HVA Report IS1-C.B-Y1: Acceptance Test Finished Successfully

This document summarizes a high voltage test of an underground cable. The test was conducted successfully at two voltage levels without any breakdown events. Key details include the cable's rated voltage of 33kV, insulation type of XLPE, and conductor size. The test used a GH5238 test equipment and applied voltages of 19kV and 44kV at 0.1Hz for 1 and 60 minutes, respectively. Measurements showed load capacities of 440nF and resistances over 20GOhm at each level.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views1 page

HVA Report IS1-C.B-Y1: Acceptance Test Finished Successfully

This document summarizes a high voltage test of an underground cable. The test was conducted successfully at two voltage levels without any breakdown events. Key details include the cable's rated voltage of 33kV, insulation type of XLPE, and conductor size. The test used a GH5238 test equipment and applied voltages of 19kV and 44kV at 0.1Hz for 1 and 60 minutes, respectively. Measurements showed load capacities of 440nF and resistances over 20GOhm at each level.

Uploaded by

Ahmed Rabaa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

HVA Report IS1-C.

B-Y1 Page 1 of 4

Company Location
Customer PO# Owner
Job# Owner
Representative
Date 1/17/2020 10:41:00 AM Temperature
Tested by Humidity
Substation Position
Circuit ID IS1-C.B-Y1
Device Under Test is Cable
Rated Voltage 33.0 kV Operating Voltage
Manufacturer Model
Insulation Type XLPE Insulation Thickness
Shield Type Grounding
Conductor Size Conductor Material
# of Conductors Length
Installed in Age
Cable Test End Cable Far End
Termination Type Termination Type
# of Splices Splice Locations
Jacket (Y/N) - Jacket Integrity

Equipment
Equipment Used GH5238 Serial No. GH5238.17E018

Test Setup
Type of HV Test Acceptance Test Voltage 19.0 / 44.0 kVrms
Waveform Sine Planned Test 1 / 60 min
Duration
Frequency 0.1 Hz Current Limit Trip out on Arc

Measurements / Results
Breakdown No Breakdown Voltage
Time to Failure
Acceptance Test finished successfully
Step Voltage Current Load Cap. Load Res. Frequency
1 19.0 kVrms 5.25 mArms 440 nF >20 GOhm 0.1 Hz
2 44.0 kVrms 12.2 mArms 440 nF >20 GOhm 0.1 Hz
3
4

Test Result X Acceptable Unacceptable

Comments