MCC Panel Dismantling Procedure

MEASUREMENTS 1. Insulation resistance of supply circuits: - Phase - mass (MΩ) - Phase - phase (MΩ) 2. Insulation resistance of secondary circuits (MΩ) 3. Phasing of voltage circuits 4. Polarity of DC circuits 5. Verification of current flows 6. Local and remote command checks 7. Local and remote signaling checks 8. Lighting circuits inside the cabinet 9. Heating circuits inside the cabinet 10. Earthing circuits CONCLUSIONS: The command panel - control / protection is: [ ] Accepted for commission

Uploaded by

AlinaIordache
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views6 pages

MCC Panel Dismantling Procedure

MEASUREMENTS 1. Insulation resistance of supply circuits: - Phase - mass (MΩ) - Phase - phase (MΩ) 2. Insulation resistance of secondary circuits (MΩ) 3. Phasing of voltage circuits 4. Polarity of DC circuits 5. Verification of current flows 6. Local and remote command checks 7. Local and remote signaling checks 8. Lighting circuits inside the cabinet 9. Heating circuits inside the cabinet 10. Earthing circuits CONCLUSIONS: The command panel - control / protection is: [ ] Accepted for commission

Uploaded by

AlinaIordache
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Approval

Project manager

0 November ‘17 Initially Dan Pîrvulescu Florinel Petrilă Gheorghe Ţăranu


NO. DOCUMENT
REV. DATE DESIGNED CHECKED APPROVED
DESCRIPTION
Revision Sheet
CUSTOMER:
MINISTRY OF ELECTRICITY (MOE)
REPUBLIC OF IRAQ
PROJECT :
IFB no. M21-21-2016
Rehabilitation of Unit 3
Facilities and Common System, Al Mussaib Thermal Power Plant Rehabilitation

CONTRACTOR:

BLACK SEA TECHNOCHIM CO SRL

DESIGNED BY DATE

Dan Pîrvulescu November ‘17

CHECKED BY DATE TITLE:


THE PROCEDURE FOR DISMANTLING OLD MCC PANELS
Florinel Petrilă November ‘17 AND MOUNTING NEW MCC PANEL
APPROVED BY DATE

Gheorghe Ţăranu November ‘17

Contract No. DOCUMENT NUMBER REV.NO.

IFB no. M-21-2016 XXXXXXXXX 0


TABLE OF CONTENTS
1. SCOPE .................................................................................................................. 3
2. DOMAIN ................................................................................................................ 3
3. TERMS, DEFINITIONS AND ABBREVIATIONS................................................. 3
4. REFERENCE DOCUMENTS................................................................................ 3
5. RESPONSIBILITIES ............................................................................................. 3
6. PROCEDURE ....................................................................................................... 4
6.1 Preparatory operations ............................................................................................... 4
6.2 Making measurements ................................................................................................ 4
6.3 Command-control cabinets test ................................................................................. 4
6.4 Checking Projection Cabinets .................................................................................... 4
7. ACCEPTANCE CRITERIA ................................................................................... 5
8. REPORTS AND REGISTERS .............................................................................. 5

2|5
1. SCOPE
This procedure establishes checks and verification methods that are performed on cabinets
and electrical panels.

2. DOMAIN
This procedure applies to checks and tests of control cabinets and control panels and
protection.

3. TERMS, DEFINITIONS AND ABBREVIATIONS


According to MC-PRAM-ELC

4. REFERENCE DOCUMENTS

At the latest applicable revision

Document type Documents


International 4.1 ISO 9001:2015 – Quality management systems. Requirements.
Standards 4.2 ISO 14001:2015 – Environment management systems. Requirements with
user guide.
4.3 OHSAS 18001:2007 - OH&S Management Systems. Requirements.
4.4 ISO / TR 10013:2006 - Guidelines for quality management system‘s
documentation.
4.5 Purchase contract.

NOTE: The user’s responsibility is to ensure that it is using the valid editions of the
documents, by reading the reference list of the documents.

5. RESPONSIBILITIES
Position / Competence
5.1. PRAM laboratory supervisor
5.1.1. Shall ensure that electrical checks are carried out by qualified, authorized and trained personnel
for the specifics of these works.
5.1.2. Shall ensure the equipping of PRAM teams with the necessary equipment and devices as well
as with metrological measuring devices.
5.1.3. Check and approve Electric Checks Records.
5.2. PRAM team supervisor
5.2.1. Instructs PRAM members to work under the Specific Safety and Health Regulations applicable to
the work and the project and operations to be performed.
5.2.2. Prepare a Work Authorization where necessary, coordinate and supervise a team member for
the duration of the work.
5.2.3. Draw Verification Records with Measurement Results
5.3 PRAM personnel
5.3.1. It appropriates and complies with the provisions of this procedure.
3|5
5.3.2. Perform measurements in accordance with the Specific Wiring Instructions, applicable Norms
and Specific Instruction Guidelines.
5.3.3. He / she understands and complies with the Specific Work Safety and PSI Norms applicable to
the work.
5.3.4. Uses metrology devices only.

6. PROCEDURE
6.1 Preparatory operations
6.1.1. Preparation of appliances, devices, cords, sources of power required for Checks at
the established Cabinets / Panels.
6.1.2. Identify and isolate the work area.
6.1.3. Dust or dirt cleaning of electrical components as well as cable clamps.
6.1.4. Determining the order execution of the measurements.

6.2 Making measurements


6.2.1. The types of measurements required depend on the type and destination of cabinets
or paintings. When performing the measurements, the requirements of the Equipment Factory
Instructions and then those set out in PE 116/94 shall be met first.

6.3 Command-control cabinets test


6.3.1. On the control cabinets / panels the following measurements and checks are made:
a) Measurement of the insulation resistance of the AC and / or DC supply circuits is
done with a 500 V megohmmeter (at least) on each phase with respect to the
mass, as well as between the phases;
b) The insulation resistance of the secondary circuits is measured with the 1000 V
megohmmeter and the minimum value at the PIF must be 5 MΩ;
c) Checking the phasing of the voltage circuits is done with a phasmerer and it is
observed that the phases are in a correct sequence (R, S, T) in accordance with
the source from where they leave;
d) Check the polarity of the DC circuits with a DC tester, checking that they are not
reversed (+) with (-);
e) Verification of current flows is done with a Ditz Pliers. by priming or secondary
current injection and measuring each current circuit in the Panel;
f) Local and remote command checks are made with operative voltage fed by
preference from an independent, temporary source;
g) Check local and remote signaling is done simultaneously with order verification;
h) Checking the lighting circuits inside the cabinet is done with a voltage tester for
the socket and lamp;
i) Checking the heating circuits refers to the operation of the heating resistance of
the cabinet as well as the thermostat;
j) Verification of earthing circuits refers to checking the continuity at the ground in all
the metal parts of the cabinet.

6.4 Checking Projection Cabinets


6.4.1. Protective cabinets are subject to the following checks:
a) Measurement of insulation resistance of supply circuits, ca. and / or c.c. is done
as in command-control cabinets;

4|5
b) Measuring the polarity of the operational current circuits is done as in control-
command cabinets;
c) Verification of current flows is done as in command-control cabinets;
d) Checking the protection circuits is done only by identifying the threads with a
tester;
e) Checking the protection relays is only done by an authorized company that has
the necessary verification equipment; Their verification bulletins are valid for PIF;
f) Verification of the lighting and heating cabinet, as well as control-cabinets;
g) Verification of earthing circuits is done as in control-cabinets.

7. ACCEPTANCE CRITERIA
7.1. The measured values will be passed to the Testing Bulletins by the Team Set, which
will then be forwarded to the Head of the PRAM Laboratory.
7.2. The head of the PRAM Laboratory will compare the measured values with the
reference values and establish the conclusion in Verification Report (V.R.) if the cable can be
energized.

8. REPORTS AND REGISTERS


8.1. Verification Checklist command-control / protection panel - FORM-ELC-057.

5|5
COMMAND PANEL - CONTROL / PROTECTION Page
VERIFICATION REPORT
from
No. Date

NOMINAL DATA
Cabinet Serial Manufacturing year Manufacturer U
T y pe Number N
(
k
V
The results were obtained at ambient temperature …………. ℃ and humidity ………….. %. )

1. MEASUREMENT OF ELECTRICAL PARAMETERS


Insulation Resistance
Circuits Insulation Resistance Enhanced voltage test Insulation
M𝛀) ( kV) (min) Resistance after V>

Power Supply
Secondary Circuit

2. FUNCTIONAL TESTS
Cr. Tests Conclusions Remarks
No.

1 Identification of circuits
2 Phase power circuits
3 Polarity current circuits
4 Circulation current
5 Local and remote command
6 Local and remote signaling
7 Heating panels in the cabinet
8 Indoor lighting circuits
9 Grounding circuits

3. FUNCTIONAL TESTS
Cr. Name Type Serial Precisio No. Valid until
No. number n class Verification Report date:
1
2
3

CONCLUSIONS: From the point of view of the tests carried out according to the Norm PE 116/94,
The verified cable does not / correspond and cannot / be energized.

EXECUTING WORK VERIFIED


NAME:
SIGNATURE:
DATE:

FORM-ELC-057, revision 1