Nebraska Stockwater Pipeline Handbook: April 2008 USDA Natural Resource Conservation Service
Nebraska Stockwater Pipeline Handbook: April 2008 USDA Natural Resource Conservation Service
April 2008
In most cases “Montana” was replaced with “Nebraska”; tables and figures were updated to
reflect Nebraska criteria; amendments and examples added; and data sheets changed.
This handbook is only a guide; it does not contain policy. Actual requirements and criteria
for livestock pipelines are contained in the National Conservation Planning Manual (NCPM)
and in Section IV of the Field Office Tech Guide (FOTG). It is a supplement to the
ENGINEERING FIELD HANDBOOK (EFH), CHAPTER 3, HYDRAULICS.
NEBRASKA STOCKWATER PIPELINE HANDBOOK
TABLE OF CONTENTS
CHAPTER 1 - INTRODUCTION
PART 1.1 PURPOSE AND OBJECTIVES 1-1
PART 1.2 GENERAL 1-1
APPENDICES
APPENDIX A WORKSHEETS
APPENDIX B COMPUTER PROGRAMS
APPENDIX C MATERIALS SOURCES
APPENDIX D PLANNING AND DESIGN GUIDE
INTRODUCTION
CHAPTER 1 - INTRODUCTION
TABLE OF CONTENTS
CHAPTER 1
INTRODUCTION
1.2 GENERAL
Stockwater pipelines come in many configurations and sizes in Nebraska. They may
consist of anything from a short piece of pipe between a spring and stock tank, to many
miles of pipelines, with pressures as high as 500 psi. Design may be as critical for a
short pipeline as for a long one.
Consider what can happen if a pipeline fails. If there is little or no backup water
available in a field, and the problem is not discovered promptly, livestock may die.
During hot, dry weather, a cow can only last three or four days without water.
A stockwater pipeline can be a great improvement over existing watering systems.
Stockwater ponds tend to dry up at the worst times; windmills often don't work when they
are needed, and hauling water is unpopular and time consuming. On the other hand, a
stockwater pipeline can be a very dependable water distribution system. Not only can it
be dependable, but good quality water can be delivered to optimum locations to promote
good grazing distribution and healthy animals.
Planning and design of a stockwater pipeline may be complex, and pipelines can be a
significant investment. It is very important that they be properly planned and designed,
and be as economical as possible. This handbook is dedicated to providing some of the
information and tools needed to get this job done.
PLANNING CONSIDERATIONS
CHAPTER 2 - PLANNING CONSIDERATIONS
TABLE OF CONTENTS
FIGURES
TABLES
CHAPTER 2
PLANNING CONSIDERATIONS
2.1 GENERAL
When planning a stockwater pipeline, it is always important to follow good resource planning procedures.
Figure 2.1 illustrates the NRCS planning process as it relates to stockwater pipelines. The planning
processes must be followed, even when we are involved with a system where the landowner knows
exactly what he/she wants, and we are in a rush to get the job done.
To do otherwise frequently leads to such problems as:
• System that does not meet resource conservation needs
• The types and maximum number of livestock which will use water at any given time.
• Location and details of existing water sources in the area to be serviced by the pipeline.
• Reliability and quality of existing water sources in the area to be serviced by the pipeline.
• Location, reliability and quality of water source or sources which may be used as a supply for the
pipeline.
• Desirable watering locations based on an analysis of range use patterns, range conditions,
geology, and topography.
• Geologic considerations including location of shallow bedrock, unstable soils, coarse gravel
subsoils, old slide areas, wetland areas, sharp breaks in slope, etc.
The worksheet illustrated in Appendix A, Planning Worksheet may be used as an aid in obtaining
necessary resource information.
Table 2.1
Minimum Daily Stockwater Requirements
Cow 12 17
Cow & Calf 15 20
Dairy Cow (lactating) 25 30
Horse 15 20
Buffalo 20 25
Sheep 1.5 3
Goats 1.5 3
Hogs 1.5 3
Deer 1.5 -
Antelope 1.5 -
Elk 6 -
These are minimum volumes. If livestock are larger than average or there are other planning issues, the
volume of storage should be increased accordingly.
Table 2.2
Maximum Water Facility Spacing
There will usually be water lost to evaporation and spillage at drinking tanks and troughs. Evaporation
from a water surface can amount to as mush as 0.22 inches per day in northeastern Nebraska, 0.25
inches per day in the panhandle and sandhills, and 0.28 inches per day in southwestern Nebraska during
the summer months of the year.
In intensive water facility applications, the livestock will water more often and more spillage will occur. It
is critical that the water supply meets the water demand. To account for these losses and demand, the
minimum daily water requirements shown in Table 2.1 were increased for intensive water facility
applications.
Figure 2.2
FLOW RATE REQUIRED FOR DAILY NEEDS (SUPPLIED IN 4 HRS)
90
25
gal/day/head
80
20
70
Flow Rate (gpm)
60
15
50
12
40
30
6
20
10 1.5
0
0 100 200 300 400 500 600 700 800 900
Number of Stock Using System
EXAMPLE:
Given: Conventional grazing system with 200 Dairy Cows.
Find: Design flow rate meeting daily water requirements in a 4-hour period.
Solution:
From Table 2.1: 25 gal/day/head required during peak use period.
From Figure 2.2: Minimum flow requirement is 22.9 gpm.
Figure 2.3
FLOW RATE REQUIRED FOR DAILY NEEDS (SUPPLIED IN 6 HRS)
60 gal/day/head
25
50
Flow Rate (gpm)
20
40
15
30
12
20
6
10
1.5
0
0 100 200 300 400 500 600 700 800 900
Number of Stock Using System
EXAMPLE:
Given: Conventional grazing system with 300 Cows.
Find: Design flow rate meeting daily water requirements in a 6-hour period.
Solution:
From Table 2.1: 12 gal/day/head required during peak use period.
From Figure 2.2: Minimum flow requirement is 11.0 gpm.
30 gal/day/head 25
25
20
Flow Rate (gpm)
20
15
15 12
10
6
5
1.5
0
0 100 200 300 400 500 600 700 800 900
Number of Stock Using System
EXAMPLE:
Given: Conventional grazing system with 150 Cow/calf pairs.
Find: Design flow rate meeting daily water requirements in a 12-hour period.
Solution:
From Table 2.1: 15 gal/day/head required during peak use period.
From Figure 2.2: Minimum flow requirement is 3.4 gpm.
Table 2.3
TOTAL DAILY STOCKWATER REQUIREMENTS
Gallons/Day
Based on Additional 10% for Evaporation and Waste
Number of
WATER REQUIREMENTS - Gallons/Day/Head
Stock
Using
System 2 8 12 15 20 25
25 55 220 330 413 550 688
50 110 440 660 825 1,100 1,375
75 165 660 990 1,238 1,650 2,063
100 220 880 1,320 1,650 2,200 2,750
125 275 1,100 1,650 2,063 2,750 3,438
150 330 1,320 1,980 2,475 3,300 4,125
175 385 1,540 2,310 2,888 3,850 4,813
200 440 1,760 2,640 3,300 4,400 5,500
250 550 2,200 3,300 4,125 5,500 6,875
300 660 2,640 3,960 4,950 6,600 8,250
350 770 3,080 4,620 5,775 7,700 9,625
400 880 3,520 5,280 6,600 8,800 11,000
450 990 3,960 5,940 7,425 9,900 12,375
500 1,100 4,400 6,600 8,250 11,000 13,750
600 1,320 5,280 7,920 9,900 13,200 16,500
700 1,540 6,160 9,240 11,550 15,400 19,250
800 1,760 7,040 10,560 13,200 17,600 22,000
900 1,980 7,920 11,880 14,850 19,800 24,750
1000 2,200 8,800 13,200 16,500 22,000 27,500
Table 2.4
ROUND STOCK TANK STORAGE CAPACITY
Gallons
When using a tank not similar to the above round stock tank (i.e. rubber tire tank), use sound engineering
judgment or appropriate worksheets to determine available storage.
Where a windmill is involved, and other water sources are not available, a minimum of 10 days' livestock
water requirement plus about 10% evaporation and spillage loss should be provided in storage tanks,
when feasible.
There is no hard and fast rule as to how much emergency water storage is adequate. Much depends on
how the operator operates. For example, if livestock is checked every couple of days, less storage would
be required than if checked only once a week.
Storage also depends on how easy it would be to move the stock to another field where water is located,
should the water supply in the field where the stock is located be interrupted.
The determination of adequate emergency storage is a management decision that should be made with
the operator after thorough discussion of all factors involved.
Special care must be used to exclude scum and sediment from pipelines using surface water as a source.
A screening or filtering device should always be used at the entrance to the pipeline. If sediment is a
problem, consider constructing a settling pond at the entrance to the pipeline.
2.6.3 Well
Some wells produce considerable amounts of sand. A sand separator should be installed at the
beginning of the pipeline in such a case. Sand separators are available through trickle irrigation supply
sources.
2.6.4 Water Quality
The following is taking from “Water Requirements for Pastured Livestock”- Prairie Farm Rehabilitation
Administration - Canada
Water quality can affect both total water consumption and the general health of the livestock. Elevated
water temperatures and objectionable taste and odor will discourage consumption, and reduced water
consumption will, in turn, result in a reduction of feed intake, with the net result being decreased weight
gain.
The most common water quality considerations that make water unsuitable for livestock consumption are
salinity (the concentration of various kinds of dissolved salts), nitrates, algae, and on rare occasions,
other factors such as alkalinity or pesticides.
Salinity
Dissolved salts can consist of any combination of calcium, magnesium, and sodium chlorides, sulfates
and bicarbonates. While all have slightly different effects on animal metabolism, none are particularly
worse than any other. Also, the effects of various salts seem to be additive, meaning that a mixture
seems to cause the same degree of harm as an equivalent concentration of a single salt. Animals seem
to have an ability to adapt to saline water to some extent, but abrupt changes may cause harm. Animals
may avoid drinking highly saline water for a number of days, followed by a period of high consumption
which causes illness or even death.
Nitrates
Water analyses generally report nitrates and nitrites together. Nitrate toxicity resulting exclusively from
water is rare, but is primarily of concern when combined with forages having high nitrate levels. Nitrates
themselves are not very toxic, but bacteria in ruminant animals (dairy and beef cattle) will convert the
nitrates to nitrite which reduces the blood’s ability to metabolize oxygen and effectively causes shortness
of breath and eventual suffocation.
Sulfates
Although sulfates can have a laxative effect, there is limited data available regarding their overall effect on
livestock health and productivity. It is generally felt that the presence of sulfates should seldom be a
problem in livestock water. However, in some rare cases involving very saline water, producers have lost
cattle due to a sulfate-related problem.
Alkalinity
Excessive alkalinity can cause physiological and digestive upset in livestock, but the level at which it
becomes troublesome and its precise effects have not been thoroughly studied. Most waters are alkaline
in nature, but fortunately, in only a few instances has it been found that a water source has been too
alkaline for livestock. Alkalinity is usually expressed as a concentration of Calcium Carbonate (CaCo3), in
parts per million (ppm) or milligrams per liter (mg/L).
Bacterial Contamination
Most water has varying levels of bacterial contamination, but such contamination does not generally
cause problems for livestock. Calves can sometimes suffer from Coccidiosis, which can lead to bloody
diarrhea, dehydration, weight loss, depression, and sometimes death. Elevated water sources and a
reasonable effort at maintaining cleanliness of watering facilities can reduce the potential for problem-
causing bacterial contamination.
Other Factors
Generally speaking, any surface water that can support a population of fish should not have dangerous
levels of pesticides or naturally-occurring toxic elements like heavy metals. However, there is growing
evidence that toxic compounds are present in many surface waters across the prairies. If there is any
reason to believe that a water source may have elevated levels of toxic compounds, they can be tested
for.
It is recommended that water samples from the intended source be analyzed to ensure that any problems
relating to water quality can be avoided.
The most common factors to consider are salinity and nitrates. Tables 2.5 and 2.6 describe tolerable
levels of these elements.
Table 2.5
USE OF SALINE WATER FOR LIVESTOCK
Table 2.6
EFFECTS OF NITRATES ON LIVESTOCK
TABLE OF CONTENTS
FIGURES
CHAPTER 3
PIPELINE SYSTEM TYPES
3.1 GENERAL
There are several types of stockwater pipeline systems that we need to know how to design.
More than one of these system types may be incorporated in a single system.
Figure 3.1
TYPICAL LOW HEAD GRAVITY SYSTEMS
Figure 3.2
TYPICAL HIGH HEAD GRAVITY SYSTEM
Figure 3.3
TYPICAL AUTOMATIC PRESSURE SYSTEM
Figure 3.4
TYPICAL MANUAL OR TIMER OPERATED SYSTEM
Figure 3.5
TYPICAL FLOAT SWITCH OPERATED SYSTEM
• Sun exposure
It is difficult to quantify and determine the actual effect of some of these factors. For situations
where there is not continuous flow in the pipeline during the winter months, refer to Extreme
Frost Depth Map. North slope exposure, high altitudes, and moist soils are factors indicating
the need for burying the pipe deeper. Even though the pipe is buried to these depths, it could
still freeze in some portions of the line.
Because of equipment limitations it is difficult to bury a pipeline deeper than six feet. Therefore,
the choices are to bury the pipeline a minimum of five feet in most normal conditions and six
feet or deeper where exposure, elevation, long periods of stagnant water and/or moist
conditions exist.
Appurtenances for all year pipelines must be designed in a way that will reduce the chance of
frozen pipelines during cold weather. Valves of all kinds must be protected from freezing. This
is usually done by installing them in a covered manhole or access hole. Frost free hydrants
must be used. Float valves can be installed under a protective cover or in an insulated well.
TABLE OF CONTENTS
FIGURES
CHAPTER 4
PIPELINE ROUTE SELECTION AND SURVEYS
The following are the most common engineering instruments used to survey for livestock
pipelines:
• Automatic Level
• Theodolite
• Total station
• GPS (Survey Grade)
While all of these methods are relatively accurate, surveys with automatic levels or theodolites
require more time because of sight distance limitations and required processing of the survey
data. Total station and survey grade GPS surveys will generally be the most accurate and time
efficient, especially on long pipelines.
The type of survey which should be used will depend on which one will give the degree of
accuracy necessary and which will be the most time and cost effective. For additional guidance
on survey accuracy, refer to Chapter 1 of Part 650, Engineering Field Handbook.
The horizontal accuracy for the Garminmap76 is found on the GPS Information Page, See
figure 4.1. The GPS Information Page should be monitored during the survey to verify
acceptable accuracy. GPS survey should only be collected when the horizontal accuracy is less
than 10 feet. To ensure maximum accuracy, the entire pipeline project should be surveyed in
as short a time period as possible.
Figure 4.1
TABLE OF CONTENTS
FIGURES
TABLES
CHAPTER 5
PIPE MATERIALS SELECTION
5.1 GENERAL
There are several types of pipe that may be used in stockwater systems. The most
commonly used types are discussed below. Usually, pipe cost dictates the type of pipe
that is used.
When designing a pipeline, it is important to know the type of pipe to be used. Internal
pipe diameters vary depending on material type and pressure rating for a given pipe
size. Due to differing internal cross sectional area and friction loss factors, friction loss
in long pipelines can differ considerably from one type and rating of pipe to another.
Table 5.1 lists the temperature reduction factors for PVC pipe.
Table 5.1
PVC PLASTIC PIPE RATING REDUCTION DUE TO TEMPERATURE
There are two types of PVC pipe. Standard Dimension Ratio-Pressure Rated pipe (SDR-PR) is
manufactured under specification ASTM D2241. PVC Iron Pipe Size (PVC-IPS) pipe is
manufactured under specification ASTM D1785.
SDR-PR rated pipe is rated using standard dimension ratio and pressure as factors. This is the
most common pipe type used in stockwater pipelines in Nebraska. Tables 5.2 through 5.5 list
available sizes, pressure ratings and friction loss factors.
PVC-IPS pipe has various pressure ratings depending on nominal diameter and schedule
designations. Schedule 40, 80, and 120 pipe are available. Tables 5.6 through 5.8 list
available sizes, pressure ratings, and friction loss factors.
For both of these types of pipe, the outside diameter is constant and the inside diameter varies.
The friction loss in PE pipe is so low that well depths different than the assumed 100 feet will
make little difference in total friction loss. If the total plumbing system is significantly different
than assumed above, special calculations should be performed. If steel pipe is used to drop the
pump in the well, special computations must be made.
Figure 5. 1
ESTIMATED FRICTION LOSS AT WELL
Curve Type
Table 5.2
PVC-SDR PIPE
FRICTION LOSS ft/100 ft
SDR 26, Pressure Rating = 160 psi @ 73.48 F
Hazen Williams C = 150
Q 1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
gallons 0.0078 A 0.0128 A 0.0168 A 0.0262 A 0.0384 A 0.0569 A 0.0743 A 0.0941 A
per min. 1.195 ID 1.532 ID 1.754 ID 2.193 ID 2.655 ID 3.230 ID 3.692 ID 4.154 ID
1 0.0408 0.0122 0.0063 0.0021 0.0008 0.0003 0.0002 0.0001
2 0.1473 0.0439 0.0227 0.0077 0.0030 0.0012 0.0006 0.0003
3 0.3120 0.0931 0.0481 0.0162 0.0064 0.0025 0.0013 0.0007
4 0.5316 0.1585 0.0820 0.0276 0.0109 0.0042 0.0022 0.0012
5 0.8036 0.2397 0.1240 0.0418 0.0165 0.0063 0.0033 0.0019
6 1.1264 0.3359 0.1738 0.0585 0.0231 0.0089 0.0046 0.0026
7 1.4985 0.4469 0.2312 0.0779 0.0307 0.0118 0.0062 0.0035
8 1.9189 0.5722 0.2960 0.0997 0.0393 0.0151 0.0079 0.0044
9 2.3866 0.7117 0.3682 0.1241 0.0489 0.0188 0.0098 0.0055
10 2.9008 0.8651 0.4475 0.1508 0.0594 0.0229 0.0119 0.0067
11 3.4607 1.0321 0.5339 0.1799 0.0709 0.0273 0.0142 0.0080
12 4.0658 1.2125 0.6273 0.2113 0.0833 0.0321 0.0167 0.0094
13 4.7154 1.4062 0.7275 0.2451 0.0966 0.0372 0.0194 0.0109
14 5.4091 1.6131 0.8345 0.2812 0.1108 0.0427 0.0222 0.0125
15 6.1463 1.8329 0.9482 0.3195 0.1259 0.0485 0.0253 0.0142
16 6.9265 2.0656 1.0686 0.3600 0.1419 0.0546 0.0285 0.0160
17 7.7495 2.3110 1.1956 0.4028 0.1588 0.0611 0.0319 0.0179
18 (1) 2.5691 1.3290 0.4478 0.1765 0.0679 0.0354 0.0199
19 (1) 2.8396 1.4690 0.4949 0.1951 0.0751 0.0392 0.0220
20 (1) 3.1226 1.6154 0.5443 0.2145 0.0826 0.0431 0.0242
21 (1) 3.4178 1.7681 0.5957 0.2348 0.0904 0.0471 0.0265
22 (1) 3.7253 1.9272 0.6493 0.2559 0.0985 0.0514 0.0289
23 (1) 4.0450 2.0926 0.7050 0.2779 0.1070 0.0558 0.0314
24 (1) 4.3767 2.2642 0.7628 0.3007 0.1157 0.0603 0.0340
25 (1) 4.7203 2.4420 0.8227 0.3243 0.1248 0.0651 0.0367
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly used
materials. Other materials have different ratings, see ASTM D2241.
Table 5.3
PVC-SDR PIPE
FRICTION LOSS ft/100 ft
SDR 21, Pressure Rating = 200 psi @ 73.408 F
Hazen Williams C = 150
Q 1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
Gallons 0.0077 A 0.0123 A 0.0161 A 0.0252 A 0.0369 A 0.0547 A 0.0715 A 0.0904 A
per min. 1.198 ID 1.502 ID 1.720 ID 2.149 ID 2.601 ID 3.166 ID 3.620 ID 4.072 ID
1 0.0403 0.0134 0.0069 0.0023 0.0009 0.0004 0.0002 0.0001
2 0.1455 0.0484 0.0250 0.0084 0.0033 0.0013 0.0007 0.0004
3 0.3083 0.1025 0.0530 0.0179 0.0071 0.0027 0.0014 0.0008
4 0.5252 0.1746 0.0902 0.0305 0.0120 0.0046 0.0024 0.0014
5 0.7939 0.2639 0.1364 0.0461 0.0182 0.0070 0.0036 0.0021
6 1.1127 0.3699 0.1912 0.0646 0.0255 0.0098 0.0051 0.0029
7 1.4803 0.4921 0.2543 0.0860 0.0339 0.0130 0.0068 0.0038
8 1.8956 0.6301 0.3257 0.1101 0.0434 0.0167 0.0087 0.0049
9 2.3576 0.7837 0.4050 0.1369 0.0540 0.0207 0.0108 0.0061
10 2.8656 0.9525 0.4923 0.1664 0.0657 0.0252 0.0131 0.0074
11 3.4187 1.1364 0.5873 0.1985 0.0784 0.0301 0.0157 0.0088
12 4.0165 1.3351 0.6900 0.2333 0.0921 0.0353 0.0184 0.0104
13 4.6582 1.5484 0.8002 0.2705 0.1068 0.0410 0.0213 0.0120
14 5.3434 1.7762 0.9180 0.3103 0.1225 0.0470 0.0245 0.0138
15 6.0717 2.0182 1.0431 0.3526 0.1392 0.0534 0.0278 0.0157
16 6.8425 2.2745 1.1755 0.3974 0.1568 0.0602 0.0313 0.0177
17 7.6554 2.5447 1.3151 0.4446 0.1755 0.0674 0.0351 0.0198
18 (1) 2.8288 1.4620 0.4942 0.1951 0.0749 0.0390 0.0220
19 (1) 3.1267 1.6159 0.5463 0.2156 0.0828 0.0431 0.0243
20 (1) 3.4383 1.7770 0.6007 0.2371 0.0910 0.0474 0.0267
21 (1) 3.7634 1.9450 0.6575 0.2595 0.0996 0.0519 0.0292
22 (1) 4.1020 2.1200 0.7167 0.2828 0.1086 0.0565 0.0319
23 (1) 4.4539 2.3019 0.7782 0.3071 0.1179 0.0614 0.0346
24 (1) 4.8192 2.4906 0.8420 0.3323 0.1276 0.0664 0.0374
25 (1) 5.1976 2.6862 0.9081 0.3584 0.1376 0.0716 0.0404
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly used
materials. Other materials have different ratings, see ASTM D2241.
Table 5.4
PVC-SDR PIPE
FRICTION LOSS ft/100 ft
SDR 17, Pressure Rating = 250 psi @ 73.48 F
Hazen Williams C = 150
Q 1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
Gallons 0.0074 A 0.0117 A 0.0153 A 0.0239 A 0.0351 A 0.0520 A 0.0680 A 0.0860 A
per min. 1.162 ID 1.464 ID 1.676 ID 2.095 10 2.537 ID 3.088 ID 3.530 ID 3.970 ID
1 0.0470 0.0152 0.0079 0.0026 0.0010 0.0004 0.0002 0.0001
2 0.1695 0.0548 0.0284 0.0096 0.0038 0.0014 0.0008 0.0004
3 0.3592 0.1161 0.0601 0.0203 0.0080 0.0031 0.0016 0.0009
4 0.611 8 0.1978 0.1024 0.0345 0.0136 0.0052 0.0027 0.0015
5 0.9249 0.2990 0.1547 0.0522 0.0205 0.0079 0.0041 0.0023
6 1.2964 0.4190 0.2169 0.0731 0.0288 0.0111 0.0058 0.0033
7 1.7247 0.5575 0.2885 0.0973 0.0383 0.0147 0.0077 0.0043
8 2.2085 0.7139 0.3695 0.1246 0.0491 0.0188 0.0098 0.0055
9 2.7468 0.8879 0.4595 0.1550 0.0610 0.0234 0.0122 0.0069
10 3.3386 1.0791 0.5585 0.1884 0.0742 0.0285 0.0148 0.0084
11 3.9831 1.2875 0.6663 0.2247 0.0885 0.0340 0.0177 0.0100
12 4.6795 1.5126 0.7828 0.2640 0.1039 0.0399 0.0208 0.0117
13 5.4272 1.7542 0.9079 0.3062 0.1205 0.0463 0.0241 0.0136
14 6.2255 2.0123 1.0414 0.3513 0.1383 0.0531 0.0277 0.0156
15 7.0740 2.2865 1.1834 0.3992 0.1571 0.0603 0.0314 0.0177
16 7.9720 2.5768 1.3336 0.4498 0.1771 0.0680 0.0354 0.0200
17 (1) 2.8830 1.4921 0.5033 0.1981 0.0761 0.0396 0.0224
18 (1) 3.2048 1.6587 0.5595 0.2202 0.0846 0.0441 0.0249
19 (1) 3.5423 1.8333 0.6184 0.2434 0.0935 0.0487 0.0275
20 (1) 3.8953 2.0160 0.6800 0.2677 0.1028 0.0536 0.0302
21 (1) 4.2637 2.2066 0.7443 0.2930 0.1125 0.0586 0.0331
22 (1) 4.6472 2.4052 0.8113 0.3193 0.1226 0.0639 0.0361
23 (1) 5.0460 2.6115 0.8809 0.3467 0.1331 0.0694 0.0392
24 (1) 5.4598 2.8257 0.9531 0.3752 0.1440 0.0751 0.0424
25 (1) 5.8885 3.0476 1.0279 0.4046 0.1554 0.0810 0.0457
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly used
materials. Other materials have different ratings, see ASTM D2241.
Table 5.5
PVC-SDR PIPE
FRICTION LOSS ft/100 ft
SDR 13.5, Pressure Rating = 315 psi @ 73.48 F
Hazen Williams C = 150
Q 1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
Gallons 0.0069 A 0.0109 A 0.0143 A 0.0223 A 0.0327 A 0.0485 A 0.0633 A 0.0802 A
per min. 1.121 ID 1.414 ID 1.618 ID 2.023 ID 2.449 ID 2.982 ID 3.408 ID 3.834 ID
1 0.0557 0.0180 0.0093 0.0031 0.0012 0.0005 0.0002 0.0001
2 0.2011 0.0649 0.0337 0.0113 0.0045 0.0017 0.0009 0.0005
3 0.4260 0.1375 0.0713 0.0240 0.0095 0.0036 0.0019 0.0011
4 0.7258 0.2342 0.1215 0.0409 0.0161 0.0062 0.0032 0.0018
5 1.0972 0.3541 0.1837 0.0619 0.0244 0.0094 0.0049 0.0027
6 1.5378 0.4963 0.2575 0.0867 0.0342 0.0131 0.0068 0.0039
7 2.0459 0.6603 0.3425 0.1154 0.0455 0.0174 0.0091 0.0051
8 2.6198 0.8455 0.4386 0.1478 0.0583 0.0223 0.0117 0.0066
9 3.2583 1.0516 0.5455 0.1838 0.0725 0.0278 0.0145 0.0082
10 3.9603 1.2782 0.6630 0.2234 0.0881 0.0338 0.0176 0.0099
11 4.7248 1.5249 0.7910 0.2665 0.1051 0.0403 0.0210 0.0118
12 5.5509 1.7915 0.9293 0.3131 0.1234 0.0473 0.0247 0.0139
13 6.4378 2.0777 1.0778 0.3631 0.1432 0.0549 0.0286 0.0161
14 7.3848 2.3834 1.2363 0.4165 0.1642 0.0629 0.0328 0.0185
15 8.3912 2.7082 1.4048 0.4733 0.1866 0.0715 0.0373 0.0210
16 (1) 3.0520 1.5832 0.5334 0.2103 0.0806 0.0421 0.0237
17 (1) 3.4146 1.7713 0.5967 0.2353 0.0902 0.0471 0.0265
18 (1) 3.7958 1.9690 0.6633 0.2615 0.1002 0.0523 0.0295
19 (1) 4.1956 2.1764 0.7332 0.2891 0.1108 0.0578 0.0326
20 (1) 4.6137 2.3932 0.8063 0.3179 0.1218 0.0636 0.0358
21 (1) 5.0499 2.6195 0.8825 0.3479 0.1334 0.0696 0.0392
22 (1) 5.5042 2.8552 0.9619 0.3792 0.1453 0.0759 0.0427
23 (1) 5.9765 3.1002 1.0444 0.4118 0.1578 0.0824 0.0464
24 (1) 6.4666 3.3544 1.1301 0.4456 0.1708 0.0891 0.0502
25 (1) (1) 3.6178 1.2188 0.4805 0.1842 0.0961 0.0542
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly used
materials. Other materials have different ratings, see ASTM D2241.
Table 5.6
PVC-IPS SCHEDULE RATED PIPE
FRICTION LOSS ft/100 ft
Schedule 40 (3)
Hazen Williams C = 150
1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
Q
450 psi 370 psi 330 psi 280 psi 300 psi 260 psi 240 psi 220 psi
Gallons
0.0060 A 0.0104 A 0.0141 A 0.0233 A 0.0332 A 0.0513 A 0.0687 A 0.0884 A
per min.
1.049 ID 1.380 ID 1.610 ID 2.067 ID 2.469 ID 3.068 ID 3.548 ID 4.026 ID
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly used
materials. Other materials have different ratings, see ASTM D2241. Pressure rating is at
73.48 F.
Table 5.7
PVC-IPS SCHEDULE RATED PIPE
FRICTION LOSS ft/100 ft
Schedule 80 (3)
Hazen Williams C = 150
1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
Q
630 psi 520 psi 470 psi 400 psi 420 psi 370 psi 350 psi 320 psi
Gallons
0.0050 A 0.0089 A 0.0123 A 0.0205 A 0.0294 A 0.0459 A 0.0617 A 0.0798 A
per min.
0.957 ID 1.278 ID 1.500 ID 1.939 ID 2.323 ID 2.900 ID 3.364 ID 3.826 ID
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly
used materials. Other materials have different ratings, see ASTM D2241.
Pressure rating is at 73.48 F.
Table 5.8
PVC-IPS SCHEDULE RATED PIPE
FRICTION LOSS ft/100 ft
Schedule 120 (3)
Hazen Williams C = 150
1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 3-1/2 inch 4 inch
Q
720 psi 600 psi 540 psi 470 psi 470 psi 440 psi 380 psi 430 psi
Gallons
0.0060 A 0.0104 A 0.0141 A 0.0233 A 0.0332 A 0.0513 A 0.0687 A 0.0884 A
per min.
0.915 ID 1.230 ID 1.450 ID 1.875 ID 2.275 ID 2.800 ID 3.300 ID 3.626 ID
(3) For ASTM D2241, materials 1120, 1120 or 2120. These are the most commonly
used materials. Other materials have different ratings, see ASTM D2241.
Pressure rating is at 73.48 F.
Table 5.9
POLYETHYLENE (PE) SIDR-PR RATED PIPE
FRICTION LOSS ft/100 ft
ASTM D2239 (3)
Hazen Williams C = 145
Q 1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch 4 inch
Gallons 0.0060 A 0.0104 A 0.0141 A 0.0233 A 0.0333 A 0.0513 A 0.0884 A
per min. 1.049 ID 1.380 ID 1.610 ID 2.069 ID 2.469 ID 3.068 ID 4.026 ID
1 0.0820 0.0216 0.0102 0.0030 0.0013 0.0004 0.0001
2 0.2958 0.0778 0.0367 0.0109 0.0046 0.0016 0.0004
3 0.6268 0.1648 0.0778 0.0230 0.0097 0.0034 0.0009
4 1.0678 0.2808 0.1325 0.0393 0.0165 0.0057 0.0015
5 1.6142 0.4245 0.2004 0.0593 0.0250 0.0087 0.0023
6 2.2624 0.5950 0.2808 0.0832 0.0350 0.0122 0.0032
7 3.0099 0.7915 0.3736 0.1106 0.0466 0.0162 0.0043
8 3.8543 1.0136 0.4784 0.1417 0.0596 0.0207 0.0055
9 4.7937 1.2606 0.5950 0.1762 0.0742 0.0257 0.0069
10 5.8265 1.5322 0.7232 0.2142 0.0901 0.0313 0.0083
11 6.9512 1.8280 0.8628 0.2555 0.1075 0.0373 0.0099
12 8.1666 2.1476 1.0137 0.3002 0.1263 0.0439 0.0117
13 9.4714 2.4908 1.1757 0.3482 0.1465 0.0509 0.0135
14 (1) 2.8572 1.3486 0.3994 0.1681 0.0583 0.0155
15 (1) 3.2466 1.5324 0.4538 0.1910 0.0663 0.0176
16 (1) 3.6587 1.7269 0.5114 0.2152 0.0747 0.0199
17 (1) 4.0934 1.9321 0.5722 0.2408 0.0836 0.0223
18 (1) 4.5505 2.1478 0.6361 0.2677 0.0929 0.0247
19 (1) 5.0297 2.3740 0.7030 0.2959 0.1027 0.0273
20 (1) 5.5308 2.6106 0.7731 0.3253 0.1130 0.0301
21 (1) 6.0538 2.8574 0.8462 0.3561 0.1236 0.0329
22 (1) 6.5985 3.1145 0.9223 0.3881 0.1348 0.0359
23 (1) 7.1646 3.3817 1.0015 0.4214 0.1463 0.0389
24 (1) (1) 3.6590 1.0836 0.4560 0.1583 0.0421
25 (1) (1) 3.9464 1.1687 0.4918 0.1707 0.0455
(3) For ASTM D2239, material PE3408. This is the most commonly used material. Other
materials have different ratings, see ASTM D2239.
Table 5.10
HIGH DENSITY POLYETHYLENE (HDPE)
FRICTION LOSS ft/100 ft
ASTM D1248, Type III
Hazen Williams C = 150
1-1/2 inch 2 inch 1-1/2 inch 2 inch 1-1/2 inch 2 inch 1-1/2 inch 2 inch
Q
130 psi 130 psi 160 psi 160 psi 200 psi 200 psi 255 psi 255 psi
Gallons
SDR 13.5 SDR 13.5 SDR 11 SDR 11 SDR 9 SDR 9 SDR 7.3 SDR 7.3
per
0.0143 A 0.0220 A 0.0131 A 0.0203 A 0.0119 A 0.0183 A 0.0104 A 0.0159 A
min.
1.62 ID 2.01 ID 1.55 ID 1.93 ID 1.48 ID 1.83 ID 1.38 ID 1.71 ID
1 0.0093 0.0032 0.0115 0.0040 0.0144 0.0051 0.0202 0.0071
2 0.0335 0.0117 0.0415 0.0143 0.0520 0.0185 0.0731 0.0257
3 0.0709 0.0248 0.0879 0.0302 0.1101 0.0392 0.1548 0.0545
4 0.1208 0.0422 0.1498 0.0515 0.1876 0.0667 0.2637 0.0928
5 0.1826 0.0639 0.2264 0.0778 0.2835 0.1008 0.3987 0.1403
6 0.2559 0.0895 0.3173 0.1091 0.3974 0.1413 0.5588 0.1967
7 0.3405 0.1191 0.4222 0.1451 0.5287 0.1880 0.7434 0.2616
8 0.4360 0.1525 0.5406 0.1858 0.6771 0.2408 0.9519 0.3350
9 0.5422 0.1896 0.6724 0.2311 0.8421 0.2995 1.1839 0.4167
10 0.6590 0.2305 0.8172 0.2809 1.0235 0.3640 1.4390 0.5065
11 0.7863 0.2750 0.9750 0.3351 1.2211 0.4343 1.7168 0.6042
12 0.9237 0.3231 1.1454 0.3937 1.4346 0.5102 2.0170 0.7099
13 1.0713 0.3747 1.3285 0.4566 1.6638 0.5917 2.3392 0.8233
14 1.2289 0.4298 1.5239 0.5238 1.9085 0.6787 2.6833 0.9444
15 1.3964 0.4884 1.7316 0.5952 2.1686 0.7712 3.0490 1.0731
16 1.5737 0.5504 1.9514 0.6707 2.4439 0.8691 3.4361 1.2093
17 1.7606 0.6158 2.1832 0.7504 2.7343 0.9724 3.8443 1.3530
18 1.9572 0.6845 2.4270 0.8342 3.0396 1.0810 4.2736 1.5041
19 2.1633 0.7566 2.6826 0.9221 3.3597 1.1948 4.7236 1.6625
20 2.3789 0.8320 2.9499 1.0140 3.6945 1.3139 5.1943 1.8282
21 2.6038 0.9107 3.2288 1.1098 4.0438 1.4381 5.6855 2.0010
22 2.8381 0.9926 3.5193 1.2097 4.4076 1.5675 6.1970 2.1810
23 3.0816 1.0777 3.8213 1.3135 4.7858 1.7020 6.7287 2.3682
24 3.3343 1.1661 4.1346 1.4212 5.1783 1.8416 (1) 2.5624
25 3.5961 1.2577 4.4593 1.5328 5.5849 1.9862 (1) 2.7636
Table 5.11
IPS-ID POLYBUTYLENE WATER SERVICE PIPE
FRICTION LOSS ft/100 ft
ASTM D2662, SDR 11.5, 160 psi 0 73.48 F
Hazen Williams C = 150
Table 5.12
CPS (Copper Pipe Size) POLYBUTYLENE WATER SERVICE PIPE
FRICTION LOSS ft/100 ft
ASTM D2666, SDR 13.5, 160 psi @ 73.408 F
Hazen Williams C = 150
Table 5.13
CPS (Copper Pipe Size) POLYBUTYLENE WATER SERVICE PIPE
FRICTION LOSS ft/100 ft
ASTM D2666, SDR 9, 250 psi 0 73.40 F
Hazen Williams C = 150
Table 5.14
BLACK OR GALVANIZED STEEL PIPE
FRICTION LOSS ft/100 ft
Schedule 40 (Standard)
Seamless & Electric Welded ASTM A120
Hazen Williams C = 100
1/2 inch 3/4 inch 1 inch 1-1/4 inch 1-1/2 inch 2 inch 2-1/2 inch 3 inch
Q
350 psi 350 psi 350 psi 500 psi 500 psi 500 psi 500 psi 500 psi
Gallons
0.0021 A 0.0037 A 0.0060 A 0.0104 A 0.0141 A 0.0233 A 0.0332 A 0.0513 A
per min.
0.622 ID 0.824 ID 1.049 ID 1.380 ID 1.610 ID 2.067 ID 2.469 ID 3.068 ID
1 2.0792 0.5285 0.1631 0.0429 0.0202 0.0060 0.0025 0.0009
2 7.5050 1.9077 0.5886 0.1548 0.0731 0.0216 0.0091 0.0032
3 15.9018 4.0420 1.2472 0.3280 0.1548 0.0458 0.0193 0.0067
4 27.0903 6.8859 2.1248 0.5588 0.2637 0.0781 0.0329 0.0114
5 40.9521 10.4094 3.2120 0.8447 0.3987 0.1181 0.0497 0.0173
6 57.3995 14.5900 4.5020 1.1839 0.5588 0.1655 0.0696 0.0242
7 76.3630 19.4103 5.9894 1.5751 0.7434 0.2202 0.0926 0.0322
8 97.7858 24.8556 7.6696 2.0170 0.9520 0.2819 0.1186 0.0412
9 121.6193 30.9137 9.5390 2.5085 1.1840 0.3506 0.1476 0.0512
10 (1) 37.5740 11.5941 3.0490 1.4391 0.4262 0.1793 0.0623
11 (1) 44.8270 13.8322 3.6376 1.7169 0.5085 0.2140 0.0743
12 (1) 52.6646 16.2506 4.2736 2.0171 0.5973 0.2514 0.0873
13 (1) 61.0791 18.8470 4.9564 2.3394 0.6928 0.2915 0.1012
14 (1) 70.0639 21.6194 5.6855 2.6836 0.7947 0.3344 0.1161
15 (1) 79.6125 24.5658 6.4603 3.0493 0.9030 0.3800 0.1319
16 (1) 89.7194 27.6845 7.2804 3.4364 1.0176 0.4283 0.1487
17 (1) (1) 30.9738 8.1455 3.8447 1.1386 0.4791 0.1663
18 (1) (1) 34.4321 9.0549 4.2739 1.2657 0.5326 0.1849
19 (1) (1) 38.0581 10.0085 4.7240 1.3990 0.5887 0.2044
20 (1) (1) 41.8504 11.0058 5.1948 1.5384 0.6474 0.2248
21 (1) (1) 45.8077 12.0465 5.6860 1.6838 0.7086 0.2460
22 (1) (1) 49.9289 13.1303 6.1975 1.8353 0.7723 0.2681
23 (1) (1) 54.2129 14.2569 6.7293 1.9928 0.8386 0.2912
24 (1) (1) 58.6585 15.4260 7.2811 2.1562 0.9074 0.3150
25 (1) (1) 63.2648 16.6373 7.8529 2.3255 0.9786 0.3398
(3) It is good design practice to design steel pipe operating pressure for not more that 50%
of test pressure. The pressures shown are 50% of ASTM A120 test pressures.
Table 5.15
BLACK OR GALVANIZED STEEL PIPE
FRICTION LOSS ft/100 ft
Schedule 80 (Standard)
Seamless & Electric Welded ASTM A120
Hazen Williams C = 100
1/2 inch 3/4 inch 1 inch 1-1/4 inch 1-112 inch 2 inch 2-1/2 inch 3 inch
Q
424 psi 425 psi 425 psi 750 psi 750 psi 750 psi 750 psi 750 psi
Gallons
0.0016 A 0.0030 A 0.0050 A 0.0089 A 0.0123 A 0.0205 A 0.0294 A 0.0459 A
per min.
0.546 ID 0.742 ID 0.957 ID 1.278 ID 1.500 ID 1.939 ID 2.323 ID 2.900 ID
1 3.9223 0.8805 0.2550 0.0623 0.0286 0.0082 0.0034 0.0012
2 14.1580 3.1784 0.9204 0.2250 0.1031 0.0295 0.0123 0.0042
3 29.9983 6.7346 1.9503 0.4767 0.2185 0.0626 0.0260 0.0088
4 51.1052 11.4730 3.3225 0.8122 0.3723 0.1066 0.0442 0.0150
5 77.2552 17.3436 5.0226 1.2278 0.5628 0.1612 0.0669 0.0227
6 108.2829 24.3093 7.0397 1.7209 0.7888 0.2259 0.0937 0.0318
7 144.0573 32.3405 9.3655 2.2894 1.0494 0.3006 0.1247 0.0423
8 (1) 41.4133 11.9929 2.9317 1.3438 0.3849 0.1596 0.0542
9 (1) 51.5070 14.9160 3.6462 1.6713 0.4787 0.1986 0.0674
10 (1) 62.6040 18.1296 4.4318 2.0314 0.5818 0.2413 0.0819
11 (1) 74.6888 21.6292 5.2872 2.4235 0.6942 0.2879 0.0977
12 (1) 87.7474 25.4108 6.2117 2.8472 0.8155 0.3383 0.1148
13 (1) 101.7673 29.4709 7.2041 3.3022 0.9458 0.3923 0.1332
14 (1) (1) 33.8060 8.2639 3.7879 1.0850 0.4500 0.1527
15 (1) (1) 38.4133 9.3901 4.3041 1.2328 0.5114 0.1736
16 (1) (1) 43.2899 10.5822 4.8506 1.3893 0.5763 0.1956
17 (1) (1) 48.4333 11.8395 5.4269 1.5544 0.6447 0.2188
18 (1) (1) 53.8411 13.1614 6.0328 1.7280 0.7167 0.2433
19 (1) (1) 59.5110 14.5474 6.6681 1.9099 0.7922 0.2689
20 (1) (1) 65.4410 15.9970 7.3325 2.1003 0.8711 0.2957
21 (1) (1) 71.6290 17.5097 8.0259 2.2989 0.9535 0.3236
22 (1) (1) 78.0733 19.0850 8.7480 2.5057 1.0393 0.3528
23 (1) (1) (1) 20.7225 9.4986 2.7207 1.1285 0.3830
24 (1) (1) (1) 22.4218 10.2775 2.9438 1.2210 0.4144
25 (1) (1) (1) 24.1825 11.0845 3.1749 1.3169. 0.4470
(3) It is good design practice to design steel pipe operating pressure for not more that 50%
of test pressure. The pressures shown are 50% of ASTM A120 test pressures.
Table 5.16
Estimated Upper Limit Working Pressures for
Schedule 40 and Schedule 80 PVC Fittings
Schedule 40 Schedule 80
Nominal Outside Pressure Rating Pressure Rating
Diameter Diameter Burst Working Burst Working
(in) (in) (psi) (psi) (psi) (psi)
1/2 0.840 1910 358 2720 509
3/4 1.050 1540 289 2200 413
1 1.315 1440 270 2020 378
1-1/4 1.660 1180 221 1660 312
1-1/2 1.900 1060 198 1510 282
2 2.375 890 166 1290 243
2-1/2 2.875 970 182 1360 255
3 3.500 840 158 1200 225
TABLE OF CONTENTS
FIGURES
CHAPTER 6
PRESSURE AND SURGE CONTROL
Figure 6.1
TYPICAL PRESSURE REDUCING VALVE INSTALLATION
Figure 6.2 illustrates construction of a typical pressure reducing valve and a manufacturer
design chart.
Figure 6.2
PRESSURE VALVE PARTS AND DESIGN CHARTS
The valve illustrated in Figure 6.2 has a built-in strainer. Pressure reducing valves will not
operate properly if debris gets into the mechanism. If sediment and debris are a problem in the
pipeline, a more elaborate filter system may be required.
In designing a pressure reducing valve, the general rule is that velocity through the valve should
not exceed ten feet per second. Manufacturer's charts show the maximum capacity for each
size of valve based on design velocity.
There is a pressure reducing valve pressure loss called "Fall-off" that must be considered in the
design. When no flow is passing through the valve, there is zero fall-off. When maximum rated
flow is passing through the valve, there is up to 20 psi pressure fall-off. So if the pressure
reducer is set at 75 psi at no flow, the static hydraulic grade line would be at (75 x 2.31) = 173
feet above valve elevation. If the valve were to operate at design flow, hydraulic grade line
would start at the valve at [(75 - 20) x 2.31] = 127 feet above valve elevation.
When a pressure-reducing valve is used in a design, the plans should indicate, as a minimum,
the pressure differential and the allowable “fall-off” pressure for the design flow rate. This
information will be sufficient to allow the installer to obtain the appropriate valve from the
supplier.
Use of more than one pressure-reducing valve in a pipeline may result in oscillating pressures if
misused or improperly installed. When more than one pressure-reducing valve is used, the
design shall be approved by an engineer with appropriate job approval authority.
Figure 6.2 illustrates typical manufacturer information concerning valve fall-off values.
6.1.3 Grade Break at Tank
Starting a gravity pipeline at a tank is one positive way of controlling pressure in a segment of
pipeline. If the float valve hangs up, the tank simply overflows. Both static and dynamic
hydraulic grade line starts at the water surface in the tank. Only a usually insignificant pipeline
entrance loss is experienced under design flow.
Figure 6.3 illustrates one type of tank/float valve installation. This is a small tank with a float
valve used strictly for pressure regulation. A stock tank can be used in the same way.
Figure 6.3
FLOAT VALVE BOX
Figure 6.4
OPERATION OF A SURGE CHAMBER
Sometimes when pressure at the pump is very high, a normal pressure tank cannot be used. In
that case, it may be necessary to install a high pressure rated diaphragm-type pressure tank or
specially designed surge chamber. These are expensive but may be needed in high pressure
automatic systems.
It is sometimes proposed that a homemade surge chamber be installed. This is a piece of pipe
capped at one end and an air valve installed in the outer end. The chamber is filled with
compressed air after the system is pressurized with water.
Homemade surge chambers are not recommended. Experience and studies have shown that
this type of chamber soon waterlogs and becomes completely ineffective.
6.2.2 Minimize Frequency of Pump Cycles
Minimize the frequency of turning the pump on or off. This will reduce the number of surges that
pipeline and system will have to endure. This can be accomplished by increasing pressure tank
storage. Figure 6.5 illustrates a remote multiple tank setup for increased storage.
Figure 6.5
REMOTE MULTI-TANK INSTALLATION
Remote tanks can generate problems of their own. When the remote tank is far out on the
pipeline, hydraulic conditions can be such that during initial pump flow, friction loss in the pipe
will cause pressure to buildup to cut out pressure and turn the pump off before the remote tanks
have filled to design pressure. As pressure in the system equalizes, the pump will again start.
A rapid cycling can be set up which can be very destructive to pump and pipeline.
If this problem is encountered, one solution is to install an adjustable flow rate control valve
in the pipeline near the pump. With this valve, flow rate is adjusted downward until rapid
cycling is stopped. Figure 6.6 illustrates this type of installation and two types of flow rate
control valves. The valves shown are expensive.
Sometimes rubber orifice flow control valves of the type used to control flow to sprinkler
heads or trickle system laterals in irrigation systems can be used to control flow in
moderate pressure systems. These non-adjustable flow control valves are inexpensive.
There is a pressure regulator/pressure switch combination valve which works so that once
the pump comes on, it will not shut off until all flow in the system has stopped. This
guarantees that the pump will not cycle except between flow events. Figure 6.7 illustrates
this type of valve. There are two models with different flow rate ratings. At least two pump
manufacturers supply this type of valve as an accessory.
If either of the above two valves are used, make sure that the pressure rating of the pipe
between the pump and the valve is high enough to withstand the maximum pressure the pump
is capable of generating. This will require a review of the pump curve. With these types of
valves, the pressure between pump and valve will reach the maximum that the pump is able to
generate.
(3) Pump Cycle Timer
Another possible solution is to install short period timers in conjunction with the pressure
switch. The timer is set in a manner that will force minimum pump on or off cycle times. It
will be especially important to have adequate pressure tank storage; tank, pipe and
accessories rated for maximum pump pressure and pressure relief valves installed if this
alternative is selected.
Figure 6.6
FLOW RATE CONTROLLER VALVES
Figure 6.7
FLOW CONTROLLED PRESSURE SWITCH
Example 2: Use equation 6.3 to determine the pressure surge in a pipeline flowing a 1.3 fps
due to a sudden valve closure. The pipe material is SDR 26, PVC.
Ps∆V=1 fps = 14.4 psi/fps Table 6.1
Ps = 1.3 fps x 14.4 psi/fps = 19.1 psi Equation 6.3
AIR CONTROL
NE Stockwater Pipeline Handbook Air Control
TABLE OF CONTENTS
FIGURES
7.1 GENERAL
Air trapped in stockwater pipelines can reduce or even completely stop the flow of water in the
line. This is particularly a critical problem in long pipelines and those that operate under very
low pressure.
• There are various forms of gasses in well waters. These gases can come out of solution
during pipeline operation. Some wells have more serious gas problems than others.
• If the water level in a well or other source falls below the pump intake, air is drawn into
the pipeline by the pump.
• In gravity systems, air can be drawn into the pipeline when water surface falls below the
pipeline entrance.
Figure 7.1
RELEASING AIR FROM PIPELINE
Figure 7.1 illustrates what happens when air is trapped at a high point in a pipeline. A bubble is
formed at the high point. The effect is to reduce the cross-sectional area of the pipeline and
thus restrict flow. This has the same effect as inserting a short length of smaller diameter pipe
in the pipeline. Velocity accelerates through the smaller section of pipe and friction loss is
increased. Since friction loss is a function of the square of velocity, friction loss can increase
significantly when a large bubble is present. If the bubble is large enough or there are many of
them, flow can be shut off completely.
As velocity increases, the air pocket tends to be pushed down the pipe in some sort of
elongated bubble. There may be several separate bubbles formed. If velocities are high
enough and elevation difference to the next low point is not too great, the bubble may be
pushed through to the next high point or outlet.
• Install the pipe so there are no summits in the line. Carefully lay out the pipe so it is on
either a constantly increasing or decreasing grade.
For very low pressure pipelines, experience indicates that minimum pipe diameter should be:
1-1/4 inch nominal diameter for grades over 1.0 percent.
1-1/2 inch nominal diameter for grades from 0.5 to 1.0 percent.
2 inch nominal diameter for grades from 0.2 to 0.5 percent.
For grades less than 0.2 percent, gravity flow systems are not recommended. Where pipe of
minimum size will not deliver the required flow, the size should be increased.
Cleaning may be made easier by placing "T's" or "Y's" with plugs at strategic points in the
pipeline.
Outlet pipes from a spring box should be placed at least 6 inches above the box floor to allow
for sediment storage. A tee and vent pipe or a screen should be installed on the pipe within the
spring box to reduce plugging by leaves and trash.
Pipes starting at storage tanks or ponds should be screened and placed far enough above the
tank bottom to prevent sediment from entering the system. Screens should be made of copper,
plastic, or stainless steel. A swivel-elbow arrangement connected to a float will alleviate both
bottom sediment and surface trash problems associated with ponds and large open storage
tanks.
• Install air valves at summits to control the entry and exhausting of air. Figure 7.2
shows this type of installation.
Figure 7.2
TYPICAL SYSTEM WITH AIR VALVES
Figure 7.3 illustrates how a typical air valve operates. Since there is no water in the valve
chamber, the float drops on to a cage and allows air to enter the large orifice.
Figure 7.3
VACUUM RELIEF
2. When an empty pipe is filled with water, air in the line must be released in large volumes.
This can be done by leaving the hydrants open. But what if the hydrants are closed? Air
pressure will build up in the pipeline. When a hydrant or float valve is opened, high
pressure air will escape and then, when water hits the end of the line, water hammer will
probably occur.
For adequate system protection, there must be a mechanism to automatically release large
volumes of air from the pipeline during filling. For best results, the mechanism should be
located at all significant summits in the line.
Figure 7.4 illustrates how a typical air valve functions. Since water has not yet entered the
valve chamber, the float stays down on a cage. Large volumes of air escape through the
large orifice.
When the pipe fills, the float floats to the top of the valve and closes the large orifice. The
valve then remains closed until the pipeline is again empty. The float will not drop unless
pressure drops to zero, since pressure keeps it seated against the orifice. This is the case
even if an air pocket builds up in the valve chamber during operation.
Figure 7.4
RELEASE OF LARGE VOLUMES OF AIR DURING FILLING
Figure 7.5
WATER AND PRESSURE KEEP FLOAT VALVE CLOSED
3. During operation of the pipeline, air bubbles and other gasses come out of solution and
buildup as gas bubbles at summits in the line. There are usually also remnants of the large
volumes of air present immediately after filling. If the summit is high enough, this air will
never push on through the line. Gases may eventually buildup to the point where the flow
rate is seriously reduced or flow may even stop. It is not possible to predict how serious a
problem this may be when designing a pipeline.
Figure 7.6 illustrates how a typical air release valve works. A heavy float and a small orifice
allow the float to drop and open the orifice even when the system is under pressure. So
when air bubbles gravitate to the air chamber, and the float drops, high pressure air is
expelled from the valve.
Figure 7.6
AIR RELEASE VALVE
FOR RELEASING AIR WHILE PIPE IS UNDER PRESSURE
In the past, there have been long high pressure stockwater lines installed with little or no
provision for air venting. Many of these systems work. A line that has worked for years will
sometimes slow down or stop. The usual culprit is air in the line.
Long stockwater pipelines are expensive. The cost of installing adequate air handling
equipment during initial installation is a relatively small part of total installation cost. The cost of
installing air valves is much less in the initial installation than going back later to add needed
valves. Adequate air handling equipment should always be designed into a system at the time
of initial installation.
In high pressure, moderate flow systems, there are frequently many small undulations in the
ground surface and a few large peaks, causing air bubbles to be trapped in the summits. For
pipelines larger than 1-1/4 inch diameter, consideration should be given to installing air release
valves at the smaller summits. Because the velocity in larger diameter pipelines is slower, less
air bubbles will be carried from higher peaks. By installing additional hydrants or air release
valves, the potential for air entrapment problems is reduced.
In most cases, air handling equipment such as a COMB or 3-way valve should be installed on
all summits of 20 feet or more, at the end of the pipeline, and at the first high point of any kind
past the pump. A particularly important location for a continuous acting air release valve is the
first high point past the pump. This valve will catch and release most gas introduced by the
pump.
If the pipeline goes downhill from the well, it would be advisable to locate the COMB valve right
after the pressure tank (within 10 feet).
Ignoring summits which are less than 20 feet may occasionally lead to system operational
problems. In that case, the owner will have to go back and install air valves or vents at all
summits. So far, the risk involved in using this rule of thumb has proved acceptable.
Remember that it is not acceptable to ignore summits in the line in low head, low velocity
pipelines.
The preferred locations for air venting are at high points in the line. Hydrants, open vents, or
vacuum relief valves can be used. Where the hydraulic grade line is close to pipe elevation,
open air vents are the best choice. Hydrants can be used if they are always opened at the time
of draining and filling of the pipeline. The risk of using hydrants is that there may be additional
damage to the line if a sudden pipeline break should unexpectedly drain the line.
For long pipelines, pipelines installed in undulating terrain, or pipelines with long intervals
between valves or tanks, additional valves may be needed. For these situations, contact the
Field Engineer or Civil Engineering Technician for assistance.
2. Air relief/vacuum relief valve (ARV or 2-way valves): These valves relieve vacuum during
emptying and expel large volumes of air during filling.
4. Combination air/vacuum relief, air release (COMB or 3-way valves). These valves combine
all 3 of the above mentioned valve functions into one valve.
The latter three types of valves are usually used in stockwater pipelines. The smallest valves
available are usually adequate. Valves are rated according to maximum pressure that they can
operate under as well as by orifice size. Only appropriate pressure rated valves should be
used.
Figures 7.5 through 7.9 illustrate cutaway views of typical air valves used in stockwater
pipelines. Different manufacturers have different ways of doing the same job. Some valves are
made of plastic. These generally are adequate for low pressure operation. The cast iron
models are for high pressure operation.
It is sometimes claimed that the air release (small orifice) valve will also serve the purpose as
vacuum relief valve. The small orifice is not adequate to prevent high vacuum from occurring if
there is a sudden break or during emptying of the pipeline. The proper kind of valves should be
used where needed.
In most cases, the combination (three-way) valve should be installed at all significant summits.
An air release valve will suffice at small summits. At the end of the line an air release/vacuum
(two-way) valve should be installed.
Figure 7.7
TYPICAL AIR RELEASE VALVES
Figure 7.8
TYPICAL AIR RELIEF/VACUUM VALVES (TWO WAY)
Figure 7.9
TYPICAL AIR/VAC/AIR RELEASE VALVES (THREE WAY)
Figure 7.10
AIR VALVE INSTALLATION
TABLE OF CONTENTS
FIGURES
TABLES
Figure 8.1
TYPICAL SPRING BOX AND PIPE COLLECTION
Figure 8.2
TYPICAL SPRING BOX DIRECT COLLECTION
Figure 8.3
WATER COLLECTION WITHOUT SPRING BOX
PLAN
Note: Instead of a "T", a "Y" may be installed with the riser at a 45 degree angle with the
ground. This will allow using a snake to clean out the perforated drain pipe.
PROFILE
Figure 8.4
TYPICAL SPRING FED PIPELINE
8.3 PUMPS
There are many kinds of pumps used in stockwater pipelines. The best alternative depends on
available sources of power, flow rate and head requirements, and water source.
Availability of electric power is frequently a major factor in determining whether or not an electric
pump can be used. If power is not already available at the water source, it can be very
expensive to provide. Two major considerations when planning a stockwater system requiring
pumping are electric power availability and cost of providing electric power.
NE-NRCS DOES NOT determine which pump will be required for a pipeline to operate
satisfactorily. This is the responsibility of the pipeline owner after the necessary information has
been supplied as part of the design. With the proper information, the pump can be selected by
the owner or installer.
It is good practice to the review the pump selected by the operator to assure that the system will
function as designed.
The selection of the proper pump is based on the following information:
• Required discharge
• Pipeline operating pressure requirements
• Total head
The total head is obtained by adding the maximum required pressure at the well (in feet) to the
depth to the ground water. If the depth of well drawdown is known from the well installation, this
depth should be added also.
Pump Curves
The pump should be able to supply the design flow rate at the maximum operating pressure. A
pump curve is used to assure this requirement is met. The example pump curve shown on page
8-8 is valid only for the specific pump models for which it was developed (in this case, 18 GPM
SUBMERSIBLE SERIES “CC”). Therefore, to evaluate if a pump meets the design
requirements, the pump curve for the installed pump should be obtained from the pump installer
or manufacturer.
Example:
Given: Required discharge 10 gpm
Operating pressure required 60-80 psi
Depth to water table 120 feet
Drawdown 10 feet
From Figure 8.7, for 10 gpm and 315 feet of head, a 1 1/2 HP, model 11CC will meet these
design requirements.
The objective of a properly sized pump for a livestock pipeline system is to supply the required
flow rate at the required pressure while minimizing pump cycling, or stopping and starting.
Installing a pump with horsepower rating which is too large or too small may cause significant
problems with the system.
A pump with a horsepower rating too large may pump water to the open hydrant or tank faster
than the pipeline design velocity. The resulting surge of water will cause a temporary rise in the
friction loss and pressure. This elevated pressure can cause the pump to cycle off prematurely
(by reaching the "pump off" pressure) even though the tank float is still open. Once the surge of
water dissipates, the friction loss decreases until the pressure drops to the "pump on" pressure
and the well cycles on again, resulting in another surge of water. Cycling the pump on and off
too frequently can dramatically shorten the life of the pump, sometimes causing the pump to
burn out.
If a 3 HP-19CC pump was selected for the previous example, the pump would supply
approximately 21 gpm at 315 feet of head. The friction loss would increase and the pressure
would rise. At 10 gpm, the pump would supply 550 feet of operating head. Thus the pump
would cycle off by reaching the "pump off" pressure. This also illustrates the importance of
using a pressure switch. If the system did not have a pressure switch or if the switch
malfunctioned, the 3 HP pump could supply enough pressure head to rupture the pipe.
A pump with a horsepower rating too small may either supply less than the designed flow rate or
may not supply water to all pipeline locations.
A properly designed pipeline system will provide water at the design flow rate. It should never
be necessary to increase the pressure switch settings. If the installed pipe material or pipe size
is different than the design, the proper switch settings can be calculated. Arbitrarily increasing
pressure settings to increase flow rate can cause problems with the system including pipe
failure, decreased pipe life, or inadequate flow rate delivery.
8.3.1 Submersible Electric Pump
Figure 8.5 illustrates a typical submersible pump. This is the best type of pump for deep wells.
Some submersible pumps have a built-in check valve in the pump. It is a good idea though,
particularly on high-pressure systems, to install another separate check valve on the pump side
of the pressure tank.
Figure 8.6 illustrates a typical submersible pump system using a pitless adapter. Figure 8.7
illustrates a typical submersible pump curve.
Figure 8.5
SUBMERSIBLE PUMP
Figure 8.6
TYPICAL WELL WITH PITLESS ADAPTER AND SUBMERSIBLE PUMP
Figure 8.7
TYPICAL SUBMERSIBLE PUMP CURVE
Figure 8.8
HOW A JET PUMP WORKS
Figure 8.9
TYPICAL JET PUMP INSTALLATION AND CAPACITY TABLE
Figure 8.10
TYPICAL TURBINE BOOSTER PUMP
Figure 8.11
THREE PISTON PUMP
Figure 8.12
WINDMILL AS SUPPLY TO TANK
Figure 8.13 shows how to connect a windmill to a pipeline. When designing a windmill supplied
pipeline the total dynamic head equals static head plus losses in the drop pipe plus pipeline
losses.
Figure 8.13
WINDMILL CONNECTED TO PIPELINE
Table 8.1 tabulates approximate windmill capacities, and Table 8.2 tabulates approximate
pumping heads. These are based on winds exceeding 12 mph. Short stroke systems increase
pumping head by 1/3 and reduce pumping capacity by 1/4.
For 12 mph winds, capacity is reduced about 20% and for 10 mph winds, about 38%. If
prevailing winds are low, use of a cylinder smaller than shown will permit the mill to operate in
lower wind velocity.
The drop pipe should never be smaller than the pump cylinder. For deep wells, use a ball valve
and lightweight rod.
Table 8.1
APPROXIMATE WINDMILL CAPACITY
Table 8.2
WINDMILL PUMPING HEAD
Figure 8.14
WIND GENERATOR POWERED PUMP
Figure 8.15
TYPICAL SOLAR SUBMERSIBLE PUMP GRAVITY SYSTEM
Figure 8.16
Solar Powered Pump Jack
2. An engine operated generator which in turn operates any type of electrically driven pump
system. This type of system either be automatically started and stopped with a float switch
or manually started and shut off by a float actuated switch in the storage tank. Figure 8.17
illustrates what a typical generating system may look like.
This system has the advantage of being able to operate any size or pressure rated pump,
depending on the size of the generating system.
Figure 8.17
PROPANE POWERED, AUTOMATIC GENERATOR FOR PUMP
Figure 8.18
TYPICAL HYDRAULIC RAM INSTALLATION
Figure 8.19
SMALL PLASTIC HYDRAULIC RAM
Figure 8.20
LARGE STEEL HYDRAULIC RAMS
Figure 8.21
HOW A PRESSURE TANK WORKS
Cut-in pressure is that pressure at which the pump is automatically turned on. Cut-out is the
pressure at which the pump is turned off.
Tanks operating with a cut-out pressure of less than 80 psi usually have a 20 psi pressure
spread between cut-in and cut-out. Tanks operating at pressures higher than that usually
operate with a pressure spread of 30 psi. At pressures above 120 psi, it sometimes may be
advantageous to operate with a pressure spread greater than 30 psi. See Tables 8.3 through
8.12 for tank sizes based on flow rate and pressure spread between cut-in and cut-out.
More than one tank may be installed in a system to meet pressure tank capacity requirements.
Figure 8.22 illustrates how this is done.
Figure 8.22
MULTIPLE PRESSURE TANK INSTALLATION
Figure 8.23
PLAIN PRESSURE TANK CAPACITY
It is very dangerous to use a tank at higher than its rated pressure. A tank used beyond its
rating could explode and cause death or serious injury to anyone working near the tank. For
that reason a pressure tank should never be used beyond its rated pressure.
Sometimes owners want to use "used" tanks such as old propane tanks as water pressure
tanks. These tanks are not designed for water use since they will soon corrode and weaken.
Pressure tanks not manufactured for water containment should not be used.
Special pressure tanks are available with ratings beyond 110 psi. These are expensive and
must be properly sized.
In any automatic high pressure system, additional efficient storage can be added by installing
multiple diaphragm-type pressure tanks out on the pipeline where pressures are relatively low.
These tanks are usually the buried-type. In such a system, it is desirable to have a primary high
pressure tank located at the well. This tank takes the initial surge of flow and allows flow and
pressures to equalize in the pipeline.
It also may be effective to install a flow regulating valve just up stream of the pressure switch to
control initial flow rate. Without control of surge flow at the pump, frequent pump cycling can
occur due to pressure surges actuating the pressure switch. This can quickly destroy the pump
and/or pipeline.
Table 8.3
DIAPHRAGM PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
Flow = 5 gpm, Minimum Pump Running Time = 1.5 minutes
Pump
CUT- Pump CUT-IN Pressure (PSIG)
OUT
Pressure 20 30 40 50 60 70 80 90 100 110 120 130 140
(PSIG)
30 33
40 20 41
50 16 24 48
60 14 19 28 56
70 13 16 21 32 64
80 12 14 18 24 36 71
90 11 13 16 20 26 39 78
100 11 12 14 17 22 29 43 86
110 10 12 13 16 19 23 31 47 94
120 10 11 13 14 17 20 25 34 50 107
130 10 11 12 14 15 18 22 27 36 54 109
140 10 11 12 13 15 17 19 23 29 39 58 117
150 10 10 11 12 14 15 18 21 25 31 41 62 125
Table 8.4
DIAPHRAGM PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
Flow = 10 gpm, Minimum Pump Running Time = 1.5 minutes
Pump
CUT- Pump CUT-IN Pressure (PSIG)
OUT
Pressure 20 30 40 50 60 70 80 90 100 110 120 130 140
(PSIG)
30 67
40 41 82
50 32 49 97
60 28 37 56 112
70 25 32 42 64 127
80 24 28 36 47 71 142
90 22 26 31 39 52 79 156
100 21 25 29 34 43 57 86 172
110 21 23 27 31 37 47 62 94 188
120 20 22 25 29 34 40 51 67 101 214
130 20 22 24 27 31 36 43 54 72 109 217
140 19 21 23 26 29 33 39 46 58 77 116 234
150 19 21 22 25 27 31 35 41 49 62 82 124 250
Table 8.5
DIAPHRAGM PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
Flow = 15 gpm, Minimum Pump Running Time = 1.5 minutes
Pump
CUT- Pump CUT-IN Pressure (PSIG)
OUT
Pressure 20 30 40 50 60 70 80 90 100 110 120 130 140
(PSIG)
30 100
40 61 123
50 48 73 145
60 42 56 84 168
70 38 48 64 95 191
80 35 43 53 71 107 212
90 34 39 47 59 78 118 234
100 32 37 43 52 65 86 129 259
110 31 35 40 47 56 70 93 141 281
120 30 34 38 43 50 61 76 101 151 321
130 30 33 36 41 46 54 65 81 108 163 326
140 29 32 35 39 44 50 58 69 87 116 174 352
150 29 31 34 37 41 46 53 62 74 93 124 186 375
Table 8.6
DIAPHRAGM PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
Flow = 20 gpm, Minimum Pump Running Time = 1.5 minutes
Pump
CUT- Pump CUT-IN Pressure (PSIG)
OUT
Pressure 20 30 40 50 60 70 80 90 100 110 120 130 140
(PSIG)
30 134
40 82 164
50 65 97 194
60 56 75 112 224
70 51 64 85 127 254
80 47 57 71 95 142 283
90 45 52 63 79 105 157 313
100 43 49 57 69 86 115 172 345
110 41 47 53 62 75 93 124 188 375
120 40 45 51 58 67 81 101 135 201 429
130 39 43 48 54 62 72 87 108 144 217 435
140 39 42 46 52 58 66 77 93 116 155 233 469
150 38 41 45 49 55 62 70 82 98 123 165 248 500
Table 8.7
DIAPHRAGM PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
Flow = 25 gpm, Minimum Pump Running Time = 1.5 minutes
Pump
CUT- Pump CUT-IN Pressure (PSIG)
OUT
Pressure 20 30 40 50 60 70 80 90 100 110 120 130 140
(PSIG)
30 167
40 102 205
50 81 121 242
60 70 93 140 280
70 64 79 106 159 318
80 59 71 89 118 178 354
90 56 65 78 98 131 196 391
100 54 61 72 86 108 144 216 431
110 52 58 67 78 94 117 156 234 469
120 51 56 63 72 84 101 126 168 252 536
130 49 54 60 68 77 90 108 135 180 272 543
140 48 53 58 64 73 83 97 116 145 193 291 586
150 48 51 56 62 69 77 88 103 123 154 206 310 625
Table 8.8
PLAIN PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
(Based on 3,000 ft. elevation above sea level)
WITHOUT AIR VALVE
NOTES:
(1) If an automatic air charge valve is used, tank size may be reduced by 50%.
(2) Increase tank size by 5% for each 1,000 feet elevation above 3,000 feet elevation.
Table 8.9
PLAIN PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
(Based on 3,000 ft. elevation above sea level)
WITHOUT AIR VALVE
NOTES:
(1) If an automatic air charge valve is used, tank size may be reduced by 50%.
(2) Increase tank size by 5% for each 1,000 feet elevation above 3,000 feet elevation.
Table 8.10
PLAIN PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
(Based on 3,000 ft. elevation above sea level)
WITHOUT AIR VALVE
NOTES:
(1) If an automatic air charge valve is used, tank size may be reduced by 50%.
(2) Increase tank size by 5% for each 1,000 feet elevation above 3,000 feet elevation.
Table 8.11
PLAIN PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
(Based on 3,000 ft. elevation above sea level)
WITHOUT AIR VALVE
NOTES:
(1) If an automatic air charge valve is used, tank size may be reduced by 50%.
(2) Increase tank size by 5% for each 1,000 feet elevation above 3,000 feet elevation.
Table 8.12
PLAIN PRESSURE TANK SIZE SELECTION
MINIMUM RECOMMENDED TOTAL STORAGE TANK SIZE (gallons)
NOTES:
(1) If an automatic air charge valve is used, tank size may be reduced by 50%.
(2) Increase tank size by 5% for each 1,000 feet elevation above 3,000 feet elevation.
An accurate pressure gauge is a very important accessory for a pressure pipeline. With a good
pressure gauge, problems such as leaks, pump wear and pressure surges can be identified.
Frequently, low cost pressure gauges are used. They last a very short time in the damp
atmosphere of most pump enclosures. For a nominal fee, a good liquid filled gauge with a
stainless steel case can be obtained and is highly recommended.
Figure 8.24
FLOAT SWITCH PUMP CONTROL
A mechanism to control a pump based on water levels in both the well and tank is shown in
Figure 8.25. This should be used where water level in the well must control the pump.
Figure 8.25
SWITCH CONTROL OF
WATER LEVEL IN STORAGE TANK AND IN WELL
Figure 8.26
REMOTE TANK FLOAT OPERATED SWITCHING EQUIPMENT
Figure 8.27
WATER LEVEL CONTROL SWITCHES
Concrete is one of the most durable materials that can be used to build stock tanks. To be
durable though, concrete must be made and placed properly. The two environmental factors
that will rapidly deteriorate concrete are freeze thaw action and sulfates in the water.
High sulfate concentrations are present in many waters used for stock-watering in the west. It is
important to become aware of this if you are working in an area where sulfate is a problem.
Since stock tanks are often used during freezing weather, they are in an ideal environment for
damage due to freezing and thawing. Pores in the concrete fill with water, freeze, and as a
result the concrete will spall.
There are practical things that should be done to make quality concrete that will resist these
elements:
1. Use a low water cement ratio. Use the minimum amount of water in the concrete that is
possible consistent with being able to place the concrete. Use a minimum of 6 bags of
cement per cubic yard of concrete.
2. Place the concrete within 1-1/2 hours after adding water to the cement. This is sometimes
a challenge when using readymix concrete at remote sites. If travel time between batch
plant and the site is a problem, add the cement and water at the site. Adding water to
make concrete placeable after it has been in the truck too long is a leading cause of poor
concrete.
3. Use air entrained concrete with air content within NRCS specification range. Air
entrainment can be obtained by using cement with built-in air entrainment additives or by
adding admixtures at the concrete batch plant. Cement with air additives built-in is cement
type IIA.
Foundation frost heave can also be a problem, particularly if the foundation is wet when the
ground freezes. The solution is to build the tank so there will be good drainage away from the
tank, provide proper overflow drains for the tanks, and provide a well drained base material
under the tank.
Figure 8.28 illustrates a typical concrete tank. Figure 8.29 details a concrete trough. Figure
8.30 illustrates a tank made out of a section of large diameter concrete pipe. Figure 8.31 shows
plans for a concrete frost free tank.
These tanks all require some skill to construct. If multiple copies of the same tank are to be
constructed, costs can be reduced and quality increased by constructing reusable concrete
forms.
Figure 8.28
CONCRETE TANK
Figure 8.29
CONCRETE TROUGH
Figure 8.30
TANK MADE FROM CONCRETE PIPE
Figure 8.31
FROST PROOF CONCRETE TANK
Fiberglass Tanks
Many stock tanks are now made out of fiberglass. Fiberglass is very resistant to deterioration
by chemical attack. It is also light and easy to install. It is however, subject to mechanical
damage.
Since fiberglass is so light, wind and animals can easily move it out of place. If a large animal
gets into a fiberglass tank, the tank bottom can be damaged and it might be difficult for the
animal to escape.
For these reasons, it is important to provide anchors and protective rails when installing a
fiberglass tank.
Thickness of fiberglass will determine how resistant the tank is to mechanical damage.
Thickness should be at least the minimum specified in NRCS specifications. It is possible to
repair damaged fiberglass, which is one advantage of using this material.
Tanks size is limited to what can be transported to the site. Sometimes this limitation is
overcome by combining tanks built-up from two or more component parts. Several tanks can
also be placed together in series to provide the required storage.
Plastic Tanks
Some tanks and troughs are now being made out of high strength plastics without fiberglass
reinforcement. The science of plastics is very complex, and it is difficult to know what the life
will be of any given plastic formulation and tank configuration. Only brands and configurations
which have received NRCS State Conservation Engineer approval should be considered.
Figure 8.32
FROST FREE FIBERGLASS TANK
There are generally two kinds of galvanized steel tanks: (1) Those assembled at the site from
standard corrugated or formed steel segments and (2) Completely self contained manufactured
tanks.
1) Stock tanks made from corrugated steel segments
Large diameter stock tanks are made up of curved corrugated galvanized steel sheets,
which are bolted together. Mastic is used in the joints to provide water tightness. The steel
and galvanizing are usually heavy. The bottom of the tank can be made of reinforced
concrete, bentonite, heavy plastic liner, or rubber sheeting material. This type of tank will
usually last a long time if properly installed and cared for.
The thickness of steel and galvanizing vary widely in manufactured steel tanks. The tanks
are frequently small and made of light gauge steel with minimum galvanizing. As with
fiberglass tanks, these must be properly anchored and protected from livestock. Do not
use these tanks in locations where water or soil is corrosive to steel.
Figure 8.33 details a tank made from corrugated steel plate segments. Figure 8.34 illustrates
typical manufactured steel tanks.
Rubber Tire Tanks
Rubber tire tanks are manufactured from used heavy earth-moving or construction equipment
tires. The sidewall of the tire is cut away on the topside to allow drinking access. The opening
on the lower side of the tire is sealed with concrete, plastic or steel plate.
Rubber tire tanks have proven to be durable, relatively inexpensive, and capable of being used
with a variety of water sources. They are relatively easy to install, generally inexpensive, and
very durable. They are however heavy and difficult to handle during installation. There size
may limit water storage for larger herds.
The volume of a rubber tire tank should be calculated using NE200-10-002 Rubber Tire Water
Tank, Tank Gallon Calculator. Figure 8.35 illustrates rubber tire tank installation.
Figure 8.33
TANK MADE FROM CORRUGATED STEEL SEGMENTS
Figure 8.34
MANUFACTURED STEEL TANK
Figure 8.35
RUBBER TIRE TANK INSTALLATION METHODS
Figure 8.36
TYPICAL TANK LAYOUT PLANS
Figure 8.37
TANK DETAILS
Figure 8.38
LAYOUT USING SUBMERGED FLOAT VALVE
Figure 8.39
OVERFLOWS
Figure 8.40
PIPELINE TANK INLET
Figure 8.41
COMMERCIAL STEEL WATER STORAGE TANK
Figure 8.42
FABRICATED STEEL STORAGE TANK
Figure 8.43
CONSTRUCTED CORRUGATED STEEL STORAGE TANK
Figure 8.44
FIBERGLASS STORAGE TANK
Figure 8.45
WATER HARVESTING SYSTEM USING
RUBBERIZED FABRIC STORAGE BAG
Figure 8.46
PIPELINE DRAINS
GRAVITY DRAIN
BLIND DRAIN
PUMPOUT
to 560 12 550 4’ x 6’
561-1,100 10 1,000 4’ x 11’
1,101-4,000 3/16” 2,000 6’ x 12’
4,001-12,000 1/4” 5,000 8’ x 14’
12,001-20,000 5/16” 6,000 8’ x 16’
8,000 8’ x 21’
10,000 9’ x 21’
12,000 9’ x 25’
TABLE OF CONTENTS
FIGURES
CHAPTER 9
HYDRAULIC DESIGN PROCEDURES
9.1 GENERAL
A properly designed livestock pipeline system should balance the energy produced by the
system (pressure & elevation) vs. the energy used in the system (friction, elevation, hydrants,
etc.)
There are two major categories of hydraulic designs associated with stockwater pipelines. They
are:
• Gravity flow pipeline
• Pressure pipeline
Sometimes the system types are combined on one job. For instance, water may be pumped to
a large storage tank at a higher elevation and a gravity pipeline installed to other tanks.
Example No. 1--hydraulic design for a very simple, low head gravity pipeline leading from a
spring.
Example No. 2--an automatic pumped system with pressure tank.
Example No. 3--a timer/manually operated pumped system.
Example No. 4--a rural water supplied system (constant pressure)
Appendix A contains master copies of the worksheets used in these examples. These
worksheets are for your convenience. Use them only if they will aid in the computations.
Computer programs can be used to aid in computations. Appendix B illustrates the use of
currently available programs.
The process for determining the energy available follows the same process as step 6, with
a high pressure head at the water source. Typically a 20-psi differential increase over the
low pressure setting is used for the high switch setting.
9. Draw HGL for high pressure setting. When plotted, the high pressure HGL will be steeper
in slope than the low pressure HGL. This is due to the fact that under higher pressure, the
hydrant and pipeline can flow more water with higher friction loss.
10. Draw a horizontal line from the beginning station of high pressure setting to the station of
the last tank. This is known as the static water head. When a system is fully pressurized &
the pipeline is not flowing, the pressure of the system is equal to the head developed by the
static water head relative to any particular point on the pipeline.
11. Determine the pipe strength required from water hammer/surge effects on the pipeline. The
most conservative determination of water hammer/surge is found by adding the maximum
static pressure head on the system and the maximum surge at any point on the system.
The maximum pressure surge is usually greatest at the first hydrant due to this location
resulting in the steepest HGL.
Determine the high pressure setting flow rate at the first hydrant by balancing the hydrant
and pipeline flow. By finding this rate, the water velocity can be determined by V=Q/A with
A being the cross sectional area of the pipe and Q being the flow rate. Table 2 Appendix A,
provides a surge factor multiplier for various pipe types and sizes. Refer to Ch. 6 for
explanation in determining surge factor. By multiplying the surge factor by the velocity, the
surge pressure can be determined.
Determine the maximum static pressure at the lowest elevation on the pipeline. This is
found by subtracting the lowest point on the pipe profile from the static water head.
The minimum pipe strength required is found by adding the maximum static pressure and
the maximum surge pressure.
12. Minimum pressure tank size recommended. A well pump should never run for less than 1
½ minutes at a time. Constant short duration cycling of the pump will greatly reduce the life
of the pump. For this reason, a pressure tank or storage tank should be adequately sized
for the pump’s flow rate and pressure.
As the pressure tank releases water to the pipeline, the water level in the tank decreases.
This decrease in the water level causes the pressure to decrease until the pump turns. The
well then recharges the tank with water until the high pressure setting is reached and turns
the pump off.
Refer to NLPH Tables 8.3-8.12, pages 8-29 thru 8-36, for the minimum recommended
diaphragm pressure tank size based on the pipeline flow rate or use:
Q avg ⋅ t
V tan k =
⎛ P + 14.7 ⎞
1 − ⎜⎜ low ⎟⎟
⎝ PHi + 14.7 ⎠
V tan k − min. volume of tank required (gallons)
Q avg − average pump flow rate at Plow and Phigh ( gpm)
Plow , PHi − Hi and Low Pressure tank settings (psi)
t − minutes (1.5 recommended )
13. Determine where air release/relief valves are required. A combination valve (COMB) or
three-way air vent should be installed at the first summit in the pipeline after the pump. If
the pipeline goes downhill from the well, it would be advisable to locate the COMB valve
right after the pressure tank (within 10’). See Chapter 7 for additional air relief valve
guidance.
14. Pressure Reducing Valves may need to be installed on pipelines to protect pipe and
appurtenances. These valves reduce the downstream pressure with minimal flow loss.
Computations for pipelines with pressure reducing valves are handled as if the pipeline
beyond the pressure reducer were a lateral. The hydraulic grade line must clear any critical
point.
Refer to Ch. 6 for explanation for determining pressure reducing valve application and
design.
15. Flow Reducing Valves reduce flow in the downstream pipeline. A flow reducing valve can
be installed to reduce pipeline flow.
Figure 9.1
GRAVITY SYSYTEM HGL PROFILE
Figure 9.1
Example 1 Gravity Pipeline
Profile
With more complex livestock pipeline designs and with elevation differences exceeding 240 feet
along pipeline routes, a timer or manually operated livestock pipeline system should be
considered. When the pressure needed to operate the system exceeds safe levels (+100 psi) in
the pressure tank, a timer or manually operated system should be considered because most
pressure tanks are designed and manufactured to an upper limit of only 100-110 psi. In other
situations, a pressure tank can be located along the pipeline at a higher elevation to reduce the
amount of pressure needed to operate the system. For this type of system, see your CET or
Field Engineer. Pressure tanks can be specifically manufactured for high pressure, but are a
significantly higher cost due to special manufacturing processes and testing procedures.
Therefore, this design example is WITHOUT a pressure tank. The plumbing at the storage tank
is set up so water will flow back into the supply line when the pump is off. Due to gravity section
of pipeline, this route needs to be accurately surveyed with a level or total station.
1. Start with required water needs for livestock. Determine water needs for the maximum
amount of animals to be watered at critical time of the year.
Ex. 20 gal/cow/day x 150 cows = 3000 gal/day.
2. Add 10% extra for spillage and evaporation.
Ex. 3000 gal/day + (0.10 x 3000 gal/day) = 3300 gal/day
3. Determine minimum storage requirements. (2 days Recommend).
Ex. 3300 gal/day x 2 day = 6600 gallon tank
A 24-foot diameter tank with 2 feet of depth has 6768 gallons. Therefore, use a 24 foot
storage tank.
4. Determine the volume needed to refill a one day water supply in timed refills. (1 to 4 refills
per day recommended).
Ex. 3300 gal/3 refills = 1100 gallons/refill
5. Determine pump run-time with a pre-determined pump capacity. Pressure requirements
will be determined later. (Recommend 5-15 gpm pumps.)
Ex. 1100 (gal/refill)/10 (gal/min) = 110 min/refill
6. The pressure head at the well can be calculated by adding the ground elevation at the well
to the pressure needed to overcome the critical point. i.e., well elev. = 100.0
Ex. 100.0 + (120 psi x 2.31 ft/1 psi) = 100.0 + 277.2 = 377.2 ft
7. A single Hydraulic Grade Line (HGL) can be calculated based on the flow required and pipe
size chosen. See Friction. Loss tables NLPH (pages 5-8 thru 5-21).
Ex. Try 1.5” 160 psi PVC & 11 gpm => fric. loss = 0.5339 ft/100ft.
8. Determine the location of the highpoint on the pipeline. This is the location of the water
storage tank. Plot the HGL above this tank. Make sure the HGL is above the storage tank
with some clearance to assure flow. Gravity flow the remainder of the pipeline.
Ex. 1800 ft x 0.5339 ft/100ft = 9.6 ft
377.2 ft – 9.6 ft = 367.6 ft > 350 ft (Elev at high tank)
367.6 ft – 350 ft = 17.6 ft
17.6 ft x 1 psi/2.31 psi = 7.6 psi
9. Assure that the pressure at the top storage tank can supply the required flow through the
chosen hydrant. See hydrant flow table, Table 1 Appendix A.
Ex. Using a Merrill “Any Flow”, the flow at 8.3 psi = 11.0gpm OK
10. Well/Pump installer will need to match the flow required & pressure needed at the well
location. This information will be supplied by NRCS technicians. A pressure relief valve will
be installed near the well, which will activate if pump continues running and high pressure
builds up above the pressure required to protect the pipeline.
Ex. Set pressure relief valve at 130-140 psi. The pump will need to pump 120 psi @
11 gpm at well location.
11. The pipeline near the well should have a housed area where a check valve is installed after
the pump, then a pressure gauge followed by a pressure relief valve and a gate valve. The
timer mechanism or manually operated switch can be located at this location. All tanks
along the pipeline should have float valve, while the highest tank has a hydrant with an
overflow drain. The overflow drain will allow the highest tank to be filled after the pump
runs for the specified time period. The other tanks can be filled from the highest tank by
gravity flow when the pump is not running. (See STORAGE TANK PLUMBING – FIG. 9.3)
12. The remainder of the gravity pipeline can be designed by calculating the friction loss from
the slope of a line from the elevation of the highest tank to elevation of the last tank. Be
sure air valves are located at high spots along the gravity pipeline.
Ex. (352-202)/7500-1800) = 0.0263 ft/ ft.
13. Flow of the gravity pipeline can be calculated using the rearranged Hazen-Williams formula.
Check with the CET or Field Engineer.
Ex. Q =42.23 di2.63 s0.54,
where Q =flow (gpm),
di = inside diameter (in),
s = slope (ft/ft)
Q= 42.23 x 1.7542.63 x 0.02630.54 = 25.9 gpm
This is the flow to the farthest tank unless the float valve is the limiting control. An HGL can
be plotted to each tank from the storage tank, if there are several tanks along the gravity
line.
Figure 9.2
TIMER OR MANUALLY OPERATED PRESSURE SYSYTEM HGL PROFILE
Figure 9.3
STORAGE TANK PLUMBING
Tank Volume
Tank Diameter =
5.87 × Tank depth
3,850
Tank Diameter =
5.87 × 1.75
Step 3: Determine minimum system flow rate required to fill tanks for one-day volume.
(Refer to NLPH, chapter 2; NE-ENG-35)
Step 6: Determine energy required for low (pump on) setting for the most critical tank.
Energy or head required at the last hydrant for desired flow is determined by adding the
safety factor (SF) to the pressure required at the hydrant to produce desired flow.
Use manufacturer’s data or the following formula to calculate the pressure at the farthest
hydrant required to produce desired flow.
2.99
⎛ Q ⎞
Q = 5.728 × P 0.334 ⇒ H 3 / 4 = ⎜ ⎟ × 2.31
Head (ft) for ¾ in. hydrants: ⎝ 5.73 ⎠
2.99
⎛ 8 ⎞
H3 / 4 = ⎜ ⎟ × 2.31 = 6.3 ft
⎝ 5.73 ⎠
Energy required at furthest hydrant: H¾ + SF = 6.3 ft + 10 ft = 16.3 ft.
Determine friction loss for desired pipe size and flow rate (Refer to NLPH, pages 5-8 thru
5-21 or chapter 3 of the Engineering Field Manual) Pipe Size: 1 ½ in. PVC, SDR 26.
0.2960 ft
Friction loss at 8 gpm = 100 ft
0.2960 ft
× 9200 ft = 27.2 ft
Total Friction loss in pipeline = 100 ft
Determine required energy at well to produce desired flow:
Sum the elevation of the farthest hydrant, the energy required to produce desired flow, and
the total friction loss in the pipeline
3987 ft + 16.3 ft + 27.2 ft = 4030.5 ft
Determine Low (pump on) switch setting by subtracting the well elevation from the total
energy required and convert to psi:
Low switch setting = 4030 .5 ft − 3980 ft
= 21.9 psi
2.31
Select a standard low pressure switch (pump on) setting greater than 21.9 psi. Typical
ranges for pressure switches are as follows: 20-40, 30-50, 40-60, 50-70, 60-80, and 80-100.
For this example, use 30-50 psi pressure switch.
Step 7: Draw Hydraulic Grade Line (HGL) for low-pressure setting.
Calculate elevation of “pump on” setting (30 psi):
Well elevation + pump on setting = 3980 + 30psi x 2.31 = 4049.3
Balance flow in pipeline with hydrant flow:
Calculate the slope of the HGL from “pump on” setting at the well to the energy required at
last hydrant calculated in step 6.
Trial 1:
Pump on setting: 4049.3
Elevation of farthest hydrant: 3987
Sta. of farthest hydrant: 92+00
Required energy for 8 gpm: 16.3 ft
4049.3 − (3987 + 16.3)
× 100 = 0.50 ft
9200 100 ft
Refer to NLPH, pages 5-8 thru 5-21 or chapter 3 of the Engineering Field Manual to
interpolate flow rate in pipeline for the calculated slope. Flow rate = 10.6 gpm with 0.50 ft per
100 ft of friction loss 10.6 gpm > 8 gpm; Flow does not balance, increase design flow rate at
the last hydrant and repeat the previous calculation.
Trial 2:
Required energy for 10 gpm:
2.99
⎛ 10 ⎞
H3 / 4 = ⎜ ⎟ × 2.31 = 12.2 ft
For a ¾ in. hydrant, ⎝ 5.73 ⎠
Refer to NLPH, pages 5-8 thru 5-21 or chapter 3 of the Engineering Field Manual to
determine flow rate in pipeline for the calculated slope. Flow rate = 9.9 gpm with 0.44 ft/100
ft of friction loss 9.9 gpm ~ 10 gpm
Balanced flow at “pump on” setting:
Flow = 10 gpm
Energy required at hydrant = 22.2 ft
Slope of HGL = 0.4475 ft per 100 ft
Draw Low HGL on profile (see figure 9.4)
Check minimum head at critical point, if other than end. The pipeline may not pass the
desired flow if the Low HGL is closer to the ground surface than allowed by the safety factor.
There may be several critical points (intermediate summits) that require checking. To
determine minimum head at critical point inspect Low HGL plotted on profile or calculate as
follows:
Elevation of Low HGL at well: 4049.3
0.4475 ft
Slope of Low HGL: 100 ft
Step 8: Determine energy available for high (pump off) setting for the most critical tank.
Calculate elevation of “pump off” setting (50 psi):
Well elevation + pump off setting = 3980 + 50 psi x 2.31 = 4095.5
Balance flow in pipeline with hydrant flow:
Trial 1:
Assume flow rate at “pump off” setting is 5 gpm greater than “pump on” setting.
Pump off flow rate = 10 gpm + 5 gpm = 15 gpm
Use manufacturer’s data or the following formula to calculate the energy at the farthest
hydrant required to produce desired flow.
2.99
⎛ Q ⎞
H 3/ 4 = ⎜ ⎟ × 2.31
Head (ft) for ¾ in. hydrants: ⎝ 5.73 ⎠
2.99
⎛ 15 ⎞
H 3/ 4 = ⎜ ⎟ × 2.31 = 41.0 ft
⎝ 5.73 ⎠
Refer to NLPH, pages 5-8 thru 5-21 or chapter 3 of the Engineering Field Manual to
interpolate flow rate in pipeline for the calculated slope.
Flow rate = 12.0 gpm with 0.63 ft per 100 ft of friction loss
12.0 gpm < 15 gpm;
Flow does not balance, decrease design flow rate at the last hydrant and repeat the previous
calculation.
Trial 2:
Required energy for 13 gpm:
2.99
⎛ 13 ⎞
H 3/ 4 = ⎜ ⎟ × 2.31 = 26.8 ft
For a ¾ in. hydrant, ⎝ 5.73 ⎠
Refer to NLPH, pages 5-8 thru 5-21 or chapter 3 of the Engineering Field Manual to
interpolate flow rate in pipeline for the calculated slope.
Flow rate = 13.5 gpm with 0.78 ft/100 ft of friction loss
13.5 gpm > 13 gpm; Flow does not balance, increase design flow rate at the last hydrant and
repeat previous calculations until desired level of precision is obtained.
Step 11: Determine the pipe strength required for total operating pressure.
Total operating pressure is equal to the sum of the maximum static pressure and the
maximum surge pressure.
Maximum static pressure is the distance from the Static HGL to the lowest point on the
pipeline (see figure 9.4).
4095.5 − 3975
= 52.2 psi
2.31
Determine maximum surge pressure by balancing hydrant flow at the hydrant closest to the
well. Refer to previous steps for balancing process.
Maximum Q = 15.6 gpm
Convert Maximum Q from gpm to cfs.
15.6 gpm
Maximum Q (cfs) = = 0.0348 cfs
448.8 cfs
gpm
A=0.0168 ft2
Step 13: Determine where air relief valves are required (See figure 9.4.).
Use combination valve at the first summit: Sta. 6+21, Elev. 3985
Use Air/Vac valve at the critical point: Sta. 77+53, Elev. 4004
Figure 9.4
Pumped Automatic Pressure System HGL PROFILE
Since cattle are only allowed access to one watering facility at a time, the minimum required
storage at each watering facility is 2,640 gallons.
Tank Volume
Tank Diameter =
5.87 × Tank Depth
Tank Depth for this example is a 2’ deep tank (standard for galvanized
tanks), filled to within 3” of the top of the tank. This assumes that the tank is never “level full”.
2’-(3/12)’=1.75’
2,640
Tank Diameter = = 16.03 feet Æ Use a 16’ nominal tank.
5.87 × 1.75
Note: The above diameter only applies if the producer is installing a cylindrical tank, such as
a galvanized steel tank or a fiberglass tank. This diameter does not apply to rubber tire
tanks.
The energy at the source (hook-up to rural water) is best estimated by testing the static
pressure at the connection. The pressure was tested at the water meter and was found to be
38 psi.
Add this value to the elevation of the hook-up to find the elevation of the Hydraulic Grade
Line:
87.78 feet + 104.41 feet = 192.19 feet
Trial 1:
• Begin by guessing a flow rate. Since the required flow rate for this system is so small (4
gpm calculated in Step 3), the initial guess is higher. This is based on past experience.
Initial guess: Qhydrant = 10 gpm.
• Determine the energy required at the hydrant to produce 10 gpm from a ¾” hydrant. Refer
to Table 1 in Appendix A. From the Table, 10 gpm is achieved at a pressure of 5.3 psi
(12.24 feet).
• Calculate the slope of the hydraulic grade line for this trial.
Available Energy at Well − (Elev. of Hydrant + Pressure at Hydrant )
Slope of HGL =
Distance from Well to Hydrant
• Use Tables for friction loss in Chapter 5, NLPH to determine the flow rate allowed through
the pipeline with 1.966ft/100ft of friction loss.
Trial 2:
• Increase Qhydrant to 13 gpm.
• Energy required at ¾” hydrant to produce 13 gpm is 11.7 psi (27.02 feet) from Table 1 in
Appendix A.
• Slope of hydraulic grade line:
192.19 feet − (134.4 feet + 27.02 feet ) 1.328 feet
Slope of HGL = × 100 =
2,317 feet 100 feet
Trial 3:
• Decrease Qhydrant to 12.8 gpm.
• Energy required at ¾” hydrant to produce 12.8 gpm is 11 psi (25.41 feet) from Table 1 in
Appendix A.
• Slope of hydraulic grade line:
192.19 feet − (134.4 feet + 25.41 feet ) 1.397 feet
Slope of HGL = × 100 =
2,317 feet 100 feet
Check the critical point for adequate pressure, located at STA 19+02, El. 151.2.
⎛ 1,902 feet × 1.397 feet ⎞
Elevation of HGL at STA 19 + 02 = 192.19 feet - ⎜ ⎟ = 165.62 feet
⎝ 100 feet ⎠
Pressure over critical point = 165.62feet -151.2feet= 14.42feet
14.4 feet (6.2 psi) is adequate pressure at the critical point for the accuracy of this survey.
Note that if your survey requires using a safety factor in your design, the pressure at the
critical point should be checked against the allowable safety factor for adequacy.
Draw the hydraulic grade line onto the survey profile (see figure 9.5) from STA 0+00, Elev.
192.19 to STA 23+17, Elev. 159.81.
From Table 1 in Appendix A, a ¾” hydrant is capable of flowing 19.3 gpm at 38 psi. Since
friction loss is negligible in such a short run of pipe, the flow will balance at the hydrant
capacity. Therefore, Qmax=19.3 gpm.
The area of 1.25” SDR PVC pipe can be found on Table 5.2, NLPH; 0.0128 square ft.
19.3gpm 1 ft 3 1 min
Vmax = × × = 3.36 ft/sec
0.0128 ft 2 7.48 gal 60 sec
To calculate the surge pressure, multiply maximum velocity by the factor for surge in SDR 26
PVC in Table 2 in Appendix A.
Maximum Static Pressure = 192.19 feet – 92.4 feet= 99.79 feet(43.2 psi)
92.3 psi < 160 psi rated pipe strength of SDR 26 PVC, system checks.
Use an Air/Vac valve at the critical point: STA 19+02, Elev. 151.2.
Additional Considerations:
NLPH Chapter 6 recommends that pressure be limited to 80 psi at hydrants. Tank 1 is the
lowest hydrant/tank in this system and should be checked for static pressure.
Figure 9.5
Rural Water Supplied (Constant Pressure) HGL PROFILE
TABLE OF CONTENTS
FIGURES
CHAPTER 10
STOCKWATER PIPELINE INSTALLATION
10.1 TRENCHING
10.1.1 Trencher Constructed Trenches
When conditions permit, trenching for pipelines which are buried from 5 to 6 feet are usually
done with a narrow 4-to 6-inch wide chain trencher. Where there is little gravel and the ground
is not too wet, these trenchers bring up well pulverized soil that makes good backfill material.
The material is usually placed back in the trench with a trencher mounted blade. Where rocks
are not present, any of this material may be backfilled directly around the pipe.
There is no practical way to compact the fill in these narrow trenches. Within two to five years,
the backfill material will usually consolidate to the maximum extent. There will be low spots in
the trench backfill when the material consolidates. These can be a hazard to livestock, humans,
and equipment and are frequently a starting point for gully erosion.
There are three things that should always be done to minimize these problems:
1. Make it clearly understood by the landowner that maintenance of the backfill may be
necessary each year for several years. This maintenance will consist of adding fill to low
spots and repairing any erosion that may occur.
2. When backfilling, mound the soil over the trench to the maximum extent possible.
3. Construct "water bars" at right angles to the trench at periodic intervals. These are simply
very small diversion dikes across the trench at locations where the trench is traveling up or
down the slope. The purpose of these diversions is to prevent concentration of water in the
trench and erosion of the backfill. Figure 10.1 illustrates a water bar.
The selection of tracked or wheeled prime movers and their relative size for pipe plows depend
on several factors:
- Local site conditions along the planned route
- Desired rate of pipe placement - Burial depth of pipe: while company guidelines should
take precedence, the general recommendation for plow prime mover horsepower rating is
a minimum of 50 horsepower per foot of buried depth.
- Terrain variance: presence of steep slopes, sand, heavy woods, etc., all of which affect
how well a vehicle will move.
General Guidelines:
- A ripping pass to the depth required is desirable and should be made before plowing in
the pipe to make sure the route is clear between splice locations. The ripping pass is made in
the same direction that the pipe is to be plowed. In some situations, it may be necessary to
make more than one ripping pass, or to rip deeper than the required depth.
- Always start the plow tractor’s movement slowly and gradually increase speed after all
pipe slack is taken up from the pipe delivery system.
- Plow attitude and depth must be changed gradually. Such changes should be made only
while the plow’s prime mover is under way.
- Grade off abrupt changes in terrain along the pipe path ahead of the plow.
- Plowing operations must be observed continuously for obstructions, proper feeding of the
pipe, proper depth, following the marked route, and safety of the crew.
- Stationary operation of a vibratory plow for excessive periods of time can damage the
pipe through kinking or abrasion. If an obstacle is encountered, shut off the vibratory plow and
excavate the pipe to expose and remove the obstacle.
Figure 10.1
WATER BAR
TABLE OF CONTENTS
FIGURES
CHAPTER 11
OPERATION AND MAINTENANCE
11.1 GENERAL
A stockwater pipeline and the associated tanks and equipment can soon fall into disrepair if not
properly operated and maintained. A properly constructed stockwater pipeline should last in
excess of 20 years if adequate operation and maintenance are performed.
11.2 WINTERIZING
Shallow pipelines must be drained during winter months to prevent freezing. The importance of
draining the line in a timely manner must be emphasized to the landuser. Even small pockets of
water in low areas can cause damage to the pipeline.
Where a pipeline has many small undulations, it may be possible to minimize the number of
drain locations required by blowing the line out with compressed air. Drains will then only be
needed at major low areas. Facilities for connecting an air compressor to the line must be
installed. The air compressor must have enough volume to properly blow out the line. Pressure
on the pipeline must be regulated to not exceed the pressure rating of the pipe. The air should
be run through the line long enough to evacuate small remaining amounts of water that will flow
back into low areas after the air is removed. All of this should be specified in the operation and
maintenance plan.
The O&M Plan should comply with all laws, regulations, ordinances, and easements; in such a
manner that will result in the least adverse impact on the environment and assure the practice
will serve the purpose for which it was installed. Maintenance includes work to prevent
deterioration of the practice, repairing damage, or replacing components, which fail.
1. Yearly inspection of the entire length of the pipeline for any signs of leaks or pipe
damage.
2. Checking for settlement in the trench backfill when the material consolidates. These can
be a hazard to livestock, humans, equipment, and are often a starting point for gully
erosion in the trench. This settling may occur for many years after construction. The
settled areas in the trench should be refilled, and any subsequent erosion repaired.
3. Checking to assure all valves and air vents are set at the proper operating condition so
they may provide the needed protection to the pipeline.
4. Maintaining the design depth of cover over the pipeline and backfill around structures.
5. Limiting traffic over shallow buried pipelines to designated sections that were designed
for traffic loads. Avoid travel over shallow buried pipelines by tillage equipment when the
soil is saturated.
10. Draining the system and components as needed in areas that are subject to freezing. If
parts of the system cannot be drained, an antifreeze solution may be added.
11. Repairing any rodent, burrowing animal, vandalism, vehicle, or livestock damage.
12. Where sacrificial anodes are used for cathodic protection, checking their condition on a
regular basis and repairing or replacing as necessary.
13. When there are unique or critical factors associated with a system, a supplemental or
special operation and maintenance plan should be provided.
WORKSHEETS
NE Stockwater Pipeline Handbook Worksheets
Figure 1
Extreme frost penetration
NSPH April
NSPH February
20082007 Appendix A-1
NE Stockwater Pipeline Handbook Worksheets
Figure 2
Pressure Vs. Flow Rate
Any Hydrant
50.0
Any 1" Hydrant
45.0 Q =6.357P0.458
40.0
35.0
20.0
10.0
5.0
0.0
0 10 20 30 40 50 60 70 80
Pressure (psi)
NSPH April
February
20082007 Appendix A-2
NE Stockwater Pipeline Handbook Worksheets
Table 1
Pipe
Nominal Pressure Surge
Pipe Size Type SDR/SIDR Rating t ID OD E mod a Factor1
(psi) (in) (in) (in) (lb/in2) (ft/sec) (psi/ft/sec)
1" PE 19 0.060 1.049 1.169 110,000 676.49 9.09
1" PE 15 100 0.070 1.049 1.189 110,000 729.44 9.81
1" PE 11.5 125 0.091 1.049 1.231 110,000 828.73 11.14
1" PE 9 160 0.117 1.049 1.283 110,000 935.58 12.58
1" PE 7 200 0.150 1.049 1.349 110,000 1053.51 14.16
1" PE 5.3 250 0.198 1.049 1.445 110,000 1200.86 16.14
1 1/4" PE 19 0.073 1.380 1.526 110,000 651.07 8.75
1 1/4" PE 15 100 0.092 1.380 1.564 110,000 729.10 9.80
1 1/4" PE 11.5 125 0.120 1.380 1.620 110,000 829.69 11.15
1 1/4" PE 9 160 0.153 1.380 1.686 110,000 932.89 12.54
1 1/4" PE 7 200 0.197 1.380 1.774 110,000 1052.67 14.15
1 1/4" PE 5.3 250 0.260 1.380 1.900 110,000 1199.83 16.13
1 1/2" PE 19 0.085 1.610 1.780 110,000 650.45 8.74
1 1/2" PE 15 100 0.107 1.610 1.824 110,000 728.00 9.79
1 1/2" PE 11.5 125 0.140 1.610 1.890 110,000 829.69 11.15
1 1/2" PE 9 160 0.179 1.610 1.968 110,000 934.15 12.56
1 1/2" PE 7 200 0.230 1.610 2.070 110,000 1053.03 14.16
1 1/2" PE 5.3 250 0.304 1.610 2.218 110,000 1201.06 16.15
2" PE 19 0.109 2.067 2.285 110,000 650.07 8.74
2" PE 15 100 0.138 2.067 2.343 110,000 729.62 9.81
2" PE 11.5 125 0.180 2.067 2.427 110,000 830.27 11.16
2" PE 9 160 0.230 2.067 2.527 110,000 934.52 12.56
2" PE 7 200 0.295 2.067 2.657 110,000 1052.55 14.15
2" PE 5.3 250 0.390 2.067 2.847 110,000 1200.64 16.14
2 1/2" PE 19 0.130 2.469 2.729 110,000 649.59 8.73
2 1/2" PE 15 100 0.165 2.469 2.799 110,000 729.97 9.81
2 1/2" PE 11.5 125 0.215 2.469 2.899 110,000 830.25 11.16
1" PVC 26 160 0.060 1.195 1.315 400,000 1182.31 15.90
1" PVC 21 200 0.063 1.189 1.315 400,000 1212.46 16.30
1" PVC 17 250 0.077 1.161 1.315 400,000 1345.37 18.09
1" PVC 13.5 315 0.097 1.121 1.315 400,000 1518.04 20.41
1 1/4" PVC 32.5 125 0.060 1.540 1.660 400,000 1048.89 14.10
1 1/4" PVC 26 160 0.064 1.532 1.660 400,000 1084.18 14.58
1 1/4" PVC 21 200 0.079 1.502 1.660 400,000 1208.29 16.24
1 1/4" PVC 17 250 0.098 1.464 1.660 400,000 1351.11 18.16
1 1/4" PVC 13.5 315 0.123 1.414 1.660 400,000 1521.63 20.46
1 1/2" PVC 32.5 125 0.060 1.780 1.900 400,000 978.88 13.16
1 1/2" PVC 26 160 0.073 1.754 1.900 400,000 1082.26 14.55
1 1/2" PVC 21 200 0.090 1.720 1.900 400,000 1205.38 16.21
1 1/2" PVC 17 250 0.112 1.676 1.900 400,000 1350.05 18.15
1 1/2" PVC 13.5 315 0.141 1.618 1.900 400,000 1522.87 20.47
2" PVC 32.5 125 0.073 2.229 2.375 400,000 965.47 12.98
2" PVC 26 160 0.091 2.193 2.375 400,000 1080.73 14.53
2" PVC 21 200 0.113 2.149 2.375 400,000 1208.14 16.24
2" PVC 17 250 0.140 2.095 2.375 400,000 1350.05 18.15
2" PVC 13.5 315 0.176 2.023 2.375 400,000 1521.73 20.46
2 1/2" PVC 32.5 125 0.088 2.699 2.875 400,000 963.41 12.95
2 1/2" PVC 26 160 0.110 2.655 2.875 400,000 1079.94 14.52
2 1/2" PVC 21 200 0.137 2.601 2.875 400,000 1209.10 16.26
2 1/2" PVC 17 250 0.169 2.537 2.875 400,000 1348.08 18.12
2 1/2" PVC 13.5 315 0.213 2.449 2.875 400,000 1521.53 20.46
Multiply the maximum velocity change in the pipe by the surge factor to determine pressure increase due to surge,
1
Based on NEH Part 636, Chapter 52
COMPUTER PROGRAMS
NE Stockwater Pipeline Handbook Design Guide
APPENDIX B
COMPUTER PROGRAMS
Instructions and examples for the Nebraska Stockwater Pipeline Handbook will be added at
later date.
MATERIALS SOURCES
NE Stockwater Pipeline Handbook Design Guide
APPENDIX C
MATERIALS SOURCES
Material Source information for the Nebraska Stockwater Pipeline Handbook will be added at
later date.
APPENDIX D
PLANNING AND DESIGN GUIDE
The Planning and Design Guide for the Nebraska Stockwater Pipeline Handbook will be added
at later date.