LAN CONTROLLER instruction from 2.
30
RESTARTER, MONITOR, WATCHDOG, CONTROLLER
FEATURES:
WWW or SNMP v2 management.
firmware upgrade via TFTP
read data in real time without refresh page
read all sensors by xml “st0.xml”
switching output by the command from your browser (IP/outs.cgi?outx=x)
possibility switch on/off to 5 relay direct from page WWW
events panel to self-programming by user
Scheduler (switch on/off output for definite time in week days)
Watchdog IP to five IP device
monitoring od additional devices eg. sensors
measurement: environment temperature, suplly voltage, temperature and curent from
conected sensors
power measurement for DC voltage
posisibility connection of the additional board with RJ45 ports (4 LAN Input, 4 ye LAN +
PoE) or additional board with 4 relays
Set time manualy or by server NTP
Posisibility sensors calibration
steering frequency and duty PWM
e-mail notification about programmed events
SNMP TRAP notification about programmed events
Automatic send SNMP TRAP with state or value inputs
implement protocols: HTTP, SNMP, SMTP, SNTP, ICMP, DNS, DHCP.
service temperature sensors: NTC10K B=3380, KTY-84, PT1000, DS18B20
Default user and password is „admin”, IP adress is 192.168.1.100
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 1 z 15
TECHNICAL SPECIFICATIONS
supply voltage: 8-56V (from 6V- if don’t use mesurement current and PT1000)
power consumption : about 1W
PoE supply: YES, passive
Protection from wrong supply polarization: YES
interface: ethernet 10Mbit/s
relay: 255VAC 10A
work temperature: -20 do +85 st. C
weight 45g (without casing)
casing type Z-67 (not included)
dimensions 57x67mm
INPUT/OUTPUT:
1 RELAY to switch on/off/ another devices, available contact: NC and NO
4 OUTPUT to switch relays, ports PoE or another devices;
1 STEERABLE OUTPUT PWM from 2,6 KHz to 4Mhz;
4 LOGICAL INPUT (2 on terminal block- max 12V, 2 on 5 pin connector-max 5V): to
monitoring another devices, eg. bufor supply. collaboration with outputs: OC,NO, NC
5 ANALOG INPUT:
INP1: temperature measurement witch thermistor NTC 10K B=3380( from -40 to +120
°C) or thermistor KTY-84-130 (from -40 to +300°C), accuracy 1 °C (dependent on
NTC)
INP2: thermistor NTC 10K or voltage mesurement to 3,6V, with use additional divider
increase range..
INP3: voltage measurement to 35V, accuracy +- 0,1V;
INP4: temperature measurement by PT1000 (from -20 to +850 °C) accuracy +- 2°C;
INP5: measurment DC current to 3A, accuracy +- 10mA;
MAGISTRALA 1-WIRE (connector RJ11) – to DS18B20 sensor, max 4 pcs in soft
version 3.xx(without Watchdog) max 6 pcs.
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 2 z 15
PINS and COMPONENTS DESCRIPTION
IDC10
INP3D Temperature board sensor
GND5 INP4D
Power
LED 1 Ethernet 10Mbit.
INP1D
GND1
RESET button,
INP2D
change relay state
and do sets reset
GND2
+3,6V
INP6 - RJ11
INP1
1-WIRE bus
INP2
INP3 Reley bond
GND3 (output OUT0)
INP4
INP5
GND4
LED 2
PIN/Component Description
Power Power suplly 8V-56VDC or via PoE
RELAY bond To connect external device, detail description below
LED1 Shine LED means Power on board
LED2 Shine LED means relay active
IDC10 To connect additional board , detail description below
INP1D Logical inpuut 1
GND1 gnd for INP1D and INP2D or general gnd
INP2D Logical inpuut 2
GND2 general gnd
+3,6V Supply for sensors NTC-10K and KTY-84 connected to INP1 or INP2
INP1 input for sensor NTC-10K or voltage measurement max (without divider ) 3,6V
INP2 input for sensor NTC-10K Or KTY-84-130
INP3 input for voltgae measuerment max 35V
GND3 general gnd
INP4 input for sensor PT1000 or connected the same sensor in solar controller
INP5 Input for current measurement
GND4 Gnd for current measurement Or general if don’t measurement current
INP6 Input for DS18B20 sensor ( 1-wire bus on RJ11 connector)
INP3D Logical inpuut 3
INP4D Logical inpuut 4
GND5 gnd for INP4D and INP4D or general gnd
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 3 z 15
Relay Bond:
NO – contact normaly open
CON – common contact
NZ – contact normaly closed
NO CON NZ
ATTENTION: In spite of that relay can switch AC voltage 255 VAC 10A, board fail to
comply with safety requirements (lack housing, earthing). Therefore that receiver
connect with the assistance safety external relays eg. on DIN bus, controlled by relay
on board.
IDC10 and RJ11
1 2
1 – not use 2 –not use
3 – +3,6V 4 –OUT4
5 – GND 6 – OUT3
7 – PWM output 8 – OUT2
9 – VIN, vcc suplly 10 – OUT1
10
RESET BUTTON
Push about 0,5 second cause change relay state on opposite, push and keep
longer about 5 second (if we not logged by WWW on modul) cause modul reset, next if
you still keep button about 10 second cause set all settings to default. Set all settings to
default confirmation is fast switch relay on/off (klik-klik), don’t wrong this with change
relay state about 0,5s and switch relay off after restart.
User and password: admin
IP: 192.168.1.100
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 4 z 15
Sensors connect
1. Current measurement.
This reciver current
we measured
VCC
Power
suplly GND
2. Temperature measurement and logical input.
INP1_D
GND
INP2_D
+3,6V
NTC-10K INP1
INP2
NTC-10K
lub KTY84
GND
PT-1000 INP4
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 5 z 15
3. Voltage measurement.
INP1 is use to temperature
measure or voltage, in
control panel you must choice
what you want measure
GND
Measure
voltage max
3,6 V DC
or more if you INP1
add divider
resistor
INP3
Measure
voltage max GND
35 V DC
Additional resistor to increase measure range INP1
Measure R
voltage INP1
R = 10K increase range 2 (multiplier 2) that is 3,6V x 2 = 7,2V
R= 20 K increase range 3 (multiplier 3)
R= 30 K increase range 4 (multiplier 4) etc.
Add resistor must be connected with set proper multiplier in field VCC on control panel
page.
multiplier
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 6 z 15
Management by WWW.
Change outputs state display Any text description, max 8 chars
1.Control Panel
Choce type
Set state All Run PWM Value of Run Power connected sensor
Klik cause generator
change relay output calibration measure from
state on opposite simultaneously INP3 (voltage)
(OUT0 relay on according to and INP5
board) combo box (current)
Reset time – for 0 normal outputs work (ON/OFF) , for time > 0 output after push button change state and return to
state before after the specified time in seconds (max 65534).
Automatic switching outputs at a specific time (2 windows :1-time switch, 2-break time)
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 7 z 15
Delay of set outputs after occur events, in seconds max
2.Events Config (events panel) 65535
ON/OFF When signal If check, means Email text taht
input When signal cross down this Save setings that is ON will be send if
cross up this value output will (ON/OFF input events
value output will be set ON Or you don’t must occurance, max
be set ON Or generator PWM save) amount char is
generator PWM start or send 79. Chars „=”
Value of
start or send e_mail or SNMP and „& are not
hysteresis
e_mail or SNMP Trap allowed
Trap Trap
For logical input INP1D and INP2D, e-mail and SNMP Trap notification are send when
input level change from 1 to 0 or 0 to 1, additional to email text (at end) will be add
value 1 or 0 mark actual input state.
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 8 z 15
Config events description:
Example:
3.Watchdog
When check,
watchdog will be
automaticly disabled
and enabled when
relay on/off by
events set in”Events
config”
Amount PING failures, after this
When events occur, next ping to this same IPX will be send after this time one of three events will be
(max 65535second) happen:
set (ON) output,
set (OFF) output
reset (ON/OFF) output on definite
Time to respond is 4 second, after this time one PING failures time (max 65535s).
is counting. In time waiting to respond, another IPX aren’t
send ping, this may causa stretch time statment that another
IPX adress is inaccessible.
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 9 z 15
4.Scheduler
Run auto switch out
(switch times set in
control panel) at
specific time provided
than INP1D is in a
state that we set
( HIGH (1) or
LOW(0))
Week Day
Mo-Monday, Tu- Tuesday, We- Wednesday, Th- Thursday, Fi- Friday, Sa- Saturday,
Su-Sunday, ## - all week day
Letter size is important
Format: number output(from 0 to 4),day1,day2,day3,day4,day5,day6, xx:xx:xx(time)
Example:
0,Mo,12:23:00 sets out0 every Monday at 12:23:00
1,Sa;Fi,Mo,23:22:03 sets out1 every Saturday,Friday and Monday at 23:22:03
1,Sa;Fi,Mo,Tu,Su,Th,23:22:03 sets out1 every Saturday, Friday, Monday, Tuesday,
Sunday and Thursday at 23:22:03
0,##,12:01:30 - sets out0 every week day at 12:01:30
Reset – time in second (max 65535).
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 10 z 15
Network Configuration.
Working as a server (receiving packets and enable / disable the corresponding output)
or client (send packets to the server after changing the state of the INP1D or INP2D). LK
working as a server can be driven from any number of clients, provided it is set to the
same password. Change INP2D INP1D or switches to a low output state selected "ON",
the return to the high state output switches to "OFF".
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 11 z 15
Time Interwal - minuts.
TRAP Enable – enabled send
TRAP by SNMP.
Enable Automatic Send TRAP –
enable automatic send TRAP by
SNMP (above TRAP Enable must
be enable)
Time Interval (max value 10555)
– period to send TRAP from given
INPUT, accuracy 10 s
Relay state after start
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 12 z 15
Reading XML data
Enter the IP address and the page name eg 192.168.1.100/st0.xml
The values of the sensors should be divided by 10
Control Panel:
– dynamic data – st0.xml
– static data – st2.xml
Events Config : s.xml
Watchdog: w.xml
Scheduler: sch.xml
Network Config: board.xml
Up time: s_time.xml with the Timezone
Switching outputs http request
You can switch any outputs without clicking on the buttons in the control panel, making use of
the following commands:
IP/outs.cgi?out=xxxxx – Switching outputs to the opposite of the current
IP/outs.cgi?outx=x – ON or OFF the output
when password authentication is enabled, the commands have this form:
user:password@IP/outs.cgi?out=xxxxx
user:password@IP/outs.cgi?outx=x
Example:
192.168.1.100/outs.cgi?out=0 – changes the out0 state to the opposite
192.168.1.100/outs.cgi?out=2 – changes the out2 state to the opposite
192.168.1.100/outs.cgi?out=02 – changes the out0 and out2 state to the opposite
192.168.1.100/outs.cgi?out=01234 – changes the out0,1,2,3,4 state to the opposite
192.168.1.100/outs.cgi?out0=0 – out0 ON
192.168.1.100/outs.cgi?out0=1 – out0 OFF
192.168.1.100/outs.cgi?out1=0 – out1 ON
192.168.1.100/outs.cgi?out1=1 – out1 OFF
192.168.1.100/outs.cgi?out4=0 – out4 ON
192.168.1.100/outs.cgi?out4=1 – out4 OFF
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 13 z 15
Firmware Upgrade.
You my upgrade firmware on two way:
1. By dedicate software „LAN Controler Tools”(find controler or put IP and click
„Upgrade Firmware”).
2. By any TFTP client, description below.
Send firmware file by TFTP, you have 5 second (Green LED on RJ45 socket blink) to
start send firmware when modul run after reset (you my casus reset by click button
„Save config and Reboot” in Network configuration or „Reset” button on board or
dedicate software „LAN Controler Tools”). If start transmision not happen that device
start work normal. If tftp transmision will start than wait about 90 second to finish upload
firmware. After upload device will be reset and start normal.
If you want to upload upgrade file chose „Save config and Reboot” in Network
configuration or power OFF and power ON device .
The file must be send in binary mode eg. In Windows XP tftp client
tftp –i 192.168.1.100 put „file_upgrade.bin”.
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 14 z 15
OID dla SNMP
Soft_version .1.3.6.1.2.1.1.1.0 READWRITE ASCII_STRING
SYS_OID .1.3.6.1.2.1.1.2.0 READONLY OID
SYS_UP_TIME .1.3.6.1.2.1.1.3.0 READONLY TIME_TICKS.
LAN_NAME .1.3.6.1.2.1.1.5.0 READWRITE ASCII_STRING.
TRAP_RECEIVER_ID .1.3.6.1.4.1.17095.2.1.1.1.1 READWRITE BYTE.
TRAP_RECEIVER_ENABLED .1.3.6.1.4.1.17095.2.1.1.2.1 READWRITE BYTE.
TRAP_RECEIVER_IP .1.3.6.1.4.1.17095.2.1.1.3.1 READWRITE IP_ADDRESS.
TRAP_COMMUNITY .1.3.6.1.4.1.17095.2.1.1.4.1 READWRITE ASCII_STRING.
OUT0 (5) .1.3.6.1.4.1.17095.3.1.0 READWRITE BYTE.
OUT1 (6) .1.3.6.1.4.1.17095.3.2.0 READWRITE BYTE.
OUT2 (7) .1.3.6.1.4.1.17095.3.3.0 READWRITE BYTE.
OUT3 (8) .1.3.6.1.4.1.17095.3.4.0 READWRITE BYTE.
OUT4 (9) .1.3.6.1.4.1.17095.3.5.0 READWRITE BYTE.
TEMP (10) .1.3.6.1.4.1.17095.3.6.0 READONLY ASCII_STRING.
VCC (11) .1.3.6.1.4.1.17095.3.7.0 READONLY ASCII_STRING.
INP1 (12) .1.3.6.1.4.1.17095.3.8.0 READONLY ASCII_STRING.
INP2 (13) .1.3.6.1.4.1.17095.3.9.0 READONLY ASCII_STRING.
INP3 (14) .1.3.6.1.4.1.17095.3.10.0 READONLY ASCII_STRING.
INP4 (15) .1.3.6.1.4.1.17095.3.11.0 READONLY ASCII_STRING.
INP5 (16) .1.3.6.1.4.1.17095.3.12.0 READONLY ASCII_STRING.
INP6 (17) .1.3.6.1.4.1.17095.3.13.0 READONLY ASCII_STRING.
INP7 (18) .1.3.6.1.4.1.17095.3.14.0 READONLY ASCII_STRING.
INP8 (19) .1.3.6.1.4.1.17095.3.15.0 READONLY ASCII_STRING.
INP9 (20) .1.3.6.1.4.1.17095.3.16.0 READONLY ASCII_STRING.
I3XI5 (21) .1.3.6.1.4.1.17095.3.17.0 READONLY ASCII_STRING.
PXT (22) .1.3.6.1.4.1.17095.3.18.0 READONLY ASCII_STRING.
INP1D (23) .1.3.6.1.4.1.17095.3.19.0 READONLY BYTE.
INP2D (24) .1.3.6.1.4.1.17095.3.20.0 READONLY BYTE.
INP3D (25) .1.3.6.1.4.1.17095.3.21.0 READONLY BYTE.
INP4D (26) .1.3.6.1.4.1.17095.3.22.0 READONLY BYTE.
LAN CONTROLLER ver.2.9 www.tinycontrol.ats.pl side 15 z 15