General Specifications: Prosafe-Rs Standards Compliant Models
General Specifications: Prosafe-Rs Standards Compliant Models
General ProSafe-RS
Specifications Standards Compliant Models
GS 32P01B60-01EN
n GENERAL
The hardware components of the ProSafe-RS comply with the standards below.
Functional Safety Standards
IEC 61508, IEC 61511-1, IEC 62061
Programmable Controllers Standards
IEC 61131-2 (*1) (*2) (*3)
Application Standards (*1)
EN 54-2 (*2), EN 298 (*3) (*4), EN 50156-1, NFPA85, NFPA86, NFPA72
Safety Standards (*5)
EMC Conformity Standards (*5)
Standards for Hazardous Location Equipment (*5)
Marine Standards (*5)
Environmental Standards (*6)
EU Directive of “Restriction of the use of the certain hazardous substances in electrical and electronics equipment
(RoHS)” (*7).
“Administration on the Control of Pollution Caused by Electrical and Electronic Products” in the People’s Republic of
China (*8).
“UAE Cabinet Decision No. 10 of 2017 (UAE RoHS)” in United Arab Emirates (*9).
*1: Except for the case of using S2BN1D in combination with S2MMM843 or S2MDV843 of style S2 or later, a lightning arrester
or the like is required to meet this surge immunity standard.
*2: 24 V DC and 48 V DC field power to DI and DO shall not be provided directly from a DC distribution network. The field
power supply cable length must be 30 m or less.
*3: Where the system power uses 24 V DC (SPW484), use an external uninterruptible power supply (UPS).
*4: 24 V DC and 48 V DC field power to DI and DO shall not be provided directly from a DC distribution network. The field
power supply cable length must be 10 m or less.
*5: Individual Standards numbers and acquisition conditions of Safety Standards, EMC Conformity Standards, Standards for
Hazardous Location Equipment and Marine Standards are shown in Table “List of Acquisition Conditions for Conformity
Standards” below.
*6: ProSafe-RS safety instrumented system is intended to be sold and used only as a part of equipment which is excluded from
EU WEEE (Waste Electrical and Electronic Equipment) Directive, such as large-scale stationary industrial tools, a large-
scale fixed installation and so on, and therefore, subjected to the exclusion from the scope of the WEEE Directive.
*7: ProSafe-RS models compliant with the CE Marking also comply with directive.
*8: The product information required by the law is available on the Yokogawa’s web site:
http://www.yokogawa.com/dcs/CNRoHS/
*9: ProSafe-RS models except for S2BN4D and S2BN5D compliant with the CE Marking also comply with this law.
Acquisition conditions
Except for N-IO Node N-IO Node (*17)
Category Standard
100-120 V 220-240 V 100-240 V
24 V DC 24 V DC
AC AC AC
CAN/CSA-C22.2
X — X X X
No. 61010-1
CSA CAN/CSA-IEC 61010-2-201 X — X X X
CAN/CSA-C22.2
X — X X X
No. 61010-2-030 (*11)
Safety
Standards EN 61010-1 X X X X X
(*1) (*2) (*3) CE Marking EN 61010-2-201 X X X X X
Low Voltage Directive
(*6) EN 61010-2-030 (*11) X X X X X
EN 60825-1 (*12) X X X X X
EAC Marking CU TR 004 X X X X X
CE Marking EN 61000-6-2 X X X X X
EMC Directive EN 61000-3-2 (*15) — X — X (*18) —
EN 61000-3-3 (*16) — X — X (*18) —
RCM EN 55011 Class A Group 1 (*13) X X X X X
EMC Korea Electromagnetic
Conformity KC Marking X X X X X
Conformity Standard
Standards
(*2) (*4) EAC Marking CU TR 020 X X X X X
(*14) Functional Safety IEC 61326-3-1 X X X X X (*19)
NM EN 55011
X X X X X
Morocco Compliance Class A Group 1 (*13)
Marking NM EN 61000 6 2 X X X X X
(C مMarking)
EMC directive NM EN 61000 3 2 (*15) — X — X (*18) —
NM EN 61000 3 3 (*16) — X — X (*18) —
Class 3600:2011
US (FM)
Class 3611:2004 X X X X X
Nonincendive (*7)
Class 3810:2005
C22.2 No. 213-15
CAN/CSA-C22.2
Canada (FM) No. 61010-1-12
Non-Incendive X — X X X
Standards (*8) CAN/CSA-IEC 61010-2-201:14
for CAN/CSA-C22.2
Hazardous No. 61010-2-030-12
Location
Equipment EN 60079-0:2012+
ATEX Type “n” — — X — X
(*5) A11:2013
(*9)
EN 60079-15:2010 — — X — X
X: Compliant —: Non-compliant
Note: For details on S2NN70D (System model: S2ZN70D), S2NN60D (System model: S2ZN60D), and S2CB60,
refer to GS “N-IO field enclosure” (GS 32P06Q10-01EN).
Note: In relation to the CE Marking, the manufacturer and the authorised representative for ProSafe-RS in the EEA are indicated
below:
Manufacturer: YOKOGAWA Electric Corporation (2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, Japan.)
Authorised representative in the EEA: Yokogawa Europe B.V. (Euroweg 2, 3825 HD Amersfoort, The Netherlands.)
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN July 31, 2020-00
<<Contents>> <<Index>> 3
*1: For ensuring all the hardware devices to satisfy the safety standards, the dedicated breakers in the power supply
distribution board must conform to the following specifications.
[CSA] CSA C22.2 No.5 or UL 489
[CE Marking] EN 60947-1 and EN 60947-3
[EAC Marking, C مMarking] EN 60947-1 and EN 60947-3
*2: For the rack mountable devices, DIN rail montable devices, and wall mountable devices to meet the Safety Standards
and EMC Standards, the devices must be installed in a lockable metal cabinet. The cabinet must conform to IEC/EN/CSA
61010-2-201 or provide degrees of protection IP3X or above and IK09 or above.
*3: ProSafe-RS measurement input corresponds to the measurement category O (Other) based on IEC/EN 61010-2-030 and
CAN/CSA-C 22.2 No. 61010-2-030. The measurement category I defined in IEC/EN 61010-1: 2001 and CAN/CSA-C 22.2
No. 61010-1-04 has been changed to O (Other). For details, see “ProSafe-RS Installation Guidance” (TI 32P01J10-01EN).
*4: 24 V DC and 48 V DC field power to DI and DO shall not be provided directly from a DC distribution network. The field
power supply cable length must be 30 m or less.
*5: Regarding ATEX Type i, IECEx Type i and IECEx Type “n”, refer to the GS “Base Plates for Barrier (for N-IO)” (GS
32P06P10-01EN).
*6: When a product is out of the scope of Low Voltage Directive (LVD), the conformity to LVD is not declared. However, the
conformity to this standard is secured.
*7: Explosion-proof specification for US (FM) NI:
Class I, Division 2,Groups A, B, C and D Temperature code T4
There are specific conditions of use to comply with US (FM) NI. For details, refer to the Explosion Protection (TI
32S01J30-01E).
*8: Explosion-proof specification for Canada (FM) NI:
Class I, Division 2,Groups A, B, C and D Temperature code T4
There are specific conditions of use to comply with Canada (FM) NI. For details, refer to the Explosion Protection (TI
32S01J30-01E).
*9: Explosion-proof specification for ATEX Type “n”:
II 3G Ex nA nC II C T4 Gc X
SSC50, SSC57, SSC60, S2SC70, SNB10D, SBD2D, SBD3D, and SBD4D are compliant.
II 3G Ex nA IIC T4 Gc X
The products other than SSC50, SSC57, SSC60, S2SC70, SNB10D, SBD2D, SBD3D,
SBD4D, S2BN4D, and S2BN5D are compliant.
“Type of Protection” of the below products is indicated together with modules installed in.
SSC50, SSC57, SSC60, S2SC70, SNB10D, and SNT10D.
“X” indicates specific condition of use. For details, refer to the Explosion Protection (TI 32S01J30-01E).
*10: Explosion-proof specification for IECEx Type “n”:
Ex nA IIC T4 Gc
There are specific conditions of use to comply with IECEx Type “n”.
For details, refer to the Explosion Protection (TI 32S01J30-01E).
*11: SAI143, SAV144, SAT145, SAR145, and S2MMM843 are in the scope of this standard.
*12: Only SNT401, SNT411, SNT501, SNT511,and S2EN501 (Only optical ESB Bus) are compliant with safety of laser
products.
*13: A Class A hardware device is designed for use in the industrial environment. Please use this device in the industrial
environment only.
*14: Except for the case of using S2BN1D, S2NN70D, and S2NN60D in combination with S2MMM843 or S2MDV843 of style
S2 or later, a lightning arrester or the like is required to meet this surge immunity standard.
*15: An external device such as a power unit with harmonic current neutralizer and an active harmonics conditioner must be
connected to meet this harmonic current emission standard.
*16: The specified limits of voltage drop across wiring must be satisfied to meet this standard.
*17: N-IO Node consists of a node interface unit and N-IO I/O units.
*18: Only the 100-120 V AC power supply specification is not compliant. Only the 200-220 VAC power supply specification is
compliant.
*19: Where the system power uses 24 V DC (S2PW504), use an external uninterruptible power supply (UPS).
*20: Explosion-proof specification for ECAS-Ex Type “n”:
Ex nA IIC T4 Gc
There are specific conditions of use to comply with ECAS-Ex Type “n”.
For details, refer to the Explosion Protection (TI 32S01J30-01E).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN July 31, 2020-00
<<Contents>> <<Index>> 4
LIST OF CONFORMITY STANDARDS
Conformity standards of each product are shown in Table “List of Conformity Standard”.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Mar. 27, 2020-00
<<Contents>> <<Index>> 5
Table List of Conformity Standards 1 (2/3)
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Jan. 17, 2020-00
<<Contents>> <<Index>> 6
Table List of Conformity Standards 1 (3/3)
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Feb. 28, 2020-00
<<Contents>> <<Index>> 7
Table List of Conformity Standards 2 (1/3)
*1: For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.
*2: S2NN30D is compliant to the standard, which includes S2PW504, and S2EN501 as its components.
*3: S2ZN1D is compliant to the standard including its components. For the components of S2ZN1D, refer to the GS “Base
Plates (for N-IO)” (GS 32P06K20-01EN).
*4: Refer to the GS “Base Plates for Barrier (for N-IO)” (GS 32P06P10-01EN).
*5: Refer to the GS “N-IO field enclosure” (GS 32P06Q10-01EN).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN July 31, 2020-00
<<Contents>> <<Index>> 8
Table List of Conformity Standards 2 (2/3)
*1: For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN July 31, 2020-00
<<Contents>> <<Index>> 9
Table List of Conformity Standards 2 (3/3)
*1: For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN July 31, 2020-00
<<Contents>> <<Index>> 10
Table List of Conformity Standards 3 (1/4)
Marine Standards
Model ABS
BV LR
(American Bureau of DNV GL
(Bureau Veritas) (Lloyd’s Register)
Shipping)
S2SC70S (*1) X X X X
S2SC70D (*1) X X X X
S2EN402 X X X X
S2EN404 X X X X
S2NN30D (*2) (*3) X X X X
S2PW503 X X X X
S2PW504 X X X X
S2EN501 X X X X
A2BM4 — — — —
S2KLF10 X X X X
S2KPB10 X X X X
S2MMM843 X X X X
S2MDV843 X X X X
S2DCV02 X X X X
S2BN1D (*4) X X X X
S2ZN4D (*5) (*5) (*5) (*5)
S2BN4D (*5) (*5) (*5) (*5)
S2ZN5D (*5) (*5) (*5) (*5)
S2BN5D (*5) (*5) (*5) (*5)
S2ZN70D (*6) (*6) (*6) (*6)
S2NN70D (*6) (*6) (*6) (*6)
S2ZN60D (*6) (*6) (*6) (*6)
S2NN60D (*6) (*6) (*6) (*6)
S2CB60 (*6) (*6) (*6) (*6)
VI702 X X X X
SSC60S (*7) X X X X
SSC60D (*7) X X X X
SSC50S (*8) X X X X
SSC50D (*8) X X X X
X: Compliant —: Non-compliant NA: Not Applicable
*1: S2SC70D-F with SCP461 and S2SC70S-F with SCP461 comply with Marine Standards. S2SC70D-S and S2SC70S-S
do not comply with Marine Standards. S2SC70D with S2CP471 and S2SC70S with S2CP471 do not comply with Marine
Standards.
S2SC70D and S2SC70S are compliant to the standard, which includes SPW481, SPW482, SPW484, and SCP461 as its
components.
*2: S2NN30D is compliant to the standard, which includes S2PW503, S2PW504, S2EN501, S2KLF10, and S2KPB10 as its
components.
*3: S2NN30D-0 does not comply with Marine Standards.
*4: S2BN1D-0 and S2BN1D-9 do not comply with Marine Standards.
*5: Refer to the GS “Base Plates for Barrier (for N-IO)” (GS 32P06P10-01EN).
*6: Refer to the GS “N-IO field enclosure” (GS 32P06Q10-01EN).
*7: SSC60D-F with SCP461 and SSC60S-F with SCP461 comply with Marine Standards. SSC60D-S and SSC60S-S do not
comply with Marine Standards. SSC60D with S2CP471 and SSC60S with S2CP471 do not comply with Marine Standards.
SSC60D and SSC60S are compliant to the standard, which includes SPW481, SPW482, SPW484, and SCP461 as its
components.
*8: SSC50D-F and SSC50S-F comply with Marine Standards. SSC50D-S and SSC50S-S do not comply with Marine
Standards.
SSC50D and SSC50S are compliant to the standard, which includes SPW481, SPW482, SPW484, and SCP451 as its
components.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 11
Table List of Conformity Standards 3 (2/4)
Marine Standards
Model ABS
BV LR
(American Bureau of DNV GL
(Bureau Veritas) (Lloyd’s Register)
Shipping)
SSC57S (*9) X X X X
SSC57D (*9) X X X X
SNB10D (*10) X X X X
SNT10D (*11) X X X X
SAI143 (*12) X X X X
SAV144 X X X X
SAT145 X X X X
SAR145 X X X X
SAI533 X X X X
SDV144 (*12) X X X X
SCB100 X X X X
SCB110 X X X X
SDV521 (*12) X X X X
SDV526 — — — —
SDV531 (*12) (*13) X X X X
SDV53A X X X X
SDV541 (*12) X X X X
SDCV01 X X X X
ALR111 X X X X
ALR121 X X X X
ALE111 X X X X
S2LP131 X X X X
SEC402 X X X X
SEC401 X X X X
SNT401 X X X X
SNT501 X X X X
SNT411 X X X X
SNT511 X X X X
SEA4D X X X X
SED2D X X X X
SED3D X X X X
SED4D X X X X
SWD2D — — — —
SBT4D X X X X
SBR4D X X X X
SBA4D X X X X
*9: SSC57D-F and SSC57S-F comply with Marine Standards. SSC57D-S and SSC57S-S do not comply with Marine
Standards.
SSC57D and SSC57S are compliant to the standard, which includes SPW481, SPW482, SPW484, and SCP451 as its
components.
*10: SNB10D is compliant to the standard, which includes SPW481, SPW482, SPW484, and SSB401 as its components.
*11: SNT10D is compliant to the standard, which includes SPW481, SPW482, and SPW484 as its components.
*12: SA143-H•C, SDV144-S•C, SDV521-S•C, SDV531-L•C, and SDV541-S•C do not comply with Marine Standards.
*13: SDV531-L style code S3 or later complies with Marine Standards.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Oct. 5, 2018-00
<<Contents>> <<Index>> 12
Table List of Conformity Standards 3 (3/4)
Marine Standards
Model ABS
BV LR
(American Bureau of DNV GL
(Bureau Veritas) (Lloyd’s Register)
Shipping)
S1BB4D X X X X
SBD2D X X X X
SBD3D X X X X
SBD4D X X X X
SRM53D X X X X
SRM54D X X X X
SBM54D X X X X
AVR10D (*14) X X X X
STA4S — — — —
STA4D — — — —
STB4S — — — —
STB4D — — — —
YCB301 X X X X
KS1 X X X X
AKB331 X X X X
AKB651 X X X X
AKB652 — — — —
AKB611 X X X X
AKB131 — — — —
AKB132 — — — —
AKB135 — — — —
AKB136 X X X X
AKB161 X X X X
AKB162 — — — —
S2CP471 — — — —
SCP461 X X X X
SCP451 X X X X
SSB401 X X X X
SPW481 X X X X
SPW482 X X X X
SPW484 X X X X
AIP602 — — — —
SYEPD5D — — — —
SYEPD4D — — — —
SYEPD4B — — — —
SYEPA5D — — — —
SYEPA4D — — — —
SYK301 — — — —
SYK501W — — — —
SYK501 — — — —
SYK101W — — — —
SYK101 — — — —
X: Compliant —: Non-compliant NA: Not Applicable
*14: AVR10D-0 does not comply with Marine Standards.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Nov. 15, 2019-00
<<Contents>> <<Index>> 13
Table List of Conformity Standards 3 (4/4)
Marine Standards
Model ABS
BV LR
(American Bureau of DNV GL
(Bureau Veritas) (Lloyd’s Register)
Shipping)
SYK502 — — — —
SYPP10 — — — —
S1XEU4D — — — —
S1XK301 — — — —
S1XK601 — — — —
X: Compliant —: Non-compliant NA: Not Applicable
TRADEMARK ACKNOWLEDGMENT
The names of corporations, organizations, products and logos herein are either registered trademarks or trademarks
of Yokogawa Electric Corporation and their respective holders.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 32P01B60-01EN Jan. 17, 2020-01
Subject to change without notice.