLICATIONS / CONNECTIONS
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-410A TB2
APPL ; 1PP CB CLOSE CB CLOSE
TB1
SW
1
2
1 CB OPEN CB OPEN/TRIP
2 Vph SW
3
3 4
4 AUXILIARY TRIP
COIL
CLOSE
5 5 N
COIL
6 *
6
7 Ve AUXILIARY
8 7
*
9 8
P
10 N.C. Relay fail
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
Available for 33.6/77/154V
FG TCS 13
(CB CLOSED) 14
AUXILIARY Threshold
Available for 33.6/77/154V
FRONT PANEL TCS 15
(CB OPEN) 16 N
USB Type B 17
N.C.
18
19
20
Rear PANEL 22 A+
B-
COM
COM 21 COM
RJ45 N.C. A+ 23 A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
Figure 5 - Typical External Connections for the GRE130 - 410A 1PP setting
12
GRE130
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-410A TB2
APPL ; 2PP CB CLOSE CB CLOSE
TB1 2PZ SW
1
2
1 CB OPEN CB OPEN/TRIP
2 Vab SW
3
3 Vbc 4
4 AUXILIARY TRIP
COIL
CLOSE
5 5 N
COIL
6 *
6
7 Ve AUXILIARY
8 7
*
9 8
P
10 N.C. Relay fail
N 11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11 indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
Available for 33.6/77/154V
FG TCS 13
(CB CLOSED) 14
AUXILIARY Threshold
Available for 33.6/77/154V
FRONT PANEL TCS 15
(CB OPEN) 16 N
USB Type B 17
N.C. 18
19
20
Rear PANEL 22 A+
B-
COM
COM 21 COM
A+ 23 A+
RJ45 N.C. B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
Figure 6 - Typical External Connections for the GRE130 - 410A 2PP ( 2PZ ) setting
13
GRE130
A OUTPUT CONACTS
B SIGNAL LIST (DEFAULT)
Controled
CB
GRE130-411A TB2
APPL ; 3PN CB CLOSE CB CLOSE
TB1 3PV SW
1
2
1 CB OPEN CB OPEN/TRIP
2 Va SW
3
3 Vb 4
4 AUXILIARY TRIP
COIL
CLOSE
5 Vc 5 N
COIL
6 *
6
7 Ve AUXILIARY
8 7
*
9 8
P
10 N.C. Relay fail
N
11 9
12 GND POWER 10 Relay fail
13 + SUPPLY N.C. 11
indicator
14 - DEFAULT BI1-2; Off 12 N
AUXILIARY Threshold
33.6/77/154V
FG Available for 13
TCS 14
AUXILIARY Threshold
33.6/77/154V
FRONT PANEL Available for 15
TCS
Threshold
16
77/154V
USB Type B
(CB CLOSED) AUXILIARY 17
(CB OPEN) AUXILIARY 18
AUXILIARY 19
AUXILIARY 20
Rear PANEL 22 N
A+
B-
COM
COM 21 COM
RJ45 N.C. A+ 23 A+
B- 24 B-
*BO3 and BO4 are NOT applicable for direct CB coil connection.
Figure 7 -Typical External Connections for the GRE130 - 411A 3PN ( 3PV ) setting
14
GRE130
*BO3, BO4, BO7 and BO8 are NOT applicable for direct CB coil connection.
**Analogue current input ports are shorted when the terminal block is removed. (TB2 1-2, 3-4, 5-6, 7-8)
Figure 8 - Typical External Connections for the GRE130 - 412A 3PP setting
15
GRE130
RELAY OUTLINE
16
GRE130
17
GRE130
GKP-99-12025 Rev0.4
18