Product data sheet 3RV2011-1BA10
CIRCUIT-BREAKER SZ S00,
FOR MOTOR PROTECTION, CLASS 10,
A-REL. 1.4...2A, N-RELEASE 26A,
SCREW CONNECTION, STANDARD SW. CAPACITY
General technical data:
product brand name SIRIUS
product designation 3RV2 circuit breaker
Size of the circuit-breaker S00
Trip class CLASS 10
Protection class IP / on the front IP20
Degree of pollution 3
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature
• during storage °C -50 … +80
• during operating °C -20 … +60
• during transport °C -50 … +80
Resistance against shock 25g / 11 ms
Impulse voltage resistance / rated value kV 6
Insulation voltage / rated value V 690
Active power loss / total / typical W 6
Item designation
• according to DIN 40719 extendable after IEC 204-2 / according F
to IEC 750
• according to DIN EN 61346-2 F
3RV2011-1BA10 subject to modifications
Page 1/ 6 09/14/2012 © Copyright Siemens AG 2012
Mechanical operating cycles as operating time
• of the main contacts / typical 100,000
• of the auxiliary contacts / typical 100,000
Type of the driving mechanism / motor drive No
Design of the operating mechanism selector switch
Product function
• overload protection Yes
• phase disturbance recognition Yes
Product component
• auxiliary switch No
• undervoltage release mechanism No
• trip indicator No
Product extension / optional / motor drive No
Main circuit:
Number of poles / for main current circuit 3
Operating voltage / at AC-3 / rated value / maximum V 690
Operating current / at AC-3 / at 400 V / rated value A 2
Service power / at AC-3
• at 400 V / rated value W 750
• at 500 V / rated value W 750
• at 690 V / rated value W 1,100
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / 1/h 15
maximum
Arrangement of electrical connectors / for main current circuit Top and bottom
Adjustable response current
• of the non-delayed short-circuit release A 26 … 26
• of the current-dependent overload release A 1.4 … 2
Service power / at AC-3 / at 230 V / rated value W 370
Continuous current / rated value A 2
Auxiliary circuit:
Product extension / auxiliary switch Yes
Number of NC contacts / for auxiliary contacts / instantaneous 0
switching
Number of NO contacts / for auxiliary contacts / instantaneous 0
switching
Number of change-over switches / for auxiliary contacts 0
Inputs/ Outputs:
Number of digital inputs 0
3RV2011-1BA10 subject to modifications
Page 2/ 6 09/14/2012 © Copyright Siemens AG 2012
Short-circuit:
Breaking capacity limit short-circuit current (lcu)
• at 400 V / rated value A 100,000
• at 500 V / rated value A 100,000
• at 690 V / rated value A 10,000
Design of the overcurrent release and short-circuit release thermomagnetic
Installation/mounting/dimensions:
mounting position any
Type of mounting screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 60715
Width mm 45
Height mm 97
Depth mm 91
Distance, to be maintained, to the ranks assembly
• forwards mm 0
• backwards mm 0
• upwards mm 50
• downwards mm 50
• sidewards mm 0
Distance, to be maintained, to earthed part
• forwards mm 0
• backwards mm 0
• upwards mm 50
• sidewards mm 30
• downwards mm 50
Distance, to be maintained, conductive elements
• forwards mm 0
• backwards mm 0
• upwards mm 50
• downwards mm 50
• sidewards mm 30
Connections:
Product function
• removable terminal for main circuit No
• removable terminal for auxiliary and control circuit No
Design of the electrical connection
• for main current circuit screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
3RV2011-1BA10 subject to modifications
Page 3/ 6 09/14/2012 © Copyright Siemens AG 2012
• solid 2x (0.75 ... 2.5 mm²), 2x 4 mm²
• finely stranded
• with conductor end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for main contacts 2x (18 ... 14), 2x 12
Certificates/approvals:
Verification of suitability CE / UL / CSA / CCC
• für Staubexplosionsschutz für Zone 21/22 no
• for gas explosion protection for zone 1/2 no
General Product Approval For use in Declaration of
hazardous Conformity
locations
Test Certificates
other Special Test Type Test
Certificate Certificates/Test
Report
Shipping Approval
other
other
UL/CSA ratings
yielded mechanical performance (hp)
• for single-phase squirrel cage motors
• at 230 V / rated value hp 0.125
• for three-phase squirrel cage motors
• at 460/480 V / rated value hp 0.75
• at 575/600 V / rated value hp 1
Operating current (FLA) / for three-phase squirrel cage motors
• at 480 V / rated value A 1.6
• at 600 V / rated value A 1.7
Safety:
B10 value / with high demand rate
• according to SN 31920 50,000
T1 value / for proof test interval or service life
3RV2011-1BA10 subject to modifications
Page 4/ 6 09/14/2012 © Copyright Siemens AG 2012
• according to IEC 61508 a 10
Failure rate (FIT value) / with low demand rate
• according to SN 31920 FIT 50
Proportion of dangerous failures
• with low demand rate / according to SN 31920 % 40
• with high demand rate / according to SN 31920 % 40
Protection against electrical shock finger-safe
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
CAx-Online-Generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RV2011-1BA10/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RV2011-1BA10
3RV2011-1BA10 subject to modifications
Page 5/ 6 09/14/2012 © Copyright Siemens AG 2012
last change: Sep 12, 2012
3RV2011-1BA10 subject to modifications
Page 6/ 6 09/14/2012 © Copyright Siemens AG 2012