TEST CERTIFICATE
Test Report of Ambient Noise
Report No: KRTE/Noida/N-226 Date of Issue: 31-08-2020
Issued to : MRS. BECTORS FOOD SPECIALITIES LTD
11-A, Udyog Vihar, Greater Noida,
Gautam Budh Nagar, UP- 201308
Sampling & Analysis Data
Sample Drawn on : 30-08-2020
Sample Drawn By : KRTE
Sample Received on : 30-08-2020
Sample Description : Ambient Noise
Sr. Noise (dB) A
Location
No Day Night
1. Rademaker IQF outside 83.4 74.3
2. Compressor area 81.2 75.5
3. DG Area 84.0 77.6
4. Sieve Area 82.4 75.4
5. WP Oven 84.7 75.6
6. Bun Packing 80.3 73.8
7. De-panner 83.4 74.5
8. Bun Sugar Grinder 84.5 76.9
9. De-panner (First Floor) 82.0 78.2
10. WP Packing Area 79.5 72.5
11. Bakery sugar grinder 88.5 82.8
Contd…….2
KR
Head Office:
2nd Floor, 9 Office Space, Omaxe Avenue
Raebareilly Road, Lucknow-226025(U.P.)
TECHNOSAFE Branch Office:
T-16,904, Nirala Estate,Techzone IV,
COMPETENT PERSONS, SURVEYORS & VALUERS Greater Noida West, G.B.Nagar (U.P.) 201308
Mobile: 8573034092, 9839135093, Email: krtelko@gmail.com, admin@krtechnosafe.in, Website: www.krtechnosafe.com
Report No:KRTE/Noida/N-226 Date of Issue: 31-08-2020
Requirement (as per CPCB Guidelines Limits in dB (A) Leg)
Category of Area / Zone Day Time Night Time
Industrial Area 75 70
Commercial Area 65 55
Residential Area 55 45
Silence Zone 50 40
Permissible exposure in cases of continuous noise as per Factories Rule
Total time of exposure (hour) (continuous Sound pressure level in or a number of
short term exposures) dBA per day, in hours
8 85
6 87
4 90
3 92
1½ 97
1 100
¾ 102
½ 105
¼ 110
1. No exposure in excess of 110 dBA is to be permitted.
2. For any period of exposure falling in between any figure and the next higher or lower figure as
indicated in column 1, the permissible sound pressure level is to be determined by extrapolation on
a proportionate basis.
Notes :
1. The result given above are related to the tested sample, as received and mention parameter.
The customer asked for the above test only.
2. This test report not be generated again, either wholly or in part, without prior written
permission.
3. This test report will not be used for any publicity / legal purpose.
Checked by Authorized Signatory