4-pole�contactor,80A/AC-1,AC�operated
Part�no. DILMP80(230V50HZ,240V60HZ)
Article�no. 109884
Program
Product range Contactors
Application Contactors for 4 pole electric consumers
Subrange Contactors up to 200 A, 4 pole
Connection technique Screw terminals
Pole 4 pole
Rated operational current
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
at 40 °C Ith =Ie A 80
at 50 °C Ith =Ie A 76
at 60 °C Ith =Ie A 69
Contact sequence
For use with DILM150-XHI(A)(V)…
or
DILM1000-XHI11-SA
or
DILM1000-XHI(V)11-SI
Voltage AC/DC AC operation
InstructionsContacts to EN 50 012.
Approbationen
Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29096
UL CCN NLDX
CSA File No. 012528
CSA Class No. 2411-03, 3211-04
NA Certification UL listed, CSA certified
Specially designed for NA No
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations x 10
6
10
DC operated Operations x 10
6
10
Operating frequency, mechanical
AC operated Operations/ 5000
h
DC operated Operations/ 5000
h
Climatic proofing Damp heat, constant to IEC 60068-2-3
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Open °C - 25 - 60
Enclosed °C - 25 - 40
Storage °C - 40 - 80
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 1/9
HPL-ED2009 V0.9 %s
Mounting position, AC- and DC operated
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Protection type IP00
with accessories IP20
Protection against direct contact when actuated from front (EN 90274) Finger- and back-of-hand proof
Terminal capacity main cable
Solid mm
2 1 x (2.5 - 16)
2 x (2.5 - 16)
Flexible with ferrule mm
2 1 x (2.5 - 35)
2 x (2.5 - 25)
Stranded mm
2 1 x (16 - 50)
2 x (16 - 35)
Solid or stranded AWG 12 - 2
Flat conductor Number mm 2 x (6 x 9 x 0.8)
of
segments
x width
x
thickness
Terminal capacity control circuit cables
Solid mm
2 1 x (0.75 - 4)
2 x (0.75 - 4)
Flexible with ferrule mm
2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 18 - 14
Main cable connection screw/bolt M6
Tightening torque Nm 3.3
Control circuit cable connection screw/bolt M3.5
Tightening torque Nm 1.2
Tool
Main cable
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1x6
Control circuit cables
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1x6
Main�conducting�paths
Rated impulse withstand voltage Uimp V 8000
AC
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V 690
AC
Rated operational voltage Ue V 690
AC
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts V 440
AC
between the contacts V 440
AC
Making capacity (p.f. to IEC/EN 60947)
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 2/9
HPL-ED2009 V0.9 %s
Up to A 700
690 V
Breaking capacity
220/230 V A 500
380/400 V A 500
500 V A 500
660/690 V A 296
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V gG/gL A 80
500 V
690 V gG/gL A 63
690 V
Type “1” coordination
400 V gG/gL A 160
500 V
690 V gG/gL A 80
690 V
AC
AC-1 duty
Rated operational current
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C Ith =Ie A 80
at 50 °C Ith =Ie A 76
at 60 °C Ith =Ie A 69
enclosed Ith A 64
Conventional free air thermal current, 1 pole
open Ith A 207
enclosed Ith A 186
Motor rating P kWh
Motor rating AC-1 230 V kW 29
Motor rating AC-1 240 V kW 32
Motor rating AC-1 380/400 V kW 50
Motor rating AC-1 415 V kW 55
Motor rating AC-1 440 V kW 58
Motor rating AC-1 500 V kW 66
Motor rating AC-1 690 V kW 87
AC-3 duty
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole Ie
220/230 V Ie A 50
240 V Ie A 50
380/400 V Ie A 50
415 V Ie A 50
440V Ie A 50
500 V Ie A 50
660/690 V Ie A 32
Motor rating P kWh
220/230 V P kW 15.5
240V P kW 17
380/400 V P kW 22
415 V P kW 30
440 V P kW 32
500 V P kW 36
660/690 V P kW 30
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 3/9
HPL-ED2009 V0.9 %s
DC
Rated operational current, open
DC-1 operation
60 V Ie A 80
110 V Ie A 80
220 V Ie A 80
440 V Ie A 8
DC-3 operation
60 V Ie A 80
110 V Ie A 80
220 V Ie A 80
440 V Ie A 5
DC-5 operation
60 V Ie A 80
110 V Ie A 80
220 V Ie A 70
440 V Ie A 5
Current�heat�loss�(3�pole)
Current heat loss at Ith W 23
Impedance per pole mΩ 0.7
Magnet�systems
Voltage tolerance x Uc
AC operated 50 Hz Pick-up x Uc 0.8 - 1.1
AC operated 50/60 Hz x Uc 0.85 - 1.1
Drop-out voltage AC operated Drop- x Uc 0.4 - 0.6
out
DC operated Pick-up x Uc 0.7 - 1.2
DC operated Drop- x Uc 0.2 - 0.6
out
Power consumption of the coil in a cold state and 1.0 x Uc
AC operated 50/60 Hz Pick-up VA 150
AC operated 50/60 Hz Pick-up W 95
AC operated 50/60 Hz Sealing VA 16
AC operated 50/60 Hz Sealing W 4
DC operated Pick-up W 24
DC operated Sealing W 0,5
Duty factor % 100
DF
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
Closing delay ms 12 - 18
Opening delay ms 8 - 13
DC operated ms
Closing delay ms 54
Opening delay ms 24
Arcing time ms 10
Permissible residual current with actuation of A1 - A2 by the mA
electronics (with 0 signal). 1
Notes
At least double-pulse bridge rectifier
Technical�data�according�to�ETIM�4.0
Number of main contacts as N/Os 4
Rated operation current Ie at AC-1, 400 V 80
Connection type main circuit Screw connection
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 4/9
HPL-ED2009 V0.9 %s
Rated control voltage Us at AC 60HZ V 240
Number of auxiliary contacts as N/Os 0
Rated control voltage Us at AC 50HZ V 230
Number of auxiliary contacts as N/Cs 0
Suitable for rail-mounting No
Rated control voltage Us at DC V 0
Voltage type for actuation AC
Rated operation current Ie at AC-3, 400 V A 50
Number of N/Cs as main contact 0
Motor rating at AC-3, 400 V kWh 22
Characteristics
1: Auxiliary contact module
2: Suppressor
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 5/9
HPL-ED2009 V0.9 %s
Operating characteristics
Non inductive and slightly inductive loads
Electrical characteristics
Switch on: 1 × rated operational current
Switch off: 1 × rated operational current
Utilization category
100 % AC-1
Typical examples of application
Electric heat
CAD-Data
Product standards CAD data: http://eaton-moeller.partcommunity.com/PARTcommunity/Portal/eaton-moeller
Dimensions
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 6/9
HPL-ED2009 V0.9 %s
Contactors
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 7/9
HPL-ED2009 V0.9 %s
distance at side to earthed parts: 6 mm
DILMP63
DILMP80
Additional�product�information�(links)
IL03407049Z (AWA2100-2356) 4-pole Contactor ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407049Z2010_10.pdf
Installation Instructions http://www.moeller.net/en/support/instructions_awa.jsp
Documentation http://www.moeller.net/en/support/index.jsp
10/04/2011 Moeller Electric, www.moeller.net; E-Mail: catalog@moeller.net 8/9
HPL-ED2009 V0.9 %s
Motor starters and "Special Purpose Ratings" for the North American http://www.moeller.net/binary/ver_techpapers/ver953en.pdf
market
Busbar Component Adapters for modern Industrial control panels http://www.moeller.net/binary/ver_techpapers/ver960en.pdf
The Interaction of Contactors with PLCs http://www.moeller.net/binary/ver_techpapers/ver957en.pdf
Standard Compliant and Functionally Safe Engineering Design with http://www.moeller.net/binary/ver_techpapers/ver956en.pdf
Mechanical Auxiliary Contacts
Switchgear for Luminaires http://www.moeller.net/binary/ver_techpapers/ver955en.pdf
Effect of the Cabel Capacitance of Long Control Cables on the Actuation http://www.moeller.net/binary/ver_techpapers/ver949en.pdf
of Contactors
X-Start - Modern Switching Installations Efficiently Fitted and Wired http://www.moeller.net/binary/ver_techpapers/ver938en.pdf
Securely
Mirror Contacts for Highly-Reliable Information Relating to Safety- http://www.moeller.net/binary/ver_techpapers/ver944en.pdf
Related Control Functions
X-Start - New Generation:100 years of Moeler contactors - Continous http://www.moeller.net/binary/ver_techpapers/ver937en.pdf
Progress-
Switchgear of Power Factor Correction Systems http://www.moeller.net/binary/ver_techpapers/ver934en.pdf
10/04/2011 Eaton Industries GmbH 9/9