Cohen-Coon Method:
The Cohen-Coon tuning rules use three process characteristics: process gain,
dead time, and time constant. These are determined by doing a step test and
analysing the results.The Cohen-Coon method work well on virtually all self-
regulating processes and were designed to give a very fast response compared to
Ziegler-Nichols method. The Cohen-Coon tuning rules work well on processes where
the dead time is less than two times the length of the time constant.
Advantages: Good process model and simple model to use.
Disadvantages: Need to use equation to calculate the parameters, required First
Order Plus Dead Time (FOPDT) model and suitable for first order process
Application: 1) Cohen-Coon tuning rules are effective on virtually all control loops
with self-regulating processes. Most control loops such as flow, temperature and
pressure contain self-regulating process.
2) Cohen-Coon method is designed for use on a non-interactive
controller algorithm.
3) The modified Cohen-Coon method provides fast response and is an
excellent alternative to Ziegler-Nichols for self-regulating processes.
Cohen-Coon method equation