PC57.13.
   IEEE Guide for Grounding of
Instrument Transformer Secondary
       Circuits and Cases
OUTLINE
 Scope
 References
 Need for grounding; Warning
 Definition of Instrument transformers
 Grounding secondary circuits
  Grounding at a single location
  Conductor size for connecting to ground
Scope
 The scope of the guide includes the grounding
 practices presently used and the practices that
 were not previously reported. Specifically, the
 issue of the grounding of cases of electronic
 transducers is addressed.
Covers
 The practices described in this standard apply to
 all instrument transformers, including capacitive
 voltage transformers and linear couplers,
 irrespective of primary voltage or whether the
 primary windings are connected to, or are in,
 power circuits or are connected in the secondary
 circuits of other transformers as auxiliary cts or
 vts.
Does not cover
  This guide does not discuss the grounding of some
  applications. For example, grounding of gas insulated
  substations and metal clad switchgear is not discussed in
  this guide; the reader will find these topics addressed in
  reference [9] listed in clause 2. The grounding of circuits
  of core-balance CTs is also not discussed in this guide.
  The reader can find this information also in reference [9]
  listed in clause 2. Another issue that is not discussed in
  this guide is the practice of using separate safety and
  control grounds. For discussion on this topic, the reader
  is directed to reference [12] listed in clause 2.
References
  [1] NFPA 70-2002, National Electricity Code® (NESC®)
  [2] ANSI C2-2002, National Electrical Safety Code®
  (NESC®)
  [3] C37.103™-2004, IEEE Guide for Differential and
  Polarizing Relay Circuit Testing
  [4] C57.13.1™-1981 (Reaffirmed 1999), IEEE Guide for
  Field Testing of Relaying Current Transformers
  [5] C37.92™-2004, IEEE Trial Use Standard for Low
  Energy Analog Signal Inputs to Protective Relaying
References
  [6] C62.92™-2000, IEEE Guide for the Application of
  Neutral Grounding in Electrical Utility Systems
  [7] Std. 80™-2000, IEEE Guide for Safety in AC
  Substation Grounding
  [8] Std. 142™-1991, IEEE Recommended Practice for
  Grounding of Industrial and Commercial Power Systems
  [9] Std. 242™*2001, IEEE Recommended Practice for
  Protection and Coordination of Industrial and Commercial
  Power Systems
  [10] Std. 518™-1982 (R1996), IEEE Guide for the
  Installation of Electrical Equipment to Minimize Electrical
  Noise Inputs to Controllers from External Sources
References
  [11] Std. 525™-1992, IEEE Guide for the Design and
  Installation of Cable Systems in Substations
  [12] Std. 665-1995, IEEE Guide for Generating Station
  Grounding
  [13] Std. 1050-1996, IEEE Guide for Instrumentation and
  Control Equipment Grounding in Generating Stations
  [14] Std. 1100™-1999, IEEE Recommended Practice for
  Powering and Grounding Electronic Equipment
  [15] Std. 1143™-1994 (Reaffirmed 1999), IEEE Guide on
  Shielding Practice for Low Voltage Cables
Need for Grounding Secondary Circuits
  To protect equipment connected to the circuits
  To Protect personnel who might come into
  contact with the equipment
  How the problem manifests
    When secondary circuit is not grounded
    When a case is not grounded
      Voltage due to charge accumulation on an
       ungrounded secondary circuit or case
Warning
 Grounding of secondary circuits is an issue of
 safety of personnel and equipment connected to
 the secondary circuits. The reader is urged to
 consider it seriously and follow the stipulations of
 relevant standards and ensure that the
 stipulations of the National Electrical Code [1]
 and the National Electric Safety Code [2] are
 always adhered to.
Warning
 Article 90.2 (A) of National Electrical Code [1]
 lists the installations that are covered by the
 Code [1] and Article 90.2 (B) lists the installations
 that are not covered by the Code. For immediate
 reference of the readers, Article 90.2 of National
 Electrical Code [1] is reproduced in Annex C.
Grounding of Instrument Transformer
Secondary Circuits
  Definition of a secondary circuit for the purposes
  of the guide
  Issues
    Grounding at a single location
    Minimum size of the grounding conductor
Issues
  Grounding at a single location
   Voltage at different locations of the physical
    ground and circuits connected to ground is
    different when fault currents flow
   Convenience of testing a secondary circuit
   Problem with forming a common neutral of
    more than one instrument transformers and
    then grounding the neutral bus
     Isolation of all secondary circuits from
       ground
Issues
  Recommended point of grounding
   switchboard or relay panel
  Grounding unused secondary windings
  Grounding examples
Grounding 3  4 Wire VT Circuits
Grounding 3  3 Wire VT Circuits
                                        PA
          OPEN                          PB
          DELTA
                                        PC
                                                 CONNECTIONS TO
                                                 GROUND BUS AT
                                                 SWITCHBOARD
                                        PA       (#12 AWG CU
                                                 MINIMUM)
                                        PB
        WYE                             PC
                  NEUTRAL NOT BROUGHT
                                              GROUND ISOLATING
                  OUT
                                             CONNECTION
Grounding unused CTs
ISSUES
 Minimum size of grounding conductor
  12 AWG required by NESC©
TYPICAL APPLICATIONS
 VT circuits
 Voltage provided from distribution transformers
Using Voltage from a Distribution Transformer
Generator Neutral Grounding Transformer
                                          PG
TO GEN
NEUTRAL
                                               TO RELAYS,
                   R                           OSCILLOGRAPH,
                                               ETC.
                                          PN
            GROUND ISOLATING CONNECTION
                                                  SWITCHBOARD
            STATION GROUND                        GROUND
            MAT
Generator Neutral Grounding Transformer
                                                 PG
TO GEN
NEUTRAL
                                  OPTIONAL
                           R      CONNECTION                 TO RELAYS,
                                                             OSCILLOGRAPH,
                                                             ETC.
                                                 PN
                               CENTER TAP GROUND SOMETIMES
          STATION GROUND       USED SO THAT ACCIDENTAL GROUND
          MAT                  ON PG WILL NOT COMPLETELY DISABLE
                               GENERATOR GROUND PROTECTION
Generator Neutral Grounding Transformer
Generator Grounding Transformer
                                  TO RELAYS,
                      R           OSCILLOGRAPH,
                                  ETC.
      GROUNDING
      TRANSFORMER
Basic Synchroscope Circuit
           PB   25         SCOPE         25            PB
CKT. 2               RUN           INC                              CKT. 1
           PN                                          PN
                                              GROUNDING ISOLATION
                                              CONNECTION
Synchroscope with Multiple Incoming Circuits
Synchroscope with Multiple Incoming and Running
Circuits
                   PB   25-2                       25-2   PB
                   PB   25-1         SCOPE         25-1   PB
 CKT. 4   CKT. 3               RUN           INC                     CKT. 1     CKT. 2
                   PN   25-1                       25-1   PN
                   PN   25-2                       25-2   PN
                        GROUNDS NOT NECESSARILY                GROUNDING ISOLATION
                        ELECTRICALLY CLOSE                     CONNECTION
Synchroscope with Multiple Incoming and Running
Circuits using Isolating Transformers
                           PB       25-2                                     25-2
                                                                                          PB
                     PB                    25-1         SCOPE         25-1
                                                                                          PB
CKT. 4   CKT. 3                                   RUN           INC                                   CKT. 1   CKT. 2
                     PN                                                                   PN
                    PN                                                                    PN
                                                                                GROUNDING ISOLATION
                                                                                CONNECTION
                  1 - 1 ISOLATING
                  TRANSFORMERS
Synchroscope with Synchronizing Lights
                          SYNCHRONIZING LIGHTS
                     25                      25         PB
            PB
 CKT. 2                    RUN       INC                     CKT. 1
                     25                                 PN
            PN
                                SCOPE OR
                                SYNC-CHECK
                                RELAY
                  GROUNDS SHOULD BE
                  ELECTRICALLY
                  AS GROUNDING
                     CLOSE AS PRACTICAL
                                 ISOLATION
                      CONNECTION
                 THIS CONTACT PERMITS THE TWO VOLTAGE
                 CIRCUITS TO BE SEPARATELY GROUNDED
Grounding Distribution Station with one  used for
Instrumentation
                                                             SWITCHBOARD TERMINALS
                                                            PN
                                                                        GROUND ISOLATION
                                                                        CONNECTION
                                                            G(N)
                       NOTE: BECAUSE OF THE TWO GROUNDS
                       ON G(N), IT SHOULD BE SUFFICIENTLY
                       HEAVY SO THAT STATION GROUND
                       FAULTS WILL NOT CAUSE DAMAGE TO
                       G(N)
Grounding 1  CT Circuit
                           CP
                                BURDEN
                           CN
Grounding 1  CT Circuit
                               CP
                                    BURDEN
                               CN
            GROUND ISOLATION
            CONNECTION
Grounding 3  CT Circuit
Grounding 3  CT Circuit
Grounding V Connected CT Circuit
Delta-Delta Connected CTs in a Differential
Protection Relay
Delta-Wye Connected CTs in a Differential
Protection Relay
 A   B   C                                   C       B     A
                    SWITCHBOARD
                    TERMINALS
                             DIFF.
                             RELAYS
             CBC                      CBC
             CBB                      CBB
             CBA                      CBA
                                        GROUND ISOLATION
                                        CONNECTION
Percentage Bus Differential Scheme
                                       SWITCHBOARD
                                       TERMINALS     RESTRAIN
                                                     T
                                CD3A
                                                       OPERATE
                                CD3B
                  TO CTS
                  ON CKT. 3     CD3C                             PHASE A
                                CD3N
                                CD2A
                                CD2B
                  TO CTS                                         PHASE B
                  ON CKT. 2     CD2C
                                CD2N
                         A      CD1A
                         B      CD1B                             PHASE C
         CKT. 1
                         C      CD1C
                                CD1N
                   GROUND ISOLATION
                   CONNECTION
Ring Bus or Breaker and a Half Scheme
                         TO METERS,
                         RELAYS, ETC.
      TERMINALS                                  TERMINALS
      AT CT LOCATION                             AT CT LOCATION
        GROUND
        ISOLATING
        CONNECTION
                        SWITCHBOARD TERMINALS
                        (MAY BE SLIDING LINK
        CONTROL HOUSE
                        TYPE
        GROUND BUS
                        TO FACILITATE TESTING)
51-
A
51-B
51-C
       Multiple use of CTs
51-C
51-B
51-
A
Grounding of Cases
  Grounding metallic conductive cases
  Insulated cases with conductive internal parts
  Ungrounded metallic cases or internal parts
    Protected by suitable barriers or elevated to
     prevent contact if operating voltage exceeds
     1,000 V
Exceptions to Grounding
  If the primary windings of instrument transformer
  circuits are connected to circuits of less than
  1000 V with no live parts or wiring exposed or
  accessible to other than qualified persons, the
  circuits may not be grounded.
Exceptions to Grounding
  For instrument transformer cases, the cases or
  frames of CTs may not be grounded if the
  primary windings are not over 150 V to ground
  and are used exclusively to supply current to
  meters.
Exceptions to Grounding
  Cases of instruments, meters, and relays
  operating at less than 1000 V on switchboards
  having exposed live parts on the front of panels
  are not usually grounded. Mats of insulating
  rubber or other suitable floor insulation is
  provided where the voltage to ground exceeds
  150 V.
Exceptions to Grounding
  Instruments, meters, and relays, whose current-
  carrying parts operate at voltages to ground of
  1000 V and over, are isolated by elevating them
  or protecting them by suitable barriers, grounded
  metal or insulating covers, or guards. In such
  situations, the cases are not usually grounded.
Grounding of Low-Energy Transducers
Grounding of Low-Energy Transducers
Grounding of Low-Energy Transducers
Annex A
 Grounding of shielded cables
  To consider current carrying capacity of the
   shield
  Cables with spiral design shields are grounded
   at both ends
  Cables with drain wires are grounded at one
   end
Annex A
 CTs installed over shielded cables
Annex B
 IEEE Standards reviewed by the WG
Annex C
 Clause 90.2, Scope of National Electricity Code
  Type of installations covered by the Code
  Type of installations not covered bye the Code
  Special permission
ANNEX D
 Survey of Grounding Practices
  Approximately one-third of the respondents do
   not ground voltage transformers “at the first
   point of use” as described in the Guide. The
   Working Group is of the opinion that grounding
   “at the first point of use” is better than
   grounding at other locations.
  Almost all respondents indicated that current
   transformers are grounded “at the first point of
   use” as described in the Guide.