Main Features: 4 Loop Modular Power Controller
Main Features: 4 Loop Modular Power Controller
Main features
4 independent loop control unit.
Compact, ready to use, equipped also with
fieldbus interface.
3 4 5 13
2
12
1 7
11
10 8
9
8 1. DIN rail frontal
2. power terminal: screws
3. power terminal
4. ventilation grid (attention NOT obstruct)
5. hook/release device back DIN rail
6. hole for screws
7. microswitchs of configuration
8. standard digital communication
9. rotative selector switch
10. connectors J1, J2, J3, J4
11. fuses-holder (only for 30KW and 60KW models)
12. fuses-holder terminal (F1, F2, F3, F4)
14 13. power terminal (U1, U2, U3, U4)
14. ventilation grid (attention NOT obstruct)
DIMENSIONS - INSTALLATION
19,5
4 101,5
4
35
140
140
132
92,5
140 109,5
147
140 42 4 101,5
19,5
4
35
147
140
111,5
132
92,5
82
182
109,5
195
Node address: setting by double rotative
DI1, DI2 [digital inputs] selector
Connector: J2 Connector S1 / S2: 2xRJ114/4, RS485 2
wires insul. 1500V
Function Connector S3: 10 pins for flat cable
default not enable (configurable)
Type SERIAL 2 [fieldbus]
PNP, 24Vdc, 8mA (isol. 3500V) Connectors: S4 / S5
TECHNICAL DATA OUTPUTS Function
external fieldbus
INPUTS OUT 1...4 [heating control]
Protocol
IN1...IN4 [process analog inputs] outputs connected to solid state relay Modbus RTU _____115Kbps
Connector: J4 CANopen ________10K...1Mbps
Function Profibus DP ______9,6...12Mbps
Function default heating control (configurable) DeviceNet________125K...500Kbps
default process variable (configurable) Ethernet Modbus TCP 10/100Mbps
Sampling time
120msec the four inputs OUT 5...8 [cooling control] See accessories
Accuracy Connector: J1
0,2% FS ±1 steps at 25°C. (16000 points)
Thermal drift Function MICROSWITCHES
0,005% FS/°C default cooling control (configurable) 8 dip switches are available to select
Type Type wiring mode and different functionalities.
• Thermocouples ITS90: • Relay: NO, max 3A, 250V/30Vdc,
J, K, R, S, T, custom (IEC584-1, CEI EN cosϕ = 1, resistive load
60584-1, 60584-2). • Logic: 24Vdc, 35mA POWER
Internal cold junction compensation with • Continuous:
automatic compensation. • voltage: 0/2...10V, ±10V, max 25mA SSR [integrated power element]
Selectable temperature range: °C/°F short circuit protection
• Thermoresistance: Pt100 DIN 43760 • current: 0/4...20mA, 500Ω max Rated voltage: 480Vac
Max. resistance 20Ω • insulation: 3500V Work voltage range: 24...530Vac
Selectable temperature range: °C/°F • Triac: 230V/4Amp AC51 Non-repetitive voltage: 1200Vp
• Voltage: range 0/12...60mV, Ri > 1MΩ (1A for four) Switching voltage for zero: < 20V
0/0,2…1V, Ri > 1MΩ custom 60mV at 32 (2A for two) Rated frequency: 50/60Hz (self-adjusting)
sections Rated current AC51
• Current: range 0/4...20mA , Ri = 50Ω OUT 9...10 [alarms] GFX-4 30kW: 16Amp
custom 20mA at 32 sections Connector: J1a/J1 GFX-4 60kW: 32Amp
GFX-4 80kW: 57Amp
IN5...IN8 [auxiliary analogue inputs] Function Non-repetitive overcurrent [t=20msec]
Connector: J3 default alarms (configurable) GFX-4 30kW: 400A
GFX-4 60kW: 600A
Function Type GFX-4 80kW: 1150A
default analog inputs reading Relay: NO, max 5A, /30Vdc, cosϕ = 1 I2t for melt [t=1...10msec]
Sampling time GFX-4 30kW: 645A2s
480msec for TC, voltage GFX-4 60kW: 1010A2s
Accuracy LEDS GFX-4 80kW: 6600A2s
1% FS ±1 steps at 25°C. Dv/dt critical with deactivated output:
Type RN . . . . . .RUN state of the CPU 1000V/µsec
• Thermocouple ITS90: ER . . . . . .error Rated insulation voltage In/Out:
J, K, R, S, T, custom (IEC584-1, CEI EN DI1 . . . . . .DI1 digital input state 4000V
60584-1, 60584-2). DI2 . . . . . .DI2 digital input state
Internal cold junction compensation with O1 . . . . . .Out.1 main input state
automatic compensation. O2 . . . . . .Out.2 main input state GENERAL FEATURES
• Voltage: O3 . . . . . .Out.3 main input state
range 0/12...60mV, Ri > 1MΩ O4 . . . . . .Out.4 main input state Power supply:
24Vdc ±25%, max 8VA
IN9...IN12 [internal CT input] Protection class:
Connector: internal connection IP20
COMMUNICATION PORTS Working temperature range:
Function 0...50°C (see dissipation curves)
default internal CT reading PORT 1 [local bus] Storage temperature range:
Sampling time Connectors: S1 / S2 / S3 -20...+70°C
60msec for CT Relative humidity:
Accuracy Function: local bus 20...85% UR non-condensing
1% FS ±1 steps at 25°C. Protocol: Modbus RTU Installation:
Type Baud Rate: 115Kbps (default) EN50022 DIN rail or panel by screw
internal CT: 50mAac, 50/60Hz, Ri = 10Ω setting 1200...115Kbps Dimensions:
ELECTRICAL CONNECTIONS
Load 1 OUT 5 no
Load 2 OUT 6 no
Load 3 OUT 7 no
Load 4 no
OUT 8
J1 4 +VI
c 3 Tx/Rx-
6
2 Tx/Rx+
S1
OUT 9
no 1 GNDI
c J1a 4 +VI
3 Tx/Rx-
OUT 10
no 9
9
2 Tx/Rx+ S2
1 GNDI Port 1
1
Green
POWER SUPPLY
18...32Vdc Red J2 S3
+24Vdc
Yellow
7
Yellow
1
Yellow
Yellow
IN 5 S4
Yellow
IN 6
J3
Yellow
IN 7 Port 2
IN 8 12
1
IN 1
S5
IN 2
J4
IN 3
IN 4
12
power
Model without fuses-holder Model with fuses-holder
F1 F2 F3 F4
F1 F2 F3 F4 U1 U2 U3 U4
U1 U2 U3 U4
* UL certification
ORDER CODE
M Modbus RTU
60KW 60
P Profibus DP
80KW 80
C CANopen
C1 Euromap 66
D DeviceNet
AUXILIARY OUTPUTS
E Ethernet Modbus TCP
Absent 0
E1 Ethernet IP
Relay R
Logic D FUSES
Continuous C 0 Absent
AUXILIARY INPUTS
1 1 Current Transformer
2 4 Current Transformers
1 Current Transformer
3
+ 4 Linear inputs
4 Current Transformers
4
+ 4 Linear inputs
GEFRAN spa reserves the right to make aesthetic or functional changes at any time and without notice.