Manual de Servicio PS 0500 PDF
Manual de Servicio PS 0500 PDF
Generator Set
X1.3 & X2.5 Engine with PowerStart 0500 Control
C8D5
C11D5
C17D5
C17D5 (Spec E)
C22D5
C22D5 (Spec E)
C28D5
C28D5 (Spec E)
C12D6
C12D6 (Spec E)
C16D6
C16D6 (Spec E)
C20D6
C20D6 (Spec E)
English
Original Instructions 08-2017 A029U889 (Issue 3)
PowerStart 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Table of Contents
SECTION TITLE PAGE
1 IMPORTANT SAFETY INSTRUCTIONS 5
2 INTRODUCTION 7
3.1 General 8
4 CIRCUIT BOARD 19
5 TROUBLESHOOTING 24
8 WITHDRAWING ROTOR 49
page 3
PowerStart 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 4
PowerStart 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Before operating the generator set (genset), read the • Provide an adequate exhaust system to properly
Operator’s Manual and become familiar with it and the expel discharged gases away from enclosed or
equipment. Safe and efficient operation can be sheltered areas and areas where individuals are
achieved only if the equipment is properly operated likely to congregate. Visually and audibly inspect
and maintained. Many accidents are caused by failure the exhaust daily for leaks per the maintenance
to follow fundamental rules and precautions. schedule. Make sure that exhaust manifolds are
secured and not warped. Do not use exhaust
The following symbols, found throughout this manual, gases to heat a compartment.
alert you to potentially dangerous conditions to the • Be sure the unit is well ventilated.
operator, service personnel, or the equipment. • Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
DANGER birth defects, and other reproductive harm.
This symbol warns of
immediate hazards which will result in MOVING PARTS CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH
severe personal injury or death.
• Keep your hands, clothing, and jewelry away from
WARNING moving parts.
This symbol refers to a • Before starting work on the generator set,
hazard or unsafe practice which can disconnect battery charger from its AC source,
result in severe personal injury or death. then disconnect starting batteries, negative (–)
cable first. This will prevent accidental starting.
CAUTION This symbol refers to a • Make sure that fasteners on the generator set are
hazard or unsafe practice which can secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
result in personal injury or product or
• Do not wear loose clothing or jewelry in the vicinity
property damage. of moving parts, or while working on electrical
FUEL AND FUMES ARE FLAMMABLE equipment. Loose clothing and jewelry can
become caught in moving parts.
Fire, explosion, and personal injury or death can result • If adjustment must be made while the unit is
from improper practices. running, use extreme caution around hot
manifolds, moving parts, etc.
• DO NOT fill fuel tanks while engine is running, DO NOT OPERATE INFLAMMABLE AND
unless tanks are outside the engine compartment. EXPLOSIVE ENVIRONMENTS.
Fuel contact with hot engine or exhaust is a
potential fire hazard. Flammable vapor can cause an engine to overspeed
• DO NOT permit any flame, cigarette, pilot light, and become difficult to stop, resulting in possible fire,
spark, arcing equipment, or other ignition source explosion, severe personal injury and death. Do not
near the generator set or fuel tank. operate a genset where a flammable vapor
• Fuel lines must be adequately secured and free of environment can be created by fuel spill, leak, etc.,
leaks. Fuel connection at the engine should be unless the genset is equipped with an automatic
made with an approved flexible line. Do not use safety device to block the air intake and stop the
zinc coated or copper fuel lines with diesel fuel engine. The owners and operators of the genset are
• Be sure all fuel supplies have a positive shutoff solely responsible for operating the genset safely.
valve. Contact your authorized Cummins Inc.
• Be sure battery area has been well-ventilated prior distributor for more information.
to servicing near it. Lead-acid batteries emit a
page 5
PowerStart 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
ELECTRICAL SHOCK CAN CAUSE SEVERE • Keep multi-class ABC fire extinguishers
PERSONAL INJURY OR DEATH handy. Class A fires involve ordinary
combustible materials such as wood and
• Remove electric power before removing cloth; Class B fires, combustible and
protective shields or touching electrical flammable liquid fuels and gaseous fuels;
equipment. Use rubber insulative mats placed Class C fires, live electrical equipment. (ref.
on dry wood platforms over floors that are metal NFPA No. 10).
or concrete when around electrical equipment. • Make sure that rags are not left on or near
Do not wear damp clothing (particularly wet the generator set.
shoes) or allow skin surface to be damp when
handling electrical equipment. Do not wear • Make sure generator set is mounted in a
jewelry. Jewelry can short out electrical contacts manner to prevent combustible materials
and cause shock or burning. from accumulating under or near the unit.
• Use extreme caution when working on electrical
components. High voltages can cause injury or • Remove all unnecessary grease and oil from
death. DO NOT tamper with interlocks. the unit. Accumulated grease and oil can
• Follow all applicable state and local electrical cause over-heating and engine damage
codes. Have all electrical installations performed which present a potential fire hazard.
by a qualified licensed electrician. Tag and lock
open switches to avoid accidental closure. • Keep the generator set and the surrounding
• DO NOT CONNECT GENERATOR SET DI- area clean and free from obstructions.
RECTLY TO ANY BUILDING ELECTRICAL Remove any debris from the set and keep
SYSTEM. Hazardous voltages can flow from the the floor clean and dry.
generator set into the utility line. This creates a
potential for electrocution or property damage. • Do not work on this equipment when
Connect only through an approved isolation mentally or physically fatigued, or after
switch or an approved paralleling device. consuming any alcohol or drug that makes
the operation of equipment unsafe.
GENERAL SAFETY PRECAUTIONS • Substances in exhaust gases have been
identified by some state or federal agencies
• Coolants sunder pressure have a higher boiling as causing cancer or reproductive toxicity.
point than water. DO NOT open a radiator or Take care not to breath or ingest or come
heat ex-changer pressure cap while the engine into contact with exhaust gases.
is running. To prevent severe scalding, let
engine cool down before removing coolant • Do not store any flammable liquids, such as
pressure cap. Turn cap slowly, and do not open fuel, cleaners, oil, etc., near the generator
it fully until the pressure has been relieved. set. A fire or explosion could result.
• Used engine oils have been identified by some • Wear hearing protection when going near an
state or federal agencies as causing cancer or operating generator set.
reproductive toxicity. When checking or
changing engine oil, take care not to ingest, • To prevent serious burns, avoid contact with
breathe the fumes, or con-tact used oil. hot metal parts such as radiator system,
turbo charger system and exhaust system.
page 6
Publication A029U889
Power Start 0500 Issue 3 - 8-2017
X1.3 & X2.5 Engine
SECTION 2 – INTRODUCTION
2.1 ABOUT THIS MANUAL
This manual provides troubleshooting and repair display panel. It accepts menu-driven control and
information regarding the PowerCommand® set-up input from the push button switches on the
1302Control (PCC) and generators for the front panel.
generator sets (gensets) listed on the front cover.
Engine service instructions are in the applicable 2.3 TEST EQUIPMENT
engine service manual. Operating and maintenance
instructions are in the applicable Operator’s To perform the test procedures in this manual, the
Manual. following test equipment must be available
True RMS meter for accurate measurement of
This manual does not have instructions for small AC and DC voltages. Fluke models 87 or
servicing printed circuit board assemblies. After 8060A are good choices.
determining that a printed circuit board assembly is Grounding wrist strap to prevent circuit board
faulty, replace it, do not repair it. Attempts to repair damage due to electrostatic discharge (ESD).
a printed circuit board can lead to costly damage to Battery Hydrometer.
the equipment. Jumper Leads.
Tachometer or Frequency Meter.
This manual contains basic (generic) wiring Wheatstone Bridge or Digital Ohmmeter.
diagrams and schematics that are included to help Variac.
in troubleshooting. Service personnel must use the Load Test Panel.
actual wiring diagram and schematic shipped with Megger or Insulation Resistance Meter.
each unit. The wiring diagrams and schematics that InPower™ Service Tool (PC based genset
are maintained with the unit should be updated service tool).
when modifications are made to the unit. PCC1302 Interface Kit (Used with InPower
Service Tool)
Read Important Safety Instructions and carefully
observe all instructions and precautions in this 2.4 HOW TO OBTAIN SERVICE
manual.
Always give the complete Model, Specification and
2.2 SYSTEM OVERVIEW Serial number of the generator set as shown on the
nameplate when seeking additional service
The PCC is a microprocessor-based control information or replacement parts. The nameplate is
for Cummins Inc. generator sets. All generator located on the front of the control panel.
set control functions are contained on one
circuit board (Base board). The Base board
provides fuel control, main alternator voltage WARNING Incorrect service or
output regulation and complete generator set replacement of parts can result in severe
control and monitoring. personal injury or death, and/or equipment
The operating software provides control of the damage. Service personnel must be trained and
generator set and its performance characteristics, experienced to perform electrical and
and displays performance information on a digital mechanical service. Read and follow Important
Safety Instructions on pages iii and iv.
page 7
PowerStart 0500 Publication A029U889
Issue 3 - 8-2017
X1.3 & X2.5 Engine
3.1 GENERAL
Note: Other devices that can remotely start / Stop
The PS0500 is a microprocessor-based controller the genset might be as simple as a switch or a push
that has these abilities. button or as sophisticated as other controllers or
• Start and stop the genset. computers. This manual introduces the ways the
• Monitor the status of the genset. Control can interact with other devices, but this
manual cannot identify all of the devices that might
• Warn the operator when unsafe conditions
be used in every application.
are occurring
• Shut down the genset to prevent damage
• Adjust settings that affect genset behavior.
• Provide a way for other devices to remotely
start / Stop the genset
page 8
Publication A029U889
Power Start 0500
Issue 3 - 8-2017
X1.3 & X2.5 Engine
The battery provides power for the PS0500 and the The PS0500 may be connected to a push button
PS0500 monitors the battery voltage. that shuts the genset down immediately when
pressed.
Starter
The PS0500 is connected to the starter control relay
in order to control the starter.
page 9
PowerStart 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Remote Start
The PS0500 may be connected to a device that can
generate a remote start signal. Typically, the device is a
transfer switch.
page 10
Publication A029U889
Power Start 0500
Issue 3 - 8-2017
X1.3 & X2.5 Engine
Safety Considerations
page 11
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 12
Publication A029U889
Power Start 0500
Issue 3 - 8-2017
X1.3 & X2.5 Engine
page 13
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
3.5 MODES OF OPERATION Pressing the Stop button shall always deactivate the FSO
immediately.
The mode of operation determines the ways the
Genset can be started and stopped. The PS0500 runs in Remote Start Signal
one of these modes at any given time.Table 2-3 explains
how to change the mode of operation. This signal will start the Genset when these conditions are
met.
Stop (Off) Mode • The PS0500 is in Auto mode
• There are no active shutdown faults
Pressing the STOP button will always put the PS0500 in
STOP mode and the RED LED above the STOP button will This signal comes typically from a transfer switch or an
start blinking. external toggle switch.
In this mode, the PS0500 does not allow the genset to start Manual Mode
/ Crank.
Pressing the Manual Button while the PS0500 is in the Stop
If the genset is running (either in Manual or Auto Mode) Mode will put the PS0500 in the Manual Mode.
when the Stop button is pressed, the PS0500 stops the
genset and enters in the STOP mode. In this mode, the genset is controlled manually. Pressing
the Start button initiates a Manual Start sequence. Remote
Setup Mode start signal has no effect.
The Setup mode can be entered only from Stop mode when Note: If you do not press the Start button in ten seconds,
the genset is not running. This is accomplished by holding the PS0500 changes over to STOP (Off) mode.
the Reset and the OK buttons pressed for 5 seconds
continuously while in stop mode. The RED Stop Led flashes Pressing the Stop button initiates a stop sequence.
faster (double the normal rate) as long as the control is in
setup mode. While in setup mode, pressing Start or Stop
button has no effect. Exiting from setup mode will return the
control to STOP mode.
Auto Mode
Pressing the Auto Button while the PS0500 is in the STOP
mode will put the PS0500 in AUTO Mode. Pressing Auto
Button while the PS0500 is in Manual Mode (Running or
Not Running) has no effect.
page 14
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Table 2-4 shows how much current the PS0500 control Stopped
module consumes in normal operation and in power-down
mode.
page 15
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Cycle Cranking
OR
FIGURE 3-7. Remote Start Sequence The PS0500 waits for the Genset to reach the rated
frequency and voltage. If that does not happen within 10
In this sequence, the PS0500 follows these steps to start seconds from the starter disconnect, the PS0500
the engine. generates Shutdown Fault 2335 (loss of AC Sensing).
1. The PS0500 waits until Start Time Delay expires.
If the trim Glow Plug Enable is set to Enabled, the Manual Start
PS0500 turns on the Glow Plug Control output. The
PS0500 turns off the Glow Plug Output when Glow Plug This sequence begins when these conditions are
Timeout Period expires. met.
The PS0500 does not proceed to crank until both Start
• The PS0500 is in Manual mode and the Start
Time Delay expires and the Glow Plug Output is turned button is pressed.
off. • There are no active shutdown faults.
2. The PS0500 turns on the fuel shutoff (FSO) output This sequence is shown in Figure 3-8. There are no
and the Starter Output. active shutdown faults.
.
page 16
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Meter Calibration
When running in Manual Mode, the control allows meter
calibration process to be invoked, when the Genset
Running (Ready to Load) state is reached. The Meter
Calibration process is invoked by holding the Reset and
OK buttons pressed for 5 seconds continuously. The
process allows the arrow keys to be used for adjusting
the displayed alternator AC Voltage / Current values to
actual values (as measured using an independent
calibrated instrument) one by one.
Stop Sequences
FIGURE 3-8. Manual Start Sequence
The PS0500 follows different stop sequences depending
on its setup and conditions.
In this sequence, the PS0500 follows these steps to start
the engine.
Auto Mode
1. If the trim Glow Plug Enable is set to Enabled, the
In Auto mode the stop sequence begins when these
PS0500 turns on the Glow Plug Control output. The
conditions are met.
PS0500 turns off the Glow Plug Output when Glow Plug
− The genset is running at rated speed and voltage
Timeout Period expires.
− The remote start signal is inactive.
The PS0500 does not proceed to crank until the Glow
Plug Output is turned off. The Genset will continue to run for the Stop Delay time
and then the FSO Output will be deactivated by the
2. The PS0500 turns ON the fuel shutoff (FSO) output PS0500.
and the Starter Output.
Manual Mode
The cycle cranking process as explained above is
followed in Manual Mode also. In Manual mode the stop sequence begins when these
conditions are met.
Genset Running (Ready to Load) − The genset is running at rated speed and voltage
− The Stop button has been pressed.
The PS0500 enters the Genset Running (Ready to − There are no active shutdown faults.
Load) state when the genset frequency and voltage are
both >= 90 percent of the nominal frequency and The FSO Output will be deactivated by the PS0500
nominal voltage respectively. immediately when the Stop button is pressed.
page 17
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Fault Shutdown
page 18
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
J12 – CT connector
Arrow at Pin 1
J12 –Pin 4
J16 –Pin 7
TB2 – Customer TB
Arrow at Pin 1
page 19
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
J22
Alternator Voltage J16 Engine Connections
Sense inputs and • • Coolant Sensor, Lube Oil
Field Output Pressure sensor, Run / OFF /
Auto Switch, FSO, Starter,
Battery, Mag Pick Up, Starter
PS0500 Disconnect Feed Back,
CONTROL BOARD Battery Charger D+, Chassis
• GND. Governor PWM
•
page 20
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Engine Connector
The engine connector (J16) is a 12 pin connector-plug (12 MINI M-N-L). A possible supplier is
Molex; their part number is 39299123. The Cummins part number for this connector is 0323-2589. The PCB outline
drawing shows where the connector is located as above .Each signal is described as below –
CT Connector
The CT connector is a 6- pin MATE-N-LOCK connector. The possible manufacturer is Tyco, and the supplier part
number for the part is 643749-1. The Cummins part number for this connector is 0323-2154. Connector details are as
follows –
page 21
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Voltage Connector
The voltage connection is via a 4 pin header with alternate spaces between the pins. The possible supplier is Tyco
with the supplier part number as 282828-4. The Cummins part number for the same is 0323-2225-03.
The customer connection TB2 is a 6 pin terminal block. The possible supplier is Magnum:
The terminal pins details are as shown below-
All the inputs are active GND. And outputs are low side drivers. Remote E-Stop switch should have two independent
potential free contacts. One NC contact for cutting out the Battery supply to the Fuel Solenoid and another NC contact
to disconnect controller’s E-Stop input from GND to indicate to the control when the E-Stop is pushed in active state.
Battery Positive is not provided on the Customer terminal block (TB2). External provision needs to be made in the
harness to provide fused B+ via a 1 amp fuse for wiring up external relays. External Relays of suitable contact ratings
must be used for controlling FSO, Starter, Customer Output and Glow plug.
PC Tool Connector
The PC tool connector is a dedicated 5 pin connector header block. The possible supplier is Tyco, with the supplier
part numbers are 796643-5. The Cummins part number for the same is 0323-2191-04.
page 22
Power Start 0500 Publication A029U889
Issue 3 - 8-2017
Connector Part
Numbers
Manufacturer’s Cummins
Quantity Name Description Manufacturer Remarks
part number part no
Alt Voltage
1 J22 TYCO 282828-4 0323-2225-03
Connector
Engine
1 J16 MOLEX 39299123 0323-2589
Connector
Tool
1 TB15 TYCO 796643-5 0323-2191-04 All these
Connector
connectors
Alt Voltage are PCB
1 J22 TYCO 282809-4 0323-2226-03
Connector mounted
connectors
CT Connector 1-480704-0 0323-1932
1 J12 Crimp TYCO
350551-1 0323-1200
Terminals
Engine
39012120 0323-2602
Connector
1 J16 MOLEX
Crimp
39000038 0323-2603
terminals
page 23
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
SECTION 5 - TROUBLESHOOTING
ON or OFF near battery. Discharge static electricity
General from body before touching batteries by first
touching a grounded metal surface.
The PS0500 control continuously monitors engine
sensors for abnormal conditions, such as low oil Ventilate battery area before working on or near
pressure and high coolant temperature. If any of these battery—Wear goggles—Stop genset and
conditions occur, the control will light a yellow warning disconnect charger before disconnecting battery
lamp or a red shutdown lamp and display a message on cables—Disconnect negative (-) cable first and
the LCD display. reconnect last.
When used improperly, a PC based service tool can The fault code and message can be viewed on the
cause symptoms like warnings and shutdowns that display. After the fault is acknowledged and corrected,
appear to be a defective control. When these problems the recorded fault will be deleted from the control panel
occur, always verify that a self-test or fault simulation memory, but will remain in a data log to maintain a fault
(override) have not been left enabled with the tool. If you code history. A PC based service tool is required to view
do not have a PC based service tool, or the enabled fault this data log.
simulation(s) can not be found using the tool, disconnect
battery power to disable the test or override condition.
5.2 TROUBLESHOOTING PROCEDURE
Make sure that parameter adjustments and time delays,
related to the fault condition, have been appropriately set The following tables are a guide to help you evaluate
for the application. It may be necessary to write the initial problems with the generator set. You can save time if
capture file to the device or update the calibration file. you read through the manual ahead of time and
Updating a calibration file requires a Pro version of many understand the system.
of PC based service tools. Confirm that the installed
calibration part number matches the serial plate
Voltage/Continuity Testing
information.
Voltage and continuity tests are required in the following
CAUTION tables. In some cases, it is necessary to remove a plug
Using the wrong capture file can
to complete the test. Where required, the corrective
result in equipment damage. Do not swap Controls
action will mention when it is necessary to remove a plug
from another genset model and only use the
for testing. In other cases, the plug cannot be removed
calibration file shown on the nameplate.
for testing. When plug removal is not mentioned, testing
must be performed by inserting a narrow meter probe
into the back of the plug.
5.1 SAFETY CONSIDERATIONS
page 24
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
TABLE 20-1. ENGINE DOES NOT CRANK IN TABLE 20-2. ENGINE DOES NOT CRANK IN
MANUAL MODE REMOTE MODE
Reason: This indicates that the PS0500 control has not
Reason: This indicates that the control has not received received or recognized a remote start signal.
or recognized a manual start signal. Effect: Engine will not start in remote mode, but starts in
Effect: Engine will not start. manual mode.
POSSIBLE CORRECTIVE ACTION POSSIBLE CORRECTIVE ACTION
CAUSE CAUSE
1. No power Check if the control is in Manual 1. The remote Check if the control is in Auto mode
supplied to mode and when the Start button is start switch or and there are no shutdown faults
control pressed, and that there are no wiring is faulty. present. Attempt to start, and check
shutdown faults present. for ground at TB2-1.
If ground level is not present, isolate
Poor battery cable connections. Clean to the remote switch or wiring. Repair
the battery cable terminals and as necessary.
tighten all connections.
If ground level is present then the
Check for blown fuses. control is bad. Replace the control
page 25
Power Start 0500
X1.3 & X2.5 Engine Publication A029U889
Issue 3 - 8-2017
page 26
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 27
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 28
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
service tool, remove battery power CODE 1448 - UNDER FREQUENCY (SHUTDOWN)
from the control to disable fault Reason: Generator AC output frequency is low.
simulation overrides. Effect: Generator set will shut down.
2. Fault threshold is 2. Reset the threshold to the POSSIBLE CORRECTIVE ACTION
not set correctly lowest allowable setting. CAUSE
with Determine the required operating 1. Fault 2. Reset the threshold to the lowest
a PC based service range before adjusting the threshold is not allowable setting. Determine the
tool. threshold. set correctly required operating range before
3. Overload. 3. Check the load and correct any with adjusting the threshold.
overload. Check operation by PC based
disconnecting load and restarting service tool.
generator set. 2. Overload. 3. Check the load and correct any
4. Improper 4. Reconnect according to the overload. Check operation by
connections have appropriate reconnection diagram. disconnecting load and restarting
been made at the See Section 17. generator set.
generator output 3. Fuel or air 4. Refer to the engine service manual.
terminals. delivery
5. Voltage sense or 5. Check that Voltage senses problem.
setup wiring inputs P22-1 to 4 are connected to 4. Governor 5. Check fuel shutoff solenoid
connection could the correct voltage sensing point fault. adjustment (refer to Section 8).
be incorrect. at alternator. 5. Loose 6. Repair connections (P22 – 1 to 4)
6. The rotating 6. Check each diode. See genset connector or or replace the Control if necessary.
rectifier assembly service manual Control is bad.
(diodes CR1
through CR6) is CODE 234 - OVERSPEED (SHUTDOWN)
faulty. Reason: Engine speed signal indicates an engine speed
7. Loose connector 8. Repair connections (P22) or greater than shutdown threshold.
or Control is bad. replace the Control if necessary. Effect: Engine will shut down.
POSSIBLE CORRECTIVE ACTION
8. AVR or 4. Refer to Alternator / AVR Board CAUSE
Alternator is bad. Isolation Procedure in Alternator 1. Cold engine 1. Overspeed can occur when starting
manual to determine if the AVR (no coolant a very cold engine. Clear fault and
board is causing the Low AC heaters) restart genset.
voltage shutdown fault.
9. Voltage sense See section 17 for proper 2. Single step 2. Clear fault and restart genset.
connections/setup connections large block load
could be incorrect removal.
3. Fault 3. With PC based service tool, verify
CODE 1449 - OVER FREQUENCY (SHUTDOWN) simulation was that the fault simulation is not enabled
Reason: Generator AC output frequency is high. enabled with a for the coolant sensor.
Effect: Generator set will shut down. PC based If you do not have PC based service
POSSIBLE CORRECTIVE ACTION service tool. tool, remove battery power from the
CAUSE control to disable fault simulation
1. Fault 2. Reset the threshold to the highest overrides.
threshold is not allowable setting. Determine the 4. Fault 4. Reset the threshold to the highest
set correctly required operating range before threshold is not allowable setting. Determine the
with adjusting the threshold. set correctly required operating range before
PC based with adjusting the threshold.
service tool. PC based
2. Fuel or air 3. Refer to the engine service manual. service tool.
delivery
problem. 5. Monitor the 5. If the RPM is not correct, refer to
3. Loose 4. Repair connections (P22 – 1 to 4) engine rpm fault code 1449 for corrective action.
connector or or replace the Control if necessary. using InPower.
Control is bad.
page 29
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 30
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 31
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
CODE 144 - COOLANT SENSOR OOR (HIGH/LOW) 3. Battery 3. Clean and tighten or replace the
(WARNING) connections battery cable connectors and cables
Reason: This indicates that the coolant temperature loose or dirty. at the battery and the set.
sensor signal is out of range - shorted high or low. 4. Insufficient 4. Adjust charge rate of AC powered
Effect: No engine protection for coolant temperature battery charging battery charging circuit, according to
during genset operation. Possible white smoke. voltage. manufactures instructions.
POSSIBLE CORRECTIVE ACTION 5. Engine DC 5. Replace engine DC alternator if
CAUSE alternator could normal battery charging voltage (12
1. The sensor 2. Inspect the sensor and engine be bad. to 14 VDC) is not obtained.
connections harness connector pins. Repair or
could be bad. replace as necessary. 6. If the 6. Remove connector P16 from
2. The sensor 3. Disconnect the sensor, and plug in batteries are Control and check battery voltage at
could be bad. a resistive sensor simulator to isolate OK, the problem P16-12 (B+) to P16-5 (GND).
the fault. may be the • If the voltage at P16 is not the
If the control responds to the harness or the same as the battery voltage, the
simulator, replace the sensor. If Control. harness is bad.
control does not respond, go to next If the voltage at P16 is OK, the
step. Control is bad.
3. The harness 4a. Remove connector P16 from 7. Fault 7. Check fault threshold against
or Control could Control and disconnect sensor. threshold could requirement of the application.
be bad. Check pins P16-1 and P16-11 be bad.
(Sensor common) for short circuit as
follows:
• Check for a short circuit to the CODE 442 - HIGH BATTERY VOLTAGE (WARNING)
engine block ground (more than Reason: High voltage has been detected for battery.
200k ohms OK). Effect: Control damage will occur.
Check for a short circuit from pin POSSIBLE CORRECTIVE ACTION
to pin (more than 200k ohms CAUSE
OK).Repair or replace as 1. Excessive 1. Adjust charge rate of AC powered
necessary. battery charging battery charging circuit according to
4b. Measure the resistance of the voltage. manufacturers instructions.
coolant sensor and reconnect 2. Engine DC 2. Replace engine DC alternator if
harness to sensor. Remove alternator could normal battery charging voltage
connector P16 from Control and be bad. (12 to 14 VDC) is not obtained.
check resistance between pins P16-1 3. Fault 3. Check fault threshold against
and P16-11 (Sensor Common). threshold could requirement of the application.
• If resistance is not the same, be bad.
harness is bad. CODE 143 - LOW OIL PRESSURE (WARNING)
• If resistance is the same, Control Reason:
is bad. Effect:
POSSIBLE CAUSE CORRECTIVE ACTION
1. Refer to code 415. 1. Refer to code 415.
CODE 441 - LOW BATTERY (WARNING) CODE 141 - OIL PRESSURE SENSOR OOR
Reason: Low voltage has been detected for battery. (HIGH/LOW) (WARNING)
Effect: The control’s voltage supply approaching level at Reason: This indicates that the engine oil pressure
which unpredictable operation may occur. sensor signal is out of range - shorted high or low.
POSSIBLE CORRECTIVE ACTION Effect: No engine protection for oil pressure during
CAUSE genset operation.
1. Weak or 1. Recharge or replace the battery. POSSIBLE CORRECTIVE ACTION
discharged Specific gravity for a fully charged CAUSE
battery. battery is approximately 1.260 at 80F 1. The sensor 2. Inspect the sensor and engine
(27C). connections harness connector pins. Repair or
2. Low 2. Replenish electrolyte and recharge could be bad. replace as necessary.
electrolyte level battery.
in battery. 2. The sensor 3. Disconnect the oil pressure sensor
page 32
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
could be bad. leads, and connect an oil pressure could be bad. check pressure signal (.500 to .033
sensor simulator to the harness. VDC) at P16-9 and P16-11 (Sensor
Common). If in range, replace
“OIL PRESSURE SENSOR OOR” Control.
warning is displayed after the fault CODE 1442 - WEAK BATTERY (WARNING)
condition is sensed for 10 Reason:
seconds. Effect:
POSSIBLE CORRECTIVE ACTION
If the control responds to the CAUSE
simulator, replace the sensor. If 1. Refer to code 1. Refer to code 441.
control does not respond, go to next 441
step.
3. The harness 4. Remove connector P7 from Control
could be bad. and connector from sensor.
Check P16-9 and P16-11 as follows:
• Check for a short circuit from pin
to pin (more than 200k ohms OK).
• Check for an open circuit (10
ohms or less OK).
Repair or replace as necessary.
4. The Control 5. With all connectors attached,
page 33
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
CAUTION Only qualified technicians should adjust the parameters described in this section. Failure
to follow this may affect genset operation and may cause damage to the genset or to equipment connected to
the genset.
Parameters
See Section 4 for more information about parameters that you can adjust in the Operator Panel.
Capture File
Use InPower to save the current settings in a capture file on a PC or network. You can use the capture file to look at
the current settings while you are away from the PS0500 or to restore settings if you have to reset the PS0500 for any
reason. See the InPower User Guide for more information.
While InPower can be used with the PS0500 for facilitating the setup, it is not essential for carrying out the basic setup
operations. The basic setup can be performed directly from the control panel of PS0500. Following paragraphs
Describe the process of carrying out basic setup from the control panel.
The Setup mode can be entered only from Stop mode when the genset is not running. This is accomplished by
holding the Reset and the OK buttons pressed for 5 seconds continuously while in stop mode. The RED Stop Led
flashes faster (double the normal rate) as long as the control is in setup mode. Pressing ← button while in Main Menu
exits the setup mode. Navigation through the setup menus is described further in a separate section later.
MENU Description
Tables 6.1 to 6.18 show a summary of the menus offered on the control panel of the PS0500.
Menu Description
Alt Setup Use this menu to select alternator setup parameters like Single / Three phase, 50 / 60 Hz
operation, Wye / Delta , Voltage etc.
Units Use this menu to select Metric or US units for Coolant Temperature and Oil Pressure
Oil Pr Input Use this menu to select the sensor types used with oil pressure
Use this Menu to configure the response to Customer input and to configure usage of the
Customer I/O
customer output
Flt History Use this menu to view last five faults that are stored in the control
page 34
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Table 6.2 Alt Setup Menu Table 6.5 Nom LL Voltage Sub Menu
page 35
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
SubMenu Description
Choose the
Cust I/P Flt response to the
input when active
Choose the
Customer O/P1 function of this
output
Choose the
Customer O/P2 function of this
output
MenuItems
ShutDown
Warning
page 36
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
Navigation
The manual (↑), Reset (↓ //), OK (→) and Auto (←) buttons are used for navigation during the setup. As long as
setup mode is not exited these buttons will only act as arrow keys. The RED Stop lamp flashes at twice the
normal rate as long as the setup mode is not exited and the control is not returned to STOP mode.
Navigation Example
← Main Menu //
Alt Setup →
Line 1 always bears the Menu Name and Line 2 shows items in the Menu.
The symbols ←, / /, → indicate that the buttons bearing those symbols are active and can be used as follows
← Back Button
// (↓) Scroll Down to the next item
→ Select the item shown on line 2
When a menu or submenu containing more choices is selected, the Name of the Menu or Submenu moves to
line 1 and the choices in the menu are displayed on line 2. / / (↓) button can then be used to scroll through the
choices available in the Menu, and → (OK) button can be used to choose the item shown on line 2. The ←
button can be used to go back one level up in the menu.
Here in the current example, pressing → will take you to the Alt Setup menu. The Name of the chosen Menu (Alt
Setup) will move into the line 1 and the first choice within that menu (phase type) will be shown on line 2.
← Alt Setup //
Phase Type →
You can now press / / (↓) button to scroll through the choices available in the Alt Setup Menu one by one. When
the choice that you want appears on line 2, pressing → will take you into that submenu.
Here in our example, let us say, you pressed / / (↓) until “Nom LL Voltage” submenu was displayed in line 2.
← Alt Setup //
Nom LL Voltage →
Pressing → will take you into the choices available for nominal line to line voltages. Pressing ← will take you to
the main menu and pressing / / (↓) will take you to the next item within Alt Setup Menu.
Let us say you pressed →. The display will now look like this.
page 37
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
← Nom LL Voltage //
190 →
Pressing / / (↓) will show all the choices available for nominal LL voltage one by one. Let us say you pressed / /
(↓) until 440 was displayed.
← Nom LL Voltage //
440 →
Pressing → will select that as the Nominal LL Voltage. An asterisk (*) will appear in line 2 indicating that to be
the current selection. The → at the end of line 2 will change to ← indicating that the only active buttons now are /
/ (↓) and ←.
← Nom LL Voltage //
* 440 ←
Pressing ← button will take you to one level up in the menu tree at a time. You have to press ← several times to
reach the main menu. Pressing ← button while at the main menu shall exit the setup mode. Following message
shall be displayed before leaving the setup mode.
Current Config
Saved ←
Press ← to leave setup mode and resume normal operation. The red Stop LED will resume flashing with normal
rate (1 Hz).
page 38
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
These tests can be performed without removing the CAUTION Disconnect battery
generator. Before starting tests, disconnect the charger from AC source before disconnecting
negative (–) cable from the battery to make sure the battery cables. Otherwise, disconnecting cables
engine will not start while performing these tests. can result in voltage spikes damaging to DC
control circuits of the set.
FIGURE 7.1 Po P1 Appropriate frame and type of connection is used to meet the application
requirements in terms of single phase three phase, 50 Hz, 60 Hz temperature rise and the KVA rating
page 39
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 40
Publication A029U889
Power Start 0500 Issue 3 - 8-2017
X1.3 & X2.5 Engine
page 41
Publication A029U889
Power Start 0500
Issue 3 - 8-2017
X1.3 & X2.5 Engine
7.4 EXCITER RECTIFIER BRIDGE Replacing Diodes: Make sure the replacement diode
(Rotating Rectifier Assembly) is of the correct polarity. Disconnect the pig tail from
the terminal post and unscrew the old diode. Apply
heat-sink compound under the head of the diode.
The exciter rectifier bridge is mounted on the exciter Make sure the compound does not get on the threads.
rotor, inboard, facing the main rotor. It consists of a Torque the diodes to 36 to 42 in-lbs (4 to 4.8Nm) and
positive plate and a negative plate, split diametrically. the pigtail terminals to 24 in-lbs (2.7 Nm) when
Each carries three diodes, three terminal posts for reassembling.
connecting exciter rotor leads to the diode pig-tails and
a terminal for the main rotor (generator field) lead. A Surge Suppresser Testing and Replacement:
surge suppresser is connected across the two plates Remove the suppresser. Replace the suppresser if it
to prevent transient voltages that could damage the appears to have overheated or if ohmmeter readings
diodes. indicate less than infinite resistance (end of scale) in
both directions. Torque the terminals to 24in-lbs (2.7
Testing Diodes: Disconnect the diode pigtails from the Nm) when reassembling.
terminal posts. Using an ohmmeter, measure electrical
resistance between each diode pigtail and the plate on
which the diode is mounted. Reverse the meter test CAUTION Layers of dust can cause
probes and repeat the tests. The electrical resistance diodes to overheat and fail. Brush dust off
across each diode should be high in one direction and regularly.
low in the other. If the resistance is high or low in both
directions, replace the diode.
page 42
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 43
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 44
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
7.5 MAIN STATOR sets of two winding elements in series). Single phase
only windings can be measured at W-V and should be
Testing Winding Resistance: twice the table value.
Measure electrical resistance across each pair of stator Testing Winding Insulation Resistance:
leads (U1-U2, U5-U6, VI-V2, V5-V6, W1-W2 and W5-
W6) with a Wheatstone bridge or ohmmeter having at Disconnect the AVR completely, (AT THE AVR), before
least0.001 ohm precision. Replace the stator if the carrying out this test. Disconnect any connections from
resistance of any winding is not as specified in Table6-1. Neutral to Earth.The Stator insulation should be checked
with an Insulation tester. The test instrument should be
Alternatively, winding resistance can be measured line- 500 or 1000 volts for low voltage Generators (up to
to-line at the generator terminals (U-V, V-W,W-U)on 690V). For low voltage machines (up to 690V), the
“star” connected generators. On a 600 volt generator, MINIMUM insulation value is 1.0 Meg-Ohm to Earth
line-to-line resistance should be twice the table value (Ground). WINDINGS MUST BE DRIED OUT IF
(two winding elements in series). On a “series star” BELOW 1.0 MEG-OHM.
connected generator, line-to-line resistance should be
four times the table value (four winding elements in
series).
NOTE Faults on the stator winding or cables may
On a “parallel star” connected generator, line-to-line
also cause noticeable load increase on the engine
resistance should be the same as the table value (two
when excitation is applied.
page 45
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
If after establishing and correcting any fault on the rectifier assembly the output is still low when separately excited,
then the main rotor, exciter stator and exciter rotor winding resistances should be checked (see Resistance Charts),
as the fault must be in one of these windings. The exciter stator resistance is measured across leads F1 and F2.
The exciter rotor is connected to six studs, which also carry the diode lead terminals. The main rotor winding is
connected across the two rectifier plates. The respective leads must be disconnected before taking the readings.
Resistance values should be within 10% of the values given in the table below
ALTERNATOR FRAME SIZE Main Rotor (Ohms) Exciter stator (Ohms) Exciter Rotor (Ohms)
P044D 0.437 17.5 0.211
P044E 0.415 17.7 0.211
P044F 0.465 18.5 0.228
P044G 0.551 18.5 0.228
P044H 0.545 18.5 0.228
P144D 0.657 18.5 0.228
P144E 0.67 19.36 0.215
P144F 0.708 20.25 0.201
P144G 0.857 22.25 0.201
P144H 0.89 22.9 0.21
P144J 0.983 22.9 0.21
P144K 0.99 22.9 0.21
*- Note :These Windings are referred by the alternator Manufacturer as “311” Winding no.
page 46
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
WARNING Ignition of explosive battery CAUTION Do not use fan blade to bar over
gases can cause severe personal injury or death. Arc- engine. That can damage blades and cause property
ing at battery terminals, light switch or other damage and personal injury.
equipment, flame, pilot lights and sparks can ignite 1. The rotor will be carried inside the stator when
battery gas. Do not smoke, or switch trouble light ON the generator is withdrawn from the engine. Bar
or OFF near battery. Discharge static electricity from the engine until one of the four poles of the rotor
body before touching batteries by first touching a points straight down so that the rotor will rest on
grounded metal surface. the face of the pole when the generator is
Ventilate battery area before working on or near withdrawn.
battery—Wear goggles—Stop genset and disconnect 2.
charger before disconnecting battery cables—
Disconnect negative (–) cable first and reconnect last. CAUTION The rotor can be damaged if it
rests on the edges of the winding slot between two
CAUTION poles.
Disconnect battery charger from 2. Attach lifting eyes and a hoist of sufficient
AC source before disconnecting battery cables. capacity (Figure 6-7).
Otherwise, disconnecting cables can result in voltage 3. Take up hoist slack and remove the two through
spikes damaging to DC control circuits of the set . bolts securing the generator to the rubber
isolation mounts.
WARNING 4. Raise the generator end approximately one inch
Accidental starting of the (12 mm) and securely block the engine under the
generator set can cause severe personal injury or flywheel housing. Lower the generator slightly so
death. Prevent accidental starting by disconnecting that the blocks carry most of the weight.
the negative (–) cable from the battery terminal. 5. Remove the bolts securing the generator drive
discs to the flywheel.
Removing The Generator Control Housing 6. Loosen all the bolts securing the generator
adapter casting to the flywheel housing. Adjust
1. Disconnect the line cables and conduit. For the hoist to carry the full weight of the generator,
reconnections later, make sure each cable is remove the bolts and pull the generator away.
clearly marked to indicate the correct terminal. Never withdraw the generator leaving the rotor to
2. Disconnect the remote control wiring and conduit. hang by the drive discs. The weight of the rotor will
For reconnections later, make sure each wire is damage the drive discs.
clearly marked to indicate the correct terminal.
page 47
Publication A029U889
Power Start 0500
Issue 3 - 8-2017
X1.3 & X2.5 Engine
25
page 48
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
2. Using a hoist of sufficient capacity, cinch a lifting 4. Remove the retaining clip if the rotor shaft
strap on the drive end of the rotor. Lift the bearing bearing is to be removed.
end of the rotor by a Eye Bolt and push it towards
the drive end of the generator until half the width of
the rotor core protrudes from the stator. Release
the weight of the rotor and recinch the lifting strap 8.1 Generator Reassembly
around the middle of the rotor core. Withdraw the
rotor until it is free of the stator, guiding it by Reassembling is the reverse of disassembling. Note
the following. The Assembly Torques are specified in
the succeeding page.
page 49
Power Start 0500 Publication A029U889
Issue 3 - 8-2017
X1.3 & X2.5 Engine
Generator Assembly Tools and Torque Values
page 50
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
GENSET SPECIFICATIONS
3-Phase Ratings
50 Hz
Model Standby Prime
kW (kVA) kW (kVA)
C8D5 6.6 (8.25) 6 (7.5)
60 Hz
Model Standby Prime
kW (kVA) kW (kVA)
C12D6, C12D6 (Spec E) 12 (15) 11 (13)
page 51
Power Start 0500 Publication A029U889
Issue 3 - 8-2017
X1.3 & X2.5 Engine
Engine specifications
X1.3 X2.5
Design 4 cycle, in-line, naturally aspirated 4 cycle, in-line, naturally aspirated
Bore 95mm (3.74 in) 91.44mm (3.6 in)
Stroke 91mm (3.58 in.) 127mm (5 in)
Displacement 1.3 liter (78.72 in.³ ) 2.5 liter ( 152.56 in.³ )
Cylinder block Alloy Cast iron, In-line, 2 cylinder Alloy Cast iron, In-line, 2 cylinder
Battery capacity 32 Ampere-Hour 63 Ampere-Hour
Battery charging alternator N/A N/A
Starting voltage 12 volt, negative ground 12 volt, negative ground
Fuel system Direct injection: Number 2 diesel fuel Direct injection: Number 2 diesel fuel
Single element, Spin-on fuel filter cum Water Single element, Spin-on fuel filter cum Water
Separator, Filtration efficiency 25 micron Separator, Filtration efficiency 25 micron
Fuel filter
99%(min) ,Water Separation efficiency 90% 99%(min) ,Water Separation efficiency 90%
(min) (min)
Air cleaner type Dry replaceable element Dry replaceable element
Spin on full flow filter , Filtration efficiency 25 Spin on full flow filter , Filtration efficiency 25
Lube oil filter type(s)
micron 99%(min) micron 99%(min)
122°F (50°C) ambient radiator with coolant 122°F (50°C) ambient radiator with coolant
Standard cooling system
Recovery System Recovery System
Alternator specifications
Design Brushless, 4 pole, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Standard temperature rise 163 ºC standby @ 27 ºC ambient
Exciter type Torque match (shunt) standard, EBS optional EBS(Excitation Boost System)
Phase rotation A (U), B (V), C (W)
Alternator cooling Shaft mounted centrifugal fan
THD < 1.8 % on no-load and < 5 % under non-distorting
AC waveform total harmonic distortion balanced linear load
Telephone influence factor (TIF) < 50
Telephone harmonic factor (THF) < 2%
Available voltages
50 Hz line–neutral/line-line ( Std Voltage -)
230/400
(STD) 240/416 220/380 127/220 138/240
page 52
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
This section consists of the schematic and connection NOTE: P1 Alternators for X1.3 have Winding 311 for 3
wiring diagrams referenced in the text. The following phase for 50 05/06 Winding for 50/60 Hz Single phase
drawings are included. respectively.
• Page 54, 3 Phase Reconnect Wiring Diagram NOTE: The Wiring Drawings are representative
• Page 56, 1 Phase NON Reconnect Wiring drawings.
• Page 57, Wiring Diagram
For service, use drawing supplied with geneset pasted
• Page 58, Battery Charger and Coolant Heater
on the backside of the door of the pedestal panel
Connections (optional)
• Page 59, 3 Phase - Mechanical Governor wiring The Drawings can be downloaded from the PGBU
• Page 122, Engine Harness Jumper (PC2100 Engineering Database.
to PCC1302)
• Page 123, Customer Connections
page 53
Power Start 0500 Publication A029U889
Issue 3 - 8-2017
X1.3 & X2.5 Engine
3 Phase Reconnectable, 12 Lead CT Secondary Connection
page 54
Publication A029U889
Power Start 0500
Issue 3 - 8-2017
X1.3 & X2.5 Engine
8–3
page 55
Power Start 0500 Publication A029U889
Issue 3 - 8-2017
X1.3 & X2.5 Engine
1 Phase NON -Reconnectable, 4 Lead CT Secondary Con
page 56
Power Start 0500 Publication A029U889
Issue 3 - 8-2017
X1.3 & X2.5 Engine
page 57
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 58
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 59
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 60
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 61
Power Start 0500 Publication A029U889
X1.3 & X2.5 Engine Issue 3 - 8-2017
page 62
page 63
power.cummins.com
Copyright E 2017 Cummins Inc. All rights reserved.
Cummins, the “C” logo, PowerCommand, AmpSentry, and InPower are trademarks of Cummins Inc.
Other company, product, or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.