Engineering Standard: IPS-E-PR-400
Engineering Standard: IPS-E-PR-400
ENGINEERING STANDARD
FOR
ORIGINAL EDITION
JULY 1994
This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner.
Neither whole nor any part of this document may be disclosed to any third party, reproduced, stored in
any retrieval system or transmitted in any form or by any means without the prior written consent of the
Iranian Ministry of Petroleum.
July 1994 IPS-E-PR-400
0. INTRODUCTION ............................................................................................................................. 3
1. SCOPE ............................................................................................................................................ 4
1.1 General..................................................................................................................................... 4
2. REFERENCES ................................................................................................................................ 4
3. DEFINITIONS AND TERMINOLOGY ............................................................................................. 5
4. SYMBOLS & ABBREVIATIONS .................................................................................................... 8
5. UNITS.............................................................................................................................................. 9
6. DESIGN........................................................................................................................................... 9
6.1 Internal Combustion Engines, Cooling Systems................................................................. 9
6.1.1 General.............................................................................................................................. 9
6.1.2 Methods ............................................................................................................................ 9
6.1.3 Heat transfer..................................................................................................................... 9
6.1.4 Calculation of heat lost to cylinder’s inside surface ................................................... 9
6.1.5 Requirements of cooling system ................................................................................. 10
6.1.5.1 Design features ...................................................................................................... 10
6.1.5.2 Equipment/devices and process design.............................................................. 10
6.2 Reciprocating Compressors’ Cooling System .................................................................. 11
6.2.1 General............................................................................................................................ 11
6.2.2 Methods .......................................................................................................................... 11
6.2.3 Calculation of heat rejected to circulating cooling water.......................................... 12
6.2.4 Requirements................................................................................................................. 12
6.2.4.1 General .................................................................................................................... 12
6.2.4.2 Cylinder jackets cooling ........................................................................................ 12
6.2.4.3 Integral cooling system ......................................................................................... 12
6.2.4.4 Packing box cooling system ................................................................................. 13
6.2.4.5 Lubricating oil cooling system ............................................................................. 13
6.2.5 Design features.............................................................................................................. 13
6.2.6 Piping and appurtenances............................................................................................ 14
6.2.7 Coolers............................................................................................................................ 15
6.2.8 Cooling water reservoir................................................................................................. 16
6.2.9 Circulating pumps ......................................................................................................... 16
APPENDICES:
1
July 1994 IPS-E-PR-400
6.3 Designing Requirements and Features for Inter cooling and After cooling Facilities . 22
2
July 1994 IPS-E-PR-400
0. INTRODUCTION
The primary purpose of IPS standard specifications on "Process Design of General Heating &
Cooling and Flushing Systems" is to establish minimum requirements and design criteria needed in
process design of the following standards:
3
July 1994 IPS-E-PR-400
1. SCOPE
1.1 General
Note 1:
This standard specification is reviewed and updated by the relevant technical committee on
Feb. 1999. The approved modifications by T.C. were sent to IPS users as amendment No. 1
by circular No. 46 on Feb. 1999. These modifications are included in the present issue of IPS.
Note 2:
This standard specification is reviewed and updated by the relevant technical committee on
Oct. 2004. The approved modifications by T.C. were sent to IPS users as amendment No. 2
by circular No 243 on Oct. 2004. These modifications are included in the present issue of
IPS.
2. REFERENCES
Throughout this Standard the following dated and undated standards/codes are referred to. These
referenced documents shall, to the extent specified herein, form a part of this standard. For dated
references, the edition cited applies. The applicability of changes in dated references that occur
after the cited date shall be mutually agreed upon by the Company and the Vendor. For undated
references, the latest edition of the referenced documents (including any supplements and
amendments) applies.
4
July 1994 IPS-E-PR-400
3.1 After-Cooler
After-Cooler is a species of surface condenser in which compressed air/gas is cooled after
compression.
3.2 Air-Cooler
Air-Cooler is an exchanger in which the heating surface is indirectly cooled by air.
5
July 1994 IPS-E-PR-400
3.5 Combustion
Combustion is the rapid oxidation of fuel accompanied by production of heat.
3.6 Condensation
Condensation is the constituent of air or gas when liquified due to certain reduction in coolant
temperature against the air/gas inlet temperature.
3.11 Inter-Cooler
Inter-cooler is a species of surface condenser placed between the two consecutive cylinders of a
multistage compressor so that, the heat of compression generated in the first stage cylinder may be
removed (in part or whole) from the compressed air/gas, as it passes through the next stage
cylinder’s inter-cooler.
6
July 1994 IPS-E-PR-400
Note:
The acceptable standard for reciprocating compressor industry, tolerance of ±3 percent is
applicable to capacity. Because of this tolerance on capacity, the manufacturer will increase
the required capacity by 3 percent prior to sizing the compressor.
7
July 1994 IPS-E-PR-400
8
July 1994 IPS-E-PR-400
PI = Pressure Indicator
PA = Pressure Alarm
PRC = Pressure Recorder Controller
PDI = Pressure Differential Indicator
PRV = Pressure Relieve Valve
TIC = Temperature Indicator Controller
THA = Temperature High Alarm
TI = Temperature Indicator
TCV = Temperature Control Valve
TSHA = Temperature Switch High Alarm
TT = Temperature Transmitter
V = Vent
5. UNITS
This Standard is based on International System of Units, (SI) except where otherwise specified.
6. DESIGN
6.1.1 General
When the fuel is burnt in the cylinder, a part of the heat developed during combustion, flows to
cylinder walls. If the temperature of cylinder walls is allowed to rise above a certain limit (about
150°C) then the oil lubricating the piston starts evaporating. This action damages both piston and
cylinder. The high temperature developed may sometimes cause excess thermal stresses and
hence cracking of the cylinder head and piston. The hot spots may also cause preignition in the
combustion space. In order to avoid any damages, the heat flowing to the cylinder walls must be
carried away.
6.1.2 Methods
All heat carried away from an engine shall finally be conveyed to atmosphere. However, the
methods of cooling may be divided into two main groups of direct or air-cooling and indirect or
liquid-cooling.
9
July 1994 IPS-E-PR-400
6.1.5.2.1 Unless otherwise specified, the process design of the following equipment/devices shall
constitute a combined, self-contained closed water cooling system for internal combustion engines.
a) Soft water circulating pumps.
10
July 1994 IPS-E-PR-400
6.2.1 General
6.2.1.1 When air/gas is compressed, its temperature and pressure will rise and a considerable heat
will be generated due to rise in temperature. Part of the heat so, generated, will be transferred to
cylinder wall rising the wall temperature which will reduce the lubricating efficiency in cylinder and
might result in, an overheated and warped rod. The heat of compression will also results in a loss
by boosting of pressure.
6.2.1.2 It has been found desirable to remove part of this heat traveled to cylinder wall in order to
get rid of any damage to cylinder barrel and heads. Any heat removed also results in a slight
reduction in the compression brake kilowatt.
6.2.1.3 Unless otherwise specified, the following standards, codes, and specifications to the extent
specified herein, form the Company’s minimum requirement for the process design of a complete
closed cooling water system for reciprocating compressor cylinder jackets, it’s engine cylinder
jackets, it’s lubricating oil cooling circuit and the compressor packing box cooling in part or in
integral.
6.2.1.4 Throughout this Standard, references are mainly made to the API Standard 618 and API
Specification 11 P along with other internationally acceptable codes, standards and engineering
practices and many important applied design book and resources.
6.2.2 Methods
6.2.2.1 The heat traveled to the cylinder wall can be carried off either by direct air-cooling or by
indirect liquid cooling process. Most cylinders have water jackets to remove the heat and maintain
required cylinder and /or liner temperature. Usually small kilowatt power units may use air-cooling
system.
6.2.2.2 According to API Standard 618, three following methods of cooling may be used, depending
on the extended period of time where, cylinders will or will not be required to operate fully unloaded.
a) Thermosyphon coolant systems may be used where cylinders will not be required to operate
fully unloaded for extended period of time and either (1) expected maximum discharge
temperature is between 88°C and 99°C or (2) the rise in adiabatic gas temperature is less than
66°C (see Fig. B.1 (b) in Appendix "B").
b) Static field coolant system may be used when the cylinders will not be required to operate
fully unloaded for extended period of time. The expected maximum discharge temperature is
less than 88°C and the rise in adiabatic gas temperature (difference between suction and
discharge temperatures based on the isentropic compression) is less than 66°C (see Fig. B.1 (a)
in Appendix "B").
11
July 1994 IPS-E-PR-400
c) Forced liquid coolant system shall be provided, where cylinders will operate fully unloaded for
extended period of time and either (1) the expected maximum discharge temperature is above
99°C or (2) the rise in adiabatic gas temperature is 66°C or greater (see Fig. B.1, (c) of Appendix
"B").
6.2.2.3 Unless otherwise specified, forced closed cooling water system shall be used for taking
away the heat traveled to cylinder wall. The water shall be pumped through the secondary cooler
and then back to cylinder jacket for reuse.
6.2.2.4 The Vendor is required to evaluate the Company’s proposed standard coolant system as
specified under Clause 6.2.2.3 above against his own standard coolant system or any other
standard coolant system and shall recommend the use of the most efficient, effective and techno-
commercially feasible other coolant system together with strong convincing proves. However the
employment of any other coolant system will solely be upon the Company’s written approval.
6.2.3.1 The Vendor/Manufacturer if deemed necessary may furnish an integral closed cooling water
system for compressor cylinder jackets, engine cylinder jackets, lubricating oil circuit and
compressor packing boxes, he should provide separate design data on the quantity of heat rejected
to cooling system from each section separately and as a whole along with quantity of water
circulating and pressure drops.
6.2.4 Requirements
6.2.4.1 General
A closed cooling water system for packaged reciprocating compressor shall be furnished either in
separate for cylinder jacket cooling or integral with engine cylinder, lubricating oil and cooling of
compressor packing boxes, within the temperature limit recommended by the manufacturer for the
specified compression services.
6.2.4.2.1 Unless otherwise specified, the following requirements shall be considered when the
closed cooling water system is used only for cylinder jacket cooling:
a) The cylinder jackets when designed, all protective measures must be taken to prevent the
process gas flow into the cooling water circuit.
b) A liberal supply of cooling water for cylinder jacket and cylinder head must be maintained.
c) The cylinder cooling system provided shall be designed to prevent gas condensation in the
cylinder, that may dilute or remove lubricant or may cause knocking.
d) The use of untreated or scale depositing water that will cause fouling and plugging of the
water passage, reducing cooling efficiency should strongly be avoided.
6.2.4.3.1 Not withstanding the requirements set-forth under clause or 6.2.4.2 unless otherwise
specified, the following requirement, shall be considered when the closed cooling water system is
12
July 1994 IPS-E-PR-400
used for an integral compressor and engine cylinder jackets, lubricating oil and packing box cooling:
a) The cooling circuit shall include engine lubricating oil, engine cylinder jacket, compressor
cylinder jacket and packing boxes.
b) Elevated deaerating type reservoir with gage glass, vent line, cooling water level switches,
overflow, filling connections and drains.
c) Cooling water temperature control shall be provided.
d) Plugged manual drain connection(s) for complete draining of the system.
6.2.4.4.1 If a separate closed cooling circuit is specified for the piston rod pressure packing (see
Fig. D.1), the criteria given in 6.2.4.4.2 and 6.2.4.4.3 shall be followed.
6.2.4.4.2 When packing is cooled by forced circulation, the Vendor shall supply a suitable filter of
appropriate mesh rating.
6.2.4.4.3 Where cooling of packing is required, the Vendor shall be responsible for determining and
informing the Company on the minimum requirements such as flow, pressure, pressure drop and
temperature as well as filtration and corrosion protection criteria.
6.2.4.5.1 Since cooling of the lubricating oil shall be considered as an integral part of the closed
cooling water system, the following recommendations apply:
a) Since liquid coolant is used, the design should minimize the chance of the lube oil being
contaminated.
b) The coolant pressure should be less than the lube oil pressure at all time.
c) Adequate cooling water circulating rate for removal of total heat rejection to lube oil, should be
maintained.
6.2.5.1 Unless otherwise specified, the provisions set-forth under 6.1.5.1 of this Standard when
applicable, shall be considered as the design feature for a closed cooling water system for
reciprocating compressors.
6.2.5.2 The cooling water supply to each cylinder jacket shall be at temperature of at least 6°C
above gas inlet temperature as per API Standard 618.
6.2.5.3 The quantity of cooling water circulation by each pump shall be regulated to maintain a rise
in cooling water temperature across only of the individual cylinder and cylinder head between 6°C to
11°C (as per API Standard 618).
6.2.5.4 An oil detection device shall be provided in the water supplied to pumps suction head.
6.2.5.5 In case of compressor cylinder cooling, the following should be observed:
a) Coolant inlet temperature less than 6°C greater than gas inlet temperature may cause gas
constituent condensation.
b) Cooling water rate and velocity shall be provided by the Vendor to prevent fouling of cylinder
jacket system.
c) Cooling water exit temperature more than 17°C above gas inlet temperature may cause
13
July 1994 IPS-E-PR-400
6.2.6.1 Unless otherwise specified by the Company, the Vendor shall supply a closed cooling water
piping system for all equipment mounted on the compressor package. The piping shall be arranged
to provide single flanged inlet and outlet connections at the edge of the skid. Necessary valves and
bypasses shall be provided for temperature control.(See Figs. A.1, C.1, & E.1 of Appendices "A",
"C", & "E" as the case may be).
6.2.6.2 Unless otherwise specified, piping design, inspection and testing shall be in accordance with
relevant IPS-E-PR-440.
6.2.6.3 The piping of the cooling system shall be pre-piped, factory skid mounted and complete with
various pressure and temperature indicators, alarm and other specific instrumentation required.
6.2.6.4 The inlet water connections shall be located at the lowest point of cylinder, so that water can
easily be drained from cylinder when compressor is shut down.
6.2.6.5 The discharge connection should be at the highest point to ensure of complete filling of
water jackets with no air pockets.
6.2.6.6 The water piping should be provided with a valve controlling the flow of water.
6.2.6.7 If the Company does not specify the extent of closed cooling water piping, the Vendor shall
supply piping with single inlet and a single outlet connection on each cylinder requiring cooling (see
Appendix "B", Fig. B.1, Plan c).
6.2.6.8 Coolant piping shall be arranged so that air can not be trapped. Where air trap can not be
avoided, vent equipment shall be provided. Low points shall have drains.
6.2.6.9 Both, cooling water inlet line and cooling water outlet to each compressor cylinder shall be
provided with a gate valve. A globe valve with union shall be provided on the main outlet line from
each cylinder. A sight flow and temperature indicator shall be installed in the outlet line from each
cylinder.
Note:
Where more than one cooling water inlet and outlet point exist on a cylinder, one sight flow
indicator and regulating globe valve shall be provided for each outlet point on each cylinder.
14
July 1994 IPS-E-PR-400
6.2.6.10 For the packaged reciprocating compressor, Vendor shall supply all necessary piping,
valves and fittings for all instrument and instrument panel.
6.2.6.11 The cylinder cooling system piping shall be equipped with vents and low point drains.
Manual block valves to permit working on the compressor unit or auxiliary equipment without
draining the engine cooler shall be furnished.
6.2.6.12 Internals of piping and appurtenances shall be accessible through openings or by
dismantling for complete visual inspection and cleaning.
6.2.6.13 External drain and vent piping shall be of Schedule 80 carbon steel and of not less than
DN 25 (Diameter Nominal 25 mm) size. However vent connection in the packing case and inter
connecting tubing, shall be of 300 series stainless steel and at least 6.35 mm outside diameter
(OD). With a minimum wall thickness of 1.24 mm.
6.2.7 Coolers
6.2.7.1 Unless otherwise specified by the Company, shell and tube heat exchanger shall be used
for forced closed cooling water system on reciprocating compressors and internal combustion
engine cylinder cooling.
6.2.7.2 The Vendor shall advise, when a cooler other than shell and tube exchanger is preferred.
However the use of any cooler other than shell and tube, shall only be made upon the Company’s
written approval.
6.2.7.3 Heat exchanger’s tube-bundle shall be designed removable with clean and non corrosive
fluid flowing through the tube side.
6.2.7.4 The mechanical design, testing and inspection of the shell and tube exchanger in closed
cooling water system shall be in accordance with IPS-G-ME-220, unless otherwise specified.
6.2.7.5 Unless otherwise specified, process design of shell and tube exchanger shall be in
accordance with the following conditions:
- Velocity in exchanger tubes 1.5-2.5 m/s
- Maximum allowable working pressure ≥ 690 kPa (ga) or 6.9 bar (ga)
- Test pressure 1.5 × MAWP
- Maximum pressure drop 100 kPa or (1 bar)
- Maximum inlet temperature 32°C
- Maximum outlet temperature 49°C
- Maximum temperature rise 17°C
- Minimum temperature rise 11°C
- Shell corrosion allowance 3.2 mm
- Fouling factor on water side 0.35 m2. K/kW
Note:
The Vendor shall notify the Company if the criteria for minimum temperature rise and
velocity in exchanger tube result in a conflict. The criterion for velocity in exchanger tubes is
intended to minimize water-side fouling; the criterion for minimum temperature rise is
intended to minimize the use of cooling water. The Company will approve the final selection.
(Mod. To API Std. 618, Clause 2.1.3).
6.2.7.6 The following recommendations shall be applied for the coolers used in closed cooling water
system in general and for the lubricating oil cooler in particular:
15
July 1994 IPS-E-PR-400
a) The heat exchange surface should be located and arranged so that it can be removed for
maintenance or replacement.
b) Provide means for draining both sides of the cooler during shutdown.
Cautions:
These drains need to be protected from draining the reservoir during operation.
6.2.8.1 Unless otherwise specified, Vendor mechanical design, inspection and testing shall be in
accordance with IPS-C-ME-100, 110, 120 and 130 & IPS-E-ME-100, 110, 120 and 130 Standards.
6.2.8.2 The cooling water reservoir should be located above the highest point of the closed cooling
water system.
6.2.8.3 Working capacity of the reservoir shall be at least equal to the normal capacity of the pump
per 5- minutes.
6.2.8.4 The reservoir shall be furnished with appropriate level indicator, with sufficient length
covering working range of the reservoir and normal expansion and contraction of the system.
6.2.8.5 Level control system shall be provided for automatic control and maintaining of desired level
and pumping suction head.
6.2.8.6 The reservoir shall be furnished with level switches and alarm, vent/overflow and filling
connection and drain.
6.2.8.7 The reservoir vent/overflow line size shall have a diameter not less than ½ the diameter of
the pump suction line.
6.2.8.8 The design of the suction line from the reservoir to the pump shall not provide any air
pocket.
6.2.8.9 Reservoir shall be furnished with necessary chemical injection facilities to control more
corrosive nature of circulating water.
6.2.8.10 Continuous steam injection line shall be provided for required rate of steam flow to the
reservoir’s top position for blanketing and spilling out the air.
6.2.8.11 The Company shall specify wether the installation is to be indoor or outdoor and the
climatic conditions, including maximum and minimum temperature. The Vendor shall take all
necessary protective measures in design by proper winterizing of the reservoir and other auxiliaries
in cooling water system.
16
July 1994 IPS-E-PR-400
6.2.9.1 Unless otherwise specified, two horizontally mounted centrifugal pumps(main and spare)
shall be furnished by the Vendor (see Figs. A.1, C.1, D.1 & E.1. in Appendices "A", "C", "D" & "E").
6.2.9.2 All process design requirements and criteria specified in IPS-E-PR-740 and API 610 and not
covered hereinunder shall be used as integral part of this Standard.
6.2.9.3 The equipment and auxiliaries, shall be designed for a minimum service life of 20 years and
at least 3 years of uninterrupted operation. This shall be considered as a design criterion.
6.2.9.4 The equipment rated operating point shall be specified on the data sheets along with any
other anticipated operating conditions.
6.2.9.5 The Vendor shall specify on the data sheets the NPSHR when pump is operated on water at
the rated capacity and rated speed, when water temperature is less than 66°C.
6.2.9.6 Pumps shall be designed for mechanical sealing in accordance with requirements of IPS-E-
PM-100, unless otherwise noted on data sheets. Pumps shall have mechanical seals with flushing
line to maintain a seal chamber pressure greater than the maximum suction pressure and, to
ensure that the temperature and pressure in the seal chamber prevent vaporization while providing
continuous flow through the seal chamber.
6.2.9.7 Pumps shall be provided with constant-speed motor drivers or steam turbine drive, (if
required by the Company). Motor driver of the pumps(main and spare) shall be on the secondary
selective electric system. (Emergency Power).
6.2.9.8 Each pump shall be designed for capacity required, to maintain complete cooling
requirement of the system.
6.2.9.9 Each pump shall be operative as the spare of the other and shall automatically be started
upon loss of pressure in the discharge of the main pump.
17
July 1994 IPS-E-PR-400
APPENDICES
APPENDIX A
18
July 1994 IPS-E-PR-400
APPENDIX B
19
July 1994 IPS-E-PR-400
APPENDIX C
20
July 1994 IPS-E-PR-400
APPENDIX D
21
July 1994 IPS-E-PR-400
APPENDIX E
6.3.1 Unless otherwise specified by the Company, Vendor shall supply water cooled intercoolers
and aftercoolers for skid mounted reciprocating compressors.
22
July 1994 IPS-E-PR-400
6.3.2 Unless otherwise specified, the process design of the intercoolers and aftercoolers shall be
based on IPS-E-PR-750 "Process Design of Compressors" and the Appendix "C" thereof.
6.3.3 Not withstanding Clause 6.3.2 above, shell and tube heat exchangers shall be used for
intercooling and aftercooling and shall be in conformity with API 619, and API 680, on the following:
a) Water-cooled intercoolers and aftercoolers for nonflammable, nontoxic services (air, inert gas,
and so forth) shall be designed and constructed in accordance with the ASME Boiler and
Pressure Vessel Code. For flammable or toxic gas services, TEMA Class R heat exchangers
shall be furnished and shall be in accordance with API Standard 660 and Section VIII, Division 1
of the ASME Code.
b) Water shall be on the tube side of the heat exchanger.
c) Unless otherwise specified the water side of shell and tube exchanger shall be designed in
accordance with, Clause 6.2.7.5 of this Standard.
d) Intercoolers shall be mounted separately or on the machine, as specified by the Company.
e) Relief valves shall be provided on the process side of both intercoolers and aftercoolers.
f) Rupture discs on the shell side shall be furnished only when specified by the Company.
* Tubular Exchanger Manufacturers Association, Inc, 331 Madison Avenue, New York, N.Y.
10017.
6.3.4 Intercoolers and aftercoolers shall be provided by the Vendor, with facilities to separate,
collect and discharge condensate through a continuous drainer. Condensate collection pots shall be
per the ASME Code, Section VIII or other pressure vessel code specified by the Company.
6.3.5 Air-cooled heat exchanger shall only be used for skid mounted compressor’s intercoolers and
aftercoolers upon the Company’s requirements and approval.
6.3.6 When air-coolers are specified by the Company, they shall conform either to API Standard
661, or shall be of Vendor’s standard. Vendor shall inform the Company on the advantages of
Vendors’s standard and shall acquire Company’s written approval.
6.3.7 Unless otherwise specified, air-cooled heat exchangers used for intercoolers and aftercoolers
shall have automatic temperature control. This control may be accomplished by louvers, variable
pitch fans, bypass valve or by any combination thereof. The proposed control systems shall be
approved by the Company.
6.3.8 Caution should be exercised because of the susceptibility of heat-exchangers and their
supporting structures to pulsation-induced vibration.
6.3.9 Thermometer wells should be located at the inlet and outlet of the intercoolers and aftercooler
and temperature reading should be taken at these points.
23