0% found this document useful (0 votes)
481 views4 pages

Model GT-CT8900: G T G T

The GT-CT8900 is an intelligent sensor for detecting combustible gas like methane. It has a catalytic bead sensor inside an explosion-proof enclosure with status displays. It provides gas concentration readings, calibration and sensor life information. Outputs include 4-20mA current, warning/alarm/fault relays, and RS485/HART interfaces. It is designed for remote monitoring in hazardous areas and has features like automatic calibration, event logging, and communications capabilities.

Uploaded by

Gilang ramadhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
481 views4 pages

Model GT-CT8900: G T G T

The GT-CT8900 is an intelligent sensor for detecting combustible gas like methane. It has a catalytic bead sensor inside an explosion-proof enclosure with status displays. It provides gas concentration readings, calibration and sensor life information. Outputs include 4-20mA current, warning/alarm/fault relays, and RS485/HART interfaces. It is designed for remote monitoring in hazardous areas and has features like automatic calibration, event logging, and communications capabilities.

Uploaded by

Gilang ramadhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

GASENSOR TECHNOLOGY MODEL GT-CT8900

Description Intelligent Sensor


For Combustible Gas Detection

Model GT-CT8900, Fixed type Catalytic combustible gas


sensor, engineered specifically for detecting combustible
gas (Methane) and vapor. The sensor is housed together
in an explosion-proof enclosure complete with status
display, which consists of three high-brightness nixie tubes
and four status indicators for gas concentration readings
and status conditions. In addition, a sensor life indication
function is provided for ease of maintenance and improves
instrument reliability. GT-CT8900 provides various output
interfaces which includes 4-20mA current output, three sets
of Normally Open Contacts for Warning/Alarm/Fault status,
two sets of communication interfaces for RS485 and HART
interfaces.

Features Benefits

• Compatible with Automatic Remote Gas Calibrator • Fully automatic calibration


(ARGC) • Fault, gas check, calibration, and alarm event logging
• Event logging • Provides complete status and control capability in the control
• HART and Modbus communications room

• 4-20 mA analog current output • Industry standard outputs for remote alarm and fault indication

• Warning, Alarm & Fault Relays • Provides local alarm capability

• Calibration, Calibration Check, and Setup Modes • Simplifies operation and maintenance

• Remaining sensor life indication • Reduces downtime by providing an estimate of sensor life

System Specifications

Sensor Type : Continuous diffusion, Zero Drift : Less than 5% of full scale per year
low temperature catalytic bead Modes : Calibration, gas check, setup
Sensor Life : 3 to 5 years typical Electrical Classification :
Measuring Ranges : 0-100% LEL ATEX II 2G Ex db IIC T6 Gb IP66
Accuracy : ±3% LEL 0- 50% LEL; ±5% LEL; 50-100% LEL (Tamb = -40°C to +70°C)
Response Time : T50 <10 s T90 <30 s with 100% LEL SIL2 Certified
Warranty : Two years
methane applied;(T90 ≤18s Typical Value)
MODEL GT-CT8900
Electrical Specifications Environmental Specifications

Input Power : 24 VDC nominal, 20 to 36 VDC 5W max Operating Temperature


Analog Output : 0-20 mA (650 Ohms max. load) Range : -40°F to 167°F (-40°C to 75°C)
0 mA ① Malfunction Storage Temperature
1.5 mA ② Gas Check/Calibrate Range : -58°F to 185°F (-50°C to 85°C)
1.5 mA ② Setup mode Operating Humidity
4 mA ± .05 mA Zero reading Range : 5% to 100% RH, non-condensing
4-20 mA 0-100% LEL
20-22 mA Over-range
RS-485 Output : Dual redundant Modbus RTU, 207
123
(Optional) suitable for linking up to 128 units or 98

up to 247 units with repeaters


Baud Rate : 2400, 4800, 9600, or 19200 bps
HART: HART 7, HART Device Description Language
(Optional) available. AMSAware
Relay Ratings : 8A @ 250 VAC / 8A @ 30 VDC res. max.

193
98
(Optional) (3x) SPDT - Warning, Alarm & Fault
Status Indicators: Three-digit LED display with gas Accessories
(Order separately)
concentration,FLT,RUN,Warn and Alarm
LED's,calibration prompts, faultcodes,
and setup options
Faults Monitored : Calibration error, sensor error, low DC
supply, EEPROM, setup error, gas check
time exceeded, switch error, internal error
I/O Protection: over-voltage, Miswiring, EMI / RFI Immunity
Cable Requirements: Three-wire shielded cable. Upright column
Max. distance between GT-CT8900 and power Equipped by user

source @ 24 VDC nominal (20-Ohm loop):


14 AWG - 2303 ft (702 m)
Max. distance for analog output (650 Ohms max):
14 AWG - 9000 ft (2740 m)

Mechanical Specifications

Mounting Holes : 3.86 inches (98 mm)


(center to center)
Housing : Marine aluminum
316 Stainless steel (optional)
Weight : 1.8 kg ( Aluminum )
4.3 kg ( Stainless steel ) Figure 1: Outline and Mounting Dimensions
Cable Entries: Two entries 3/4 ins NPT, others optional

① Under HART, current values can be either 3.5 mA or 1.25 mA, depending on user selection.
② Under HART, current value can be either 3.5 mA or 1.5 mA, depending on user selection. Publication #: DS-CT8900-D0718
Specifications subject to change without notice. GT-TD-DS.01

Gasensor Technology Pte.Ltd


Add : 71 Ubi Crescent # 04-01 Excalibur Centre Singapore 408571
Tel : ( +65 ) 67446268 Fax : ( +65 ) 67446269
E-mail : sales @ gasensor.com
Web : WWW . gasensor.com
MODEL GT-CT8900
Ordering Information

GT-CT8900 Combustible Gas Detector


A B C D E
Customized CFG: GT-CT8900     
STD CFG: GT-CT8900 -1 -8 -1 -1 -1
A: Sensor Type Description
1 std* SST Sensor Body
2 AL Sensor Body
3 SST Sensor Body, HI TEMP
4 AL Sensor Body , HI TEMP

B: Output Description
1 4-20mA+Relay+ Modbus +Hart
2 4-20mA+ Relay+ Modbus
3 4-20mA+Relay+ Hart
4 4-20mA+ Relay
5 4-20mA+ Relay
6 4-20mA+ Modbus
7 4-20mA+ Hart
8 std* 4-20mA

C: Relay State CFG Description


1 std* WARN dEn nLA, ALRM dEn nLA
2 WARN dEn nLA, ALRM En nLA
3 WARN En nLA, ALRM dEn nLA
4 WARN En nLA, ALRM En nLA
5 WARN dEn nLA, ALRM dEn LA
6 WARN dEn nLA, ALRM En LA
7 WARN En nLA, ALRM dEn LA
8 WARN En nLA, ALRM En LA

Specifications subject to change without notice

Gasensor Technology Pte.Ltd


Add : 71 Ubi Crescent # 04-01 Excalibur Centre Singapore 408571
Tel : ( +65 ) 6744 6268 Fax : ( +65 ) 6744 6269
E-mail : sales @ gasensor.com / gasensor @ gasensor.com
Web : WWW . gasensor.com
MODEL GT-CT8900
Ordering Information

D: Enclosure Description
1 std* AL
2 SST

E: Approvals Description
1 std* ATEX
2 CCCF
3 ATEX+CCCF

Note:
Std* refers to the standard configuration;

Specifications subject to change without notice.

Gasensor Technology Pte.Ltd


Add : 71 Ubi Crescent # 04-01 Excalibur Centre Singapore 408571
Tel : ( +65 ) 6744 、6268 Fax : ( +65 ) 6744 、6269
E-mail : sales @ gasensor.com / gasensor @ gasensor.com
Web : WWW . gasensor.com

You might also like