FieldLink process networking Foundation Fieldbus
Terminator
This Foundation Fieldbus terminator contains all of the components
Model number
required for terminating a Foundation Fieldbus segment. This device
AC461111A is designed to be very compact and easy to use. The terminator is used
to prevent reflections on the Fieldbus cable resulting from the ends
of the segment. One terminator should be located at each end of the
Fieldbus segment.
Features
• 100 ohm resistor • Compact, moisture resistant shell
• 1 microfarad capacitor
Specifications
Resistor 100 ohms +/-1%
Schematic drawing
Capacitor 1 micro farad +/- 5%
Housing material ABS
+
Pins 2 (not polarity sensitive)
Dimensions (L, W, H) 28mm, 14mm, 14mm
Operating temperature -40°C to + 80°C (-40ºF to 176ºF)
Dimensions (mm) Wiring diagram
+ –
1.218.739.5774 95 StoneL.com