OIL PUMP TYPE T
GEAR SIZES 2-3-4-5 T
T - 11 - Ed 11- May 2007
This is a general specification leaflet ; for specific applications not
covered herein, contact Suntec. PUMP
IDENTIFICATION
The SUNTEC T oil pump is specially designed for industrial heating applications
using light or heavy oils with high capacity. It is fitted with a preheater location to (Not all model combinations are available
Consult your Suntec representative)
render cold starting easier.
APPLICATIONS
- Light and heavy oil (for kerosene applications, contact SUNTEC). T : No pressure regulation
- SUNTEC recommend the use of a SUNTEC TV valve to regulate the pump
pressure.
Gear set capacity
PUMP OPERATING PRINCIPLE (see pump capacity curves)
The gear set draws oil from the tank and transfers it to an external valve that
regulates the oil pressure.
Shaft rotation
Bleed : (seen from shaft end)
The plug of the pressure gauge port must be loosened until the air is evacuated from A : clockwise rotation
C : anti clockwise rotation
the system.
Note :
The bypass plug inserted beween high pressure and shaft seal is only intended to
change the pump rotation, check the presence of this plug with a 4 mm Allen key
T 2 A 10 6
in the pressure outlet of the pump.
Caution : changing the direction of pump rotation involves changing of all pump
connections.
PREHEATING FACILITY
Care should be taken to avoid starting pump with high viscosity cold oil leading to
pump and coupling damage. For this reason, the T pump body includes a drilling Preheater facility
to accept an electric preheater. This drilling has been located to give maximum heat
transfer from the heater to the oil in the pump without there being direct contact
between the heater cartridge and the oil. Revision number
Heaters should be connected for a period of time prior to starting the pump. When
the right temperature is reached, they can be switched off or left permanently
switched on to maintain fluid oil in the pump during the periodic burner shut-downs.
The oil supply, pipes and filters must be separately heated.
Oil under suction
Plug inserted between To
Oil under pressure high pressure and shaft seal pressure
regulating valve
Vacuum or
inlet pressure Pressure
gauge port gauge port
Intake To
from Tank pressure
regulating
valve
Intake
from Tank
SUNTEC INDUSTRIES FRANCE - 1, rue Lavoisier - BP 102 - 21603 LONGVIC Cedex - Tel. 33 3 80 70 60 70 - Fax 33 3 80 70 61 11- http://www.suntec.fr
Pump capacity
TECHNICAL DATA Capacity (L/h)
4200 T5
4000
General 3800
3600
Mounting Flange mounting 3400
Connection threads Cylindrical according to ISO 228/1 3200
3000 T4
2800
2600
2400
Shaft Ø 20 mm 2200 T3
2000
Weight 7,8 kg (T2) - 8,1 kg (T3)
Ref : SK 226,227,295 ; 23/01/06
1800
8,7 kg (T4) - 9,4 kg (T5)
1600 T2
1400
Hydraulic data 1200
1000
Nozzle pressure range 40 bars max. (T2, T3, T4) 800
30 bars max. (T5) 0 5 10 15 20 25 30 35 40 45
Operating viscosity 3 - 75 mm²/s (cSt) Pressure (bars)
(Higher viscosity oil can be used by feeding the pump Viscosity = 75 cSt
20 cSt
or by heating the oil to lower its viscosity under 75 cSt. 5 cSt - Rated speed = 2850 rpm
For kerosene applications, contact SUNTEC)
Data shown are for new pumps, with no allowance for wear.
Oil temperature 0 - 150°C in the pump
Inlet pressure light oil : 0,45 bars max. vacuum to prevent Power consumption
air separation from oil Power (W)
heavy oil : 5 bars max. 6000
Rated speed 3600 rpm max. 5500 T5
Torque (@ 40 rpm) 0,4 N.m 5000 T4
4500
4000 T3
Choice of heater T5
3500 T4
3000 T2
Cartridge Ø 12 mm T3
2500
Fitting according to EN 50262 2000
T2
Rating 80-100 W 1500
1000
500
0
0 5 10 15 20 25 30 35 40 45
Pressure (bars)
Viscosity = 75 cSt
5 cSt - Rated speed = 2850 rpm
Data shown are for new pumps, with no allowance for wear.
PUMP DIMENSIONS Example shows "A" rotation - Reverse all pump connections for "C" rotation.
T2 T3 T4 T5 150
A 68 132
(mm) 68 73 78 87 19 19
33 p q
B
n o
Ø70 Ø11
B 132
Ø19 min
85 M16x1,5
r 22,5
1,5 max
8 min
12 min Ø12,1 min Ø11
Ø20 71,5 min
36 A 90
B-B
n Suction o Pressure outlet and p Vacuum or
q Pressure
r Preheater
internal by-pass plug inlet pressure gauge port gauge port cavity
We reserve the right to change specifications without prior notice. T - 11 - Ed 11 - May 2007