100%(1)100% found this document useful (1 vote) 2K views49 pagesInstruction
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
INSTRUCTION MANUAL
FOR
SASAKURA
FRESH WATER GENERATOR
K SERIES
SASAKURA ENGINEERING CO., LTD.CAUTION
1. Welding and other working with fire are prohibited due to the prevention of coating
inside of plant.
Observe the following items strictly for keeping tube plates and cooling tubes of
condenser from corrosion and erosion.
A) While operating the plant, open Cooling Water Inlet-Valve of Condenser
fully and regulate Cooling Water Quantity by Outlet Valve only and keep the
back pressure of minimum about 0.2 kg/cm2G.(0,019MP2)
B) And Also regulate Cooling Water Outlet Valve so as to keep the prescribed
temperature difference between inlet and outlet of condenser.
(Please refer to the heat balance as to temperature difference.)
C) Watch over Anode Protectors in Condenser Cover about every six months.
3. Carry out following items in order to prevent scale formations in heating tubes.
A) Keep the feed water pressure within green belt of pressure gauge.
B) Output shall be kept at or less than normal capacity specified.
~ 4. Centering of the shaft is important for Rigid coupling type pump. Identification
mark shall be made when the shaft end is removed. Keep centering at the shaft
end within 5/100 when the pump is assembled.
(Do not remove the shaft during normal maintenance.)
5. Alignment of ejector pump and motor shall be re-adjusted by the
shipyard/shipcrew whenever they are newly installed, replaced or
maintenance work is done.
6. If gauge (vacuum, pressure, compound) shows wrong
indication,pull yellow plug on the top of the gauge
to release air inside.INDEX
Page
1. DESCRIPTION OF THE PLANT... 1
2. FEATURES OF THE PLANT AND ITS SYSTEM eee . 2
3. OPERATION. +s seseeeeeeeeeee 3
Sele STARTING UP ects. 5
3-2, REGULATING. THE CAPACITY « s
3-3, STOPPING... sss. sees 5
3-4, ATTENTION DURING OPERATION «++ eeseeeeeeeeereeeees 7
G5 (iti ef! ocoococuoruooesuodeounosoouossedadebouncsod 4)
4ol. TESTING THE PLANT FOR LEAKS. ...+.sse0eeeeeeeeeeees 10
4-2. PRESSURE TEST OF HEAT EXCHANGER AND CONDENSER .... 10
5. CLEANING THE TUBES (DESCALING METHOD)........+ ll
5-1. CLEANING INTERVAL FOR DESCALING....--++-+ iL
CLEANING METHOD... Sennen etree eee nee eee + ln
WAY TO PROLONG THE INTERVAL OF DESCALING . - 1s
‘CONTINUOUS INJECTION OF FEED TREATMENT.... 1s
6. REPAIR OF INSIDE COATING... es sees cece cece cece eeeeees wz
7. TROUBLE SHOOTING .. +. 4-45 . Gonba0 20
8. MAINTENANCE LIST... eee ”
9. OPERATION BY STEAM (In case that steam injector is installed)... . 31
10. HANDLING OF MECHANICAL SEAL FOR DISTILLATE PUMP....-.++++ 55
11. SCALE INHIBITOR "SASABIT" + 36
ILLUSTRATIONS
Skeleton of Internal Arrangement for Fresh Water Generator
Data Sheet for Fresh Water Generatorov
DESCRIPTION OF THE PLANT
‘The Fresh Water Generator consists of heat exchanger, separator shell and condenser.
And the water ejector, the ejector pump, the distillate pump, the salinity alarm, the
deflector, the mesh separator, the solenoid valve, and the water meter are supplied as
the attachments.
K series F.W.Generators consist of K, KM, KE types. Followings are main features of
each type.
Ejector pump is installed under the
waterline as the former type.
1, Energy saving type
Driving water of the ejector pump is
taken from the outlet of condenser jacket
cooling water.
2. Easy operation
Ejector pump is assembled with the main
body, and a complete set of compornents
of F.W.Generator is installed on the same
floor.
Unnecessary to supply sea water from the
general service pump because driving
water of the ejector pump is used
for condenser jacket cooling sea water.2. FEATURES OF THE PLANT AND ITS SYSTEM
Since the Fresh Water Generator utilizes the waste heat in the circulating cooling
water from the diesel engine. In case of damage to the fresh water cooler, it may be
possible to use the fresh water generator only as cooler during the repair of the fresh
water cooler.
Part of the engine cooling water is led to the heat exchanger in the fresh water
generator where it circulates on the outside of the heating tubes, giving off heat to
the feed water (sea water) passing through the inside of tubes.
The feed water then evaporates at a comparatively low temperature because the
inside of the generator is formed vacuum by the water ejector. The generated vapor
in the heat exchanger passes through the deflector and mesh separator to the
condenser where it is condensed by the cooling sea water.
‘The brine, concentrated sea water, is constantly taken out from the evaporator shell
and discharged to over board.
‘The ejector pump supplies sea water to water ejector. The distillate pump extracts
the fresh water produced from the condenser of the Fresh Water Generator and
transfer it to the fresh water tank,
Part of cooling sea water heated by condenser is used as feed water and flow into the
bottom cover of the heat exchanger after heated by the preheater and passing through
the feed water orifice.
Produced fresh water is always registered by the salinity alarm (salinity indicator).
When the salinity is up to the prescribed value (normally 10 ppm, adjustable to the
other value), the solenoid valve on the improper fresh water line opens which leads
improper fresh water into the evaporator automatically. Fresh water with high purity
flows into the fresh water tank. ~OPERATION
3-1A. STARTING UP (K, KM type)
Before starting, the following valves are to be closed.
Inlet and outlet valves for jacket cooling water of heat exchanger
Vacuum breaker valve
Outlet valve for distillate pump
Feed water inlet valve for heat exchanger
Bottom blow valve
1) Open the outlet and inlet valves of condenser cooling water and lead cooling -
water into the condenser.
2) Start the ejector pump and then open the pump outlet valve and the overboard
discharge valve.
3) Open the feed water valve and lead sea water into the heat exchanger.
Feed water quantity can be seen by the readings of the compound gauge in
front of the feed watr orifice. Control feed water quantity within range of
green belt shown in the compound gauge.
4) When the vacuum in the generator become about J 79 SsmHe, ‘open the inlet and
outlet valves for jacket cooling water of the feet Oe. The outlet valve
for jacket cooling water is to be opened slowly lest the heat exchanger should
be overheated suddenly.
5) The air vent cock at the upper part of the heat exchanger shell should be
opened whenever jacket cooling water passes through the heat exchanger and
should be closed after confirming that the air in the shell is completely
discharged.
6) Work the salinity alarm in order to check purity of the fresh water.
7) When the distillated fresh water comes up to the sight glass of the suction pipe
of distillate pump, start the distillate pump and regulate the water quantity by
the outlet valve of the pump. If there is not abnormality on the discharge
Pressure of distillate pump, the level need not always be fixed. (normal
discharge pressure is 1.4 - 2.2 kg/em2) (0,137 — 0.216 MPa )
Fresh water quantity is increased as the sea water temperature falls after
adjusting to the fixed fresh water quantity. Naturally water level at the
distillate pump suction side increases, produced water stays inside of the
condenser, the effective heating area of the condenser decreases, evaporation
quantity decreases, accordingly, the operating condition will be naturally
balanced.3. OPERATION
3-1B, STARTING UP (KE type)
Before starting, the following valves are to be closed.
Inlet and outlet valves for jacket cooling water of heat exchanger
Vacuum breaker valve
Outlet valve for distillate pump
Feed water inlet valve for heat exchanger
Bottom blow valve
»
2
3
4)
3)
6
”n
Start the ejector pump and then open the pump outlet valve and the overboard
discharge valve.
Open the outlet and inlet valves of condenser cooling water.
Open the feed water valve and lead sea water into the heat exchanger.
Feed water quantity can be seen by the readings of the compound gauge in
front of the feed watr orifice. Control feed water quantity within range of
green belt shown in the compound gauge.
When the vacuum in the generator become about 70 cms, open the inlet and
outlet valves for jacket cooling water of the heat Se The outlet valve
for jacket cooling water is to be opened slowly lest the heat exchanger should
be overheated suddenly.
The air vent cock at the upper part of the heat exchanger shell should be
opened whenever jacket cooling water passes through the heat exchanger and
should be closed after confirming that the air in the shell is completely
discharged.
Work the salinity alarm in order to check purity of the fresh water.
When the distillated fresh water comes up to the sight glass of the suction pipe
of distillate pump, start the distillate pump and regulate the water quantity by
the outlet valve of the pump. If there is not abnormality on the discharge
Pressure of distillate pump, the level need not always be fixed. (normal
discharge pressure is 1.4 - 2.2 kg/cm2)( 0.137 ~ 0.216MPa)
Fresh water quantity is increased as the sea water temperature falls after
adjusting to the fixed fresh water quantity. Naturally water level at the
distillate pump suction side increases, produced water stays inside of the
condenser, the effective heating area of the condenser decreases, evaporation
quantity decreases, accordingly, the operating condition will be naturally
balanced.3-2.
3.3.
REGULATING THE CAPACITY
‘The capacity (quantity of produced water) of the Fresh Water Generator is
regulated by increasing or decreasing the quantities of jacket cooling water to the
heat exchanger.
‘The capacity of the plant is now measured by means of the water meter, the
quantity of the jacket cooling water shall be regulated by the by-pass valve to the
fresh water cooler until the plant produces its normal capacity.
In case that the temperature of the jacket cooling water is lower than the
prescribed one, the flow quantity passing through the heat-exchanger shall be
increased more.
The supply of cooling sea water to the condenser is regulated so that the cooling
sea water temperature rises about prescribed value when passing through the
cooling tubes of the condenser.
‘The evaporation temperature should be about 45°C to 60 OC,
If the evaporation temperature is too iow which may occur at low sea water
temperature area, the vacuum breaker valve is opened little or the quantity of the
cooling sea water for the condenser is decreased which will make the evaporation
temperature rise. If the evaporation temperature is too high which may occur at
high cooling sea water temperature, the quantity of cooling sea water to the
condenser is increased which will make the evaporation temperature drop.
Too high evaporation temperatures increase the risk of scale formation in the tubes
of the heat exchanger, and too low evaporation temperature will owing to the
resulting great vapour volumes mean a risk that sea water drops are brought with
to the condenser resulting in fresh water with a too high salt content.
STOPPING
When the vessel approaches a port, land or estuary the Fresh Water Generator is
desirable to be stopped because at such places the sea water may be heavily
infected with bacteria, and there is a risk that bacteria can be transferred to the
fresh water produced.
Before the Fresh Water Generator is stopped the by-pass valve for the jacket
cooling water should first be opened.)
2)
3)
4)
3)
6)
K, KM type
Close the inlet and outlet
valves of the heat exchanger.
Stop the distillate pump.
Turn off the salinity alarm.
Close the feed water valve.
Stop the ejector pump.
Close the outlet and inlet valves of
the condenser.
a)
8)
Open the vacuum breaker valve.
Close the overboard discharge valve and inlet valve of the ejector pump.
Note:
a)
b)
¢)
)
2
3)
%
)
68)
KE type
Close the inlet and outlet ~.
valves of the heat exchanger.
Stop the distillate pump.
Turn off the salinity alarm.
Close the feed water valve.
‘Stop the ejector pump.
Close the outlet valve of the
condenser. (overboard discharge
valve)
Supply the feed water for few minutes in order to cool the heat
exchanger.
Don't open the bottom blow off valve in order to make atmospheric
pressure because sea water in the heat exchanger spout and strike the
deflector.
In case that the plant is stopped for a long time, the heat exchanger
is emptied of sea water by opening the bottom blow off valve at the
bottom of the heat exchanger.3-4.
ATTENTION DURING OPERATION
1)
2)
Regulating the Capacity
Any regulation of the capacity of the Fresh Water Generator should be
effected by regulating the amount of jacket cooling water to the heat
exchanger.
Although when the tubes are clean, the Fresh Water Generator will be
able to produce fresh water in excess of its rated capacity, we
recommend that you will operate the plant at the prescribed quantity of
fresh water or less as production in excess hereof can involve the risk of
scale formations.
‘The Condenser
In order to condense all generated vapor in the heat exchanger, cooling
sea water, as cold as possible should be flowed to the condenser and also
should be checked temperature difference of cooling sea water between
inlet and outlet of condenser for regulating the amount of cooling sea
water.
In case excess cooling sea water should be supplied, turbulent corrosion
may possibly caused due to too high velocities in the cooling tubes of
condenser.
(On the contrary, when cooling sea water is short, the capacity of
produced fresh water should decreased because of short cooling
performance.Calculation for quantity of cooling sea water of condenser : -
dD
tL
2 : Outlet temperature of condenser
Q + Capacity of cooling sea water
Capacity of produced fresh water (T/day)
Inlet temperature of condenser
Dx 22.4 (tm
(ty -
Q
It is requested to adjust outlet valve of condenser in case that capacity of
cooling sea water is exceeded more than the value specified in heat
balance.
Maximum quantity of cooling water of each type (t/n)
K. KM type 10 1s | 20 25) |) 20) 35 40 50 | 60
Max. Flow Q'ty | 24 T/h | 37 T/H] 52 T/h| 67 T/h] 79 Tin) 90 T/n] 95 Th | 133 Th | 1427/1)
3) Automatic Control of the salinity in the Fresh Water
‘The Fresh Water Generator is furnished a salinity alarm which automatically
registers the selinity in the fresh water produced. This salinity alarm
gives an alarm if the salt content exceeds prescribed value. In addition
to the alarm lamp, a solenoid valve is operated which automatically return
improper fresh water produced to the vapore shall.
When the value of the sea-salt content returns to the normal readings, this
alarm circuit is automatically restored from the alarming state and
consequently alarm lamp is turned off, the alarm and the solenoid valve are
stopped and the fresh water with high purity begins to flow into the fresh water
tank of the ship again.
As for the detailed explanation of the salinity indicator, please refer to the
annexed "Instruction manuals for a Salinity Alarm".°
4)
dD
Checking the Evaporation Temperature
It is very important, in order to avoid the risk of scale formation, to
maintain as low an evaporation temperatue as possible, without the
salinity in the fresh water produced being too high.
Therefore, we recommend that the evaporation temperature should be
checked regularly on the thermometer, fitted on the separator shell.
‘The thermometer on the separator shell states the exact evaporation
‘temperature when the Fresh Water Generator is working steadily after
having run for 15 ~ 30 mins-- ---- ~
Keeping of Journal
We recommend that the water production, the various temperature and so
on are regularly recorded in the operation journal inserted at the end of
this instruction manual.
When the various data are recorded regularly standard of comparison will
be available if irregularities or troubles should arise in connection with
the operation of the Fresh Water Generator, and which may be of great
significance in establishing the reason for these irregularities or troubles.4,
INSPECTION
At suitable intervals, for instance twice a year, the top cover of the separator shell
and the bottom cover of the heat exchanger should be removed in order to inspect
whether scale has formed in the tubes and the state of exfoliation of inside coating.
At the same time, the condenser covers are removed in order'to check that the
condenser cooling tubes are not fouled with sludge or the like.
‘The pumps shoulld be inspected and cleaned regularly, and the corroded parts, if any,
shouyld be replaced to the spare ones.
4-1. TESTING THE PLANT FOR LEAKS.
After an inspection or if there is any difficulty in maintaining the vacuum - a leak
test should be carried out, as in course of time leaks may occur due to
deterioration of packings and joints. ~
This test procedure is as follows.
1) Close the outlet valve of the distillate pump, vacuum breaker valve, bottom
blow off vaive and feed water valve.
2) Inject air to evaporator shell.
3) Keep the shell pressure of about 0.5 kg/cm2G. (0.049MPa )
4) Spray soap solution to packings and joints.
4-2. PRESSURE TEST OF THE CONDENSER AND THE HEAT EXCHANGER ~
Condenser
Remove the water chamber of the condenser, keep the inside pressure of the shell
0.5 kgf/cm? by injecting air to the inside of the evaporator, find out leakage by
C4 PE) ,
‘Spraying soap solution.
Heater
Remove the bottom cover of the heater. Leakage can be found aut by giving 4 - 5
kgf/cm2 water pressure on the shell side. (0.392 -049MPa )
For tube crack and pin hole, spread soap solution on the surface of tube plate and
give the atmospheric pressure of 1.0 kgf/cm? on the shell side.
(0-098MPa )
-10-10
5. CLEANING THE TUBES (DESCALING METHOD)
Sel.
CLEANING INTERVAL FOR DESCALING
‘The fresh water generator is equipped with a heater, a conderiser and a preheater.
Scale forms mainly in the heating tubes of the heater and it is hardly found in the
cooling tubes of the condenser under normal operation. Chemical cleaning of the
whole system can be made by fitting adapter (option) to the corrosion plate
connection of the condenser water chamber. Sea water boils and evaporates in the
heating tubes, and consequently sea water touching the heating tubes is
considerably concentrated and supersaturated. This is why scale is deposited in the
heating tubes.
Cleaning (descaling) of the inside of the heating tubes should be made twice or
three times a year in general. However, the interval depends upon the operating
conditions and the properties of sea water. Therefore, note the following
phenomena as the standards for judging the time for cleaning.
a) Quantity of jacket cooling water can be estimated by temperature difference
at the outlet and inlet of the heater when the temperature in the shell is kept
at or below evaporation temperature of the heat balance, and jacket cooling
water quantity requires much more than that of the heat balance in order to
produce the fixed capacity on condition that jacket cooling water temperature
is same as that of the heat balance.
Calculation :
D_: Capacity of produced fresh water (T/day)
QJ +: Jacket cooling water quantity (T/h)
T + Temperature difference at the outlet and inlet of the heater
9 = 245 XD (Tm)
T
1») When the vessel if fitted with a steam injector, condition of scale formation
can be easily found out. While the temperature in the shell is kept same as
that of the heat balance as well as item a), inlet temperature of jacket cooing
water is balanced at higher temperature than before.
When a steam injector is used, quantity of produced fresh water has almost no
change. It is necessary to keep operation journal for check of scale formation.
eleIf. any of the above mentioned phenomena is observed, remove the sight glass
in front of the separator shell and insert the test rod which is supplied with the
Fresh Water Generator, if the test rod is not inserted into the heating tubes,
scale formation occurs more than | mm thickness in the heating tubes
therefore clean it soon.
5-2. CLEANING METHOD
‘Scale may be either peeled off by physical methods of dissolved by chemical
methods. The former includes the use of brush and-drifiy-the-rapid coeling-method,
injection of pressurized water, etc., but it is rather difficult to completely remove ~
scale by these methods. We will explain a method to use chemicals which prevails
recently because it requires shorter cleaning time, hardly damages the tubes and is
economical and effective.
5-2-1. Preparations for Cleaning
a) Draw sea water in the shell from the Bottom Blow Off Valve
b) Close the Bottom Blow Off Valves completely and remove the sight
glass.
5-2-2. Making Soultion
Make up solution in the drum.
(in this case, be sure to pour water into the drum first and then chemicals.)
5-2-3. Recommended Types of Clemicals and the Names of the Manufacturers
Brand Distributor
SAF - ACID Drew Chemical Corporation U.S.A.
D.S.C. Yokosuka Kasei Co. Ltd. Japan
Chiyoda Kignas Oil Co., Ltd. Japan
Mitsukane Japan
GAMLEN XD Gamlen Chemical Company U.S.A.
ATLAS H-400 ATLAS Preservative Company U.K.
** Please refer to the catalogs of each manufacturer for detailed.
-12-1L
5-2-4.
a) Submerged Cleaning
Pour solution into the heater through the sight hole until the upper tube plate is
soaked and leave it as it is. The time required for cleaning vaties in the thickness
of scale. When the solution becomes saturation, it has no capacity for cleaning.
In this case, interchange with new solution a few times.
ADAPTER
(K 15 ~SOTYPE)
Mt That
w= [por
ped
(K 3~10 TYPE)
CHEMICAL,
TANK
b) Circulated Cleaning
As the above drawing shows, by fitting the adapter for the inlet of solution to the
connection of corrosion plate at cooling water inlet nozzle of condenser water
chamberr, and using the socket of bottom cover for outlet of solution, clean the
whole system of heat exchangers.
Quantity of solutin required for each type is shown as follows. Density of solution
shall be a little bit higher than recommendable density by each maker.
-13-KKM, KE 3 | 5 | 10|-15] 20] 25} 30]. 35] 40] -50] 60
Condenser ai] 12). 27] 43] 52] 64] 77])-93/100/150/160
Submerged
Cleaning
Heater |e] 22] 25} 44] 62} 85/105}145}146/1701 206/230
Circulated
Cleaning
33] 37| 71|105}137]169]192]239| 270/356] 390
5-2-5,
5-2-6
5-2-7.
During circulated cleaning, add the capacity of the cleaning tank to the total
quantity.
Discharging Solution after Cleaning
After cleaning, solution should be discharged through the bottom blow-off valve
fitted to the bottom cover of the heater. Since the above mentioned chemicals are
for dissolving but not for peeling off, there is nothing to worry about damage to the
impellers of the pump of clogging of the pipes.
Finishing Cleaning by Running Sea Water
After discharging solution, let sea water run through the heater for the cleaning of
the inside in the following way:
Flow sea water into the heater through the feed water line. Then discharge it
overboard through the ejector by operating the ejector pump. Repeat the pumping
and discharge alternately until the inside of the heater becomes clean.
In this case, take care not to let sea water in the condenser.
Inspection after cleaning
Cleaning is usually finished if no scale is found at the upper part of the inside of
the heating tube by putting the light from a flashlight on that part from the sight
glass.
However, scale forms most around at the part of 1/5 - 1/4 of the distance between
the tube plate from the lower tube plate, or at the lower part of the vertical
heating tube.
-1b-12
5-3.
5-4
Shel.
Therefore, be sure to confirm that the whole inside of the tube has become clean
by thoroughly checking the lower part of the inside of the heating tube with-such
an electric light that can light that part or by inserting a test rod, and continue
cleaning until no scale is found throughout the tube.
Never feed steam during the cleaning work as it will damage the inside coating of
the Fresh Water Generator.
WAY TO PROLONG THE INTERVAL OF DESCALING
In order to prolong the interval of descaling as long aé possible, please keep the
following items:
a) To operate the plant with the capacity under the prescribed one.
b) To feed the sea water as much as possible the ejector can discharge.
¢) If possible, not to operate the plant at the contaminated water area such as
harbors and ports.
d) In stopping the plant, continue to feed water until the heat exchanger shell
grow enough cold for you to be able to touch by hands and fill the new sea
water, which is not concentrated, to the upper tube plate of the heat
exchanger.
CONTINUOUS INJECTION OF FEED TREATMENT
The above mentioned cleaning method is that applied periodically while the fresh
water generator stops running.
‘On the other hand, the method mentioned here is that positively prevents scale
from forming by continuously injection the prescribed amount of feed treatment
into the feed water line during the operation of the Fresh Water Generator, thus
lengthening the life-span of the plant without lowering its performance.
Recently many vessels have adopted this method dur to ecomonical merit.
Kinds of Feed Treatments (Scale Inhibitor)
Although there are various chemicals, we recommend "SASABIT" which was
specially developed for F.W. Generators.
-15-5-4-2.
5-4-3.
Saba.
Injection Method
‘Chemical tank piping is to be connected with the screw connection for scalé
inhibitor which is located behind feed water orifice, and chemical must be supplied
continuously during operation.
(injection pump is not required because feed water line after orifice is vaccum.)
Feed Treatment Injection System
The standard type of feed treatment injection system(capacity : 25 liters) including
an electromagnetic pump) specially arranged for this fresh water generator is
suppliable on request.
Care to be Taken When Pouring Feed Treatment Continuously
Keep watch on the remaining quantity of solution in the tank and supply solution in
good time lest air is put in the fresh water generator from the empty tank.
-16-13
6. REPAIR OF INSIDE COATING
If during an inspection of the Fresh Water Generator it is ascertained that th
side
coating is damaged.
a) Repair can be effected in the following way;
Damaged covering is scraped off and the surface is thoroughly dried. By means of
sandpaper coating and the steel surface with the width of 20 mm from the damaged
part is ground and cleaned. Therefore under coating is put on the steel surface and
‘then Epoxyresin is applied, but now also-on the previously ground part of coating.
The way of coating is as follows : -
Material for repair and its package
Material 1. Epoxyresin 2145 (grey) net — 300gr.
d
ii)
2. Harder 2145 (grey) net 90 gr.
Method of repair
ii-1. Kind of damaged part
damaged
—_—2—— coat ing rubber
iron
Rooting rubber
atteMethod of repair
(1) Grinding the rubber of iron and rubber by grinder.
Remove the damaged coating rubber,
If coating rubber become off from the iron part, the damagee rubber shall
be cut off by knife or grinder and repaired.
(2) Cleaning and drying
——a
Cleaning with gasoline Dry with infrared ray
Surfaces to be primed should be cleaned and dried.
In order to clean and degrease to be primed, wipe with a gasoline soaked
cloth. Other solvent of commercial paint may be used instead of gasoline.
~18-+14
Q)
w
ii-3.
Application of Epoxyresin 2145
Hardener (90 gr.)
"—————Epoxyresin (300 gr.)
After drying, Epoxyresin shall be applied.
Epoxyresin 2145 and curing agent 2145 should be mixed throughly.
Epoxyresin 2145 300 gr.
Hardener 2145 90 gr.
‘The pot life of Epoxyresin 2145 is decided on volume of the batch and the
temperature. At room temperature, the pot life of the mixture of
Epoxyresin is about 40 minutes.
Curing of Epoxyresin 2145
Epoxyresin 2145 cures at room temperature by mixing of harder 2145.
Curing generally completed for one or two days.
Notice
‘These materials should be handled carefully.
If the material touch skin, immediately wash the skin with water
thoroughly.
-19-7. Trouble Shooting
YES
Leaks in
Repair the
leak's part.
Is ejector pe
Normal?
Scale formation in the
cooling tube:
Too low capacity
v
‘Seale formation of YES.
heating tubes (In & Out side)? I
the plant?
NO
YES
s?
[ne
Normal evaporation temperature?
YES
formance ) 0
No
Fresh water stay in
condenser shell?
E
No
Clean the cooling
tubes. 1
Clean the heating tubes.
Nozzle clogged?
YES
Clean the nozzle.
-20-
Erosion of diffuser?
Renew the diffuser.
NO
Back pressure of ejector
more than 10 M?
‘Check the pipe line
NO | of ejector outlet.
B<Trouble of ejector pum
Jakcet cooling water
temperature is lower than
prescribed one?
Check the air line
of ejector.
See "Trouble Shooting”
of "Trouble of Pumps".
Raise the jacket
cooling water
temperature.
eed
Short of jacket cooling
water quantit
Non-return valve of
ejector stick
Increase the jacket
cooling water
quantity.
No
Air stay in|
shell?
heater Discharge air.
Trouble of solenoid
Repair the solenoid
0 valve.
‘of water YES
Troub!
mete
¥
High salinity of produced
fresh water
‘See "Trouble Shooting" of
‘igh Salinity of Produced Fresh Water"
Renew the water
meter.
No
—21-Watermeter of Produced Fresh Water
‘This watermeter is liquid crystal digital watermeter which contains a lithium battery.
‘The watermeter is one of extremely important accessories to check the condition of the
F.W. Generator.
‘Watermeter's life depends on frequency of use, during four to six years operation, the
number of revolution will be about several billions.
It will be the time for which watermeter shall be replaced completely when liquid crystal
display disappears.
‘According to the Measuring Law, one of the Japanese domestic law, all sorts of
watermeters for home use shall also be replaced with calibrated one once for six years.
c D {
| (i late a
Air stay in cooling out of order
tudes, See "Trouble Shooting”
of “Trouble of Pumps".
No
Repair the air vent
valve at the Suction and discharge pipes
condenser cover. of distillate pump clogged.
—22-i6
alacm?
Too low ev:
YES.
(Open the vacuum breaker
valve a little.
Disorder of salinity
temperature
less than 35 °C 7
High salinity of produced
3
g
5
Operate under normal capacity.
No
Stain of cell?
No Clean the cell.
‘aporation| Repair the
salinity alarm.
NO
(Damage
YES,
Plug the damaged
tubes.
No
Too high brine level \_yeS _ /Trouble of xo
in evaporator shell? ejector? Trouble of
YES ejector pump
NO Nozzle YES
[As operated in port or at ( clogged? > Clean the
mouth of river, feed water NO ; nozzle.
is excessively contaminated. Erosion of \__YES
dittuser? Renew the
7 = diffuser.
a
‘Stop the plant.
Back pressure of
ejector outlet
more than 10 M
-23-:
Repair the
NO
leak's part
[Feoubie of poms |
Trouble of
electric motor.
YES
No
a Repair the
7 electric
Pump seizes. motor.
Suction pipe or \¥ES
strainer clogged cleaning Repair the pump
NO YES
Cimpelter clogged? )-9f cleaning
NO
Motor rotating
direction
is wrong.
: ‘
3
zie Sucking air.) No
0
Repair the a The first, discharge
leak's part. water but soon
ceases to discharge
[oo low water?
rotating
speed?
‘Check the
electric
source
NO
—24-
discharge pressure
YES
Correct
pi
piping
Sucking aie? p—"=2>—y
Repair the
No leak’s part.
B
|
|Casing ring is
worn?
Renew the
b casing ring.| [ Erosion of
impeller?
| t
i Renew the
i impeller.
17
‘Sucking air
‘through stuffing
box..
ad
‘Check sealing pipe.
Adjust gland packing or
mechanical seal.
—25-YES
Motor overloaded?
Abnormal metal NO
contact exisits Bearings YES
in the rotating overheated? ‘Connection is\_yEs
parts? wrong. l
i) Correct
YES vo 4 xo the
Remove Vibration takes center.
contact. [| place. Bearingsare\ yes
ves _/ Connection is weong? 1
wrong. Renew the
}— Impeller balance NO bearings.
Correct No is wrong. Shait is YES
the center. Ge v
[~ Bearing assembly xo Renew the
yes _/Packing is too is wrong. shaft.
}— Connecting is increased.
Loosen gland or o wrong.
otherwise renew
packing. }— Shaft is beat.
Bearings are
wrong.
Renew the
bearings.
|~ installation is
wrong.
acings are worn.
|— Foundation is weak.
L_ Other vibration is
transmitted.
—26-
Check up whether
excessive wear exists
or impeller balance holes
are clogged, and
reassemble if necessary.
i18
Maintenance list
Part To be checked Work Interval
£./2./2
s| Eflzs|ée
€| $3/8812$
5] e2|e2/E3
& aeivs|te
B| B8l2s/es
2 | oclgsles
&| aslaslas
Heat Seale Check the scale formations
exchanger | formations inside the tubes.
inside the If scale is formed, °
tubes clean (descale) according l
to the instruction manual.
Leakages Pressure test outside
the tubes as stated in °
the instruction manual.
Evaporator | Defects on Check for damage to
shell the coating surface and take °
coating @ proper step according
to the instruction manual.
Defects of ‘Check the damage and °
deflector repair if necessary.
Condenser Scale The condenser covers:
formations are removed and the
inside the tubes are inspected °
tubes for scale formations
possibly the tubes are
cleaned.
-27-Part To be checked Work Interval
2,/2./2
2 | ssegies
5 | e2/esles
E | mslweslSs
=| 28lesles
& | dslasjas
Condenser Corrosion of Check for corrosion
the tube ends | and repair if necessary.
Corrosion of | Check for damage and
the tube corrosion, and repair
plates if necessary.
Conditions of Check for fitting
corrosion conditions and degree
plate of wear and replace
if necessary.
Defects on the | Check for damage to
coating inside | coating surface and take
of cover a proper step according
to the instruction manual.
Water Wear scale Nozzle and diffuser are
ejector formations checked and cleaned.
Worn out nozzle and
diffuser is replaced.
Strainer Impurities Cleaning
tor
water meter
-28-19
Pact To be checked Work Interval
a| 58/83/88
5 | €2/23)&2
E | msleslSs
2 | 28l2sles
a) aslaslas
Non-return Scale Cover is removed,
valves formations housing and.non-return °
mobility of valve are controlled and
flap cleaned.
Strainers Impurities Filter screen are taken
in front of out and cleaned. °
feed water
orifice
Feed water | Impurities Cleaning °
orifice
Air vent Obstruction Cleaning
valve for .
condenser
cover
Gland Wear Check condition of
packing, packing and leakage and S
cepair if necessary.
Impeller | Wear Check the condition of
casing | corrosion wear down and corrosion.
2 ir °
§ | cine a
© | shate
3
£ | steeve
Bearing | Insufficiency Infuse the grease °
case .
-29-Part To be checked Work Interval
| 2 lz |é
2| s§sejes
= 3
s | €2)es\c2
€ | asles|is
2] 2slesies
a | dsldslais
Gland Wear ‘Check condition of pack-
packing ing and leakage and repair °
if necessary.
5
& | Impeller | Wear ‘Check the condition of
= | casing | Corrosion wear down and corrosion.
= | cing °
& |. sMechani-
cal
Seal
Salinity Impurities Clean with care not to °
| cell injure the element.
eI Contra! {| Adjust Adjust the indication and
3 | panel alarm according to the °
instruction manual.
Note: * ies
wd:
o3e
For cleaning interval for descaling, refer to the instruction manual.
The degree of wear of the corrosion-proof plate varies with the
properties of sea water and other conditions.
Therefore, change inspecting intervals properly, making good use of
experience gained in the ship.
When the material of the ejector pump impeller is PBC/ALBC, the
impeller will wear out as time goes by and its surface will be
damaged.
Please note that this is enevitable due to high speed revolution.
(SUS impeller will also wear out, but its speed is lower than that of
the above impeller.)
-30-9. OPERATION BY STEAM (IN CASE THAT STEAM INJECTOR INSTALLED)
Distillation can be achieved also by steam instead of jacket cooling water.
For operation with steam, a built-in steam injector is to be used.
9-1. OPERATION SEQUENCE
‘The vacuum in the shell should be more than 70 cmHg-V. Feed water should be
supplied in normal condition and always at a pressure within the range of green
mark on the feed water pressure gauge. “Before starting operation as mentioned
below, see if sufficient cooling sea water is being supplied to the condenser.
(1) Close the inlet and outlet valves of jacket cooling water completely, and open
the valves in the jacket water outlet line (for drainging jacket cooling water).
As it is not contain various kinds of unticorrosive chemicals, drainage of such
cooling water should be accelerated by opening the air vent cock.
(2) After blowing jacket cooling water, shut the jacket water outlet and then
supply fresh water usable for boiler to the heater (shell side), pipings and the
steam injector. When they are competely filled with water, which can be
ascertained by opening the air vent cock, close the fresh water inlet valve
(for filling fresh water).
(3) The cock at the top of the drain pipe shall be always opened because it serves
as a syphone breaker.
(A syphone breaker is unnecessary when a drain tank is installed on the higher
location than F.W.Generator or on the same floor.)
(4) After the above mentioned preparation, open the steam valve before the
steam i
jector gradually in order to let steam in. Fresh water in the piping is
circulated as well as heated by steam. As heating fresh water is cooled in the
heater, steam drain goes up through the drain pipe and then it is exhaused into
‘the drain tank.
9-2. CAUTION
(1) Fill the heater (shell side) and the pipes with fresh water.
If there is air inside the shell, the packing for the heater may be damaged by
abnormal rise in temperature. Such air will also cause abnormal noise or
vibration due the cabitation or pulsating movement of inside water.
=31-(2) Do not open the steam valve rapidly. If so, water in the shell will pour into
the drain tank and cause vibration.
(3) If steam pressure is lower than the designed value, inside water will pulsate
and cause abnormal noise and vibration.
REMARKS ON THE INSTALLATION OF THE STAM INJECTOR
(1) If the back pressure is exerted to the discharge line of the steam drain of the
steam injector, extraordinary vibration’ may occur in the-injector and there is
a possiblity that the operation of the system may become impossible. As the
limit of this back pressure varies in accordance with the supplied steam
pressure, piping must be carried out referring to the following criteria.
Supplied steam pressure Back pressure
3.0 kg/em2G ( 0.294MPa ) Max. 3 mAq
4.0 (.0.392MPa} 4
5.0 (0,49 Mpa) 5
| 6.0 (0.588 Mpa) 6
{ 7.0 (O.686MP ) 7
i 8.0 (0.784MPa) 8
i 9.0 ( 0,862MPa) 9
| 10.0 (0,96 mPa) 10
(2) If the supplied steam pressure is lower than the designed pressure, the same
vibration may be caused to the system. The flucturation from the designed
value must be within about + 5%.
(3) The heating drain outlet pipe of the steam drain discharge is necessary only
when the drain tank is located lower than the installation position of the
distilling plant. The height of this heating drain outlet pipe is min. 1800 mm
from the base surface of the plant.
(4) Valves must not be contained in the discharge line of the steam drain. This is
because the fact that the valves are located in the drain line and the operation
is carried out with the valves closed, the steam pressure is exerted to the shell
side of the heater of the Fresh Water Generator.21
20. HANDILING OF MECHANICAL SEAL FOR DISTILLATE PUMP
Since a mechanical seal is a precision component of rotating -
‘equignents, ik should be handled with utmost care. Also an
“ equiment to which the seal is installed shall be carefully
prepared so that the seal efficiently performs. Followings
are part names‘ of ‘the seal, its handling procedure and
notices on maintenance of equipments. You are requested to
read them carefully for proper handling. . 4
1. :Part Name of Mechanical seal
No. Name
2
S
1 Cup Gasket
2 Mating Ring
3 Seal Ring
4 Case
5 Packing
6 Drive Ring
a Coil spring
8 ‘Spring Holder
BeBe
—33-i ———
___
aun
vas wagany
aovains 4yrwas
aovs w%s
. “yW YATA.peaaam sy;OTS
azA:e9ez OY] UReTO ‘aDey Twas B43 UO PEyoeggE
By x999Uu UBFoxos x0 A3z7p S} BOUZ Tees 943 Fx (S)
“uoFIUTTeI SUT aya z09ze SUTy
SuyzeK O43 FO USWUB;TeSTU ou aq PINoYs exOUL (¥)
suoPaeTTeasUy 9y3 709Fe Buysnoy 943 09 ATIYSTI
peaatz ang payooTzop oq JOU pTnoys yaxskH dno aus (c)
: suoFaeTTeIaSUT BAz309T59
pue sea xoz popuaumiosex st Too] uOTIeTTeISUT UW (Z)
suotguTTegeut Asva x03 vaxe oTaeT
-Te3sUy Vy} JO VoUZANS ay; UO ZeqNM Gand epTACrd (T)
Buysnon oF ( = FUTY SuTIeH
puy qexseg dno) Buyy AxeuoyzwaSs JO UOTFIVTTRISUT Cf ‘ON
touo mou e Yat
Buyxedq 943 voetder ‘os Fr "3324s yy UO ¥No
sunz yenay3 x0 TwTpex sexe Buyzeeq 94yq FF XO94D (C)
sBuyxoed 943 pue 3aX8v6 dno 94; Jo vorzans
By} Uo Bq PTNoYs sxa;;eW UBpexosy x0 sxeDS ON (Z)°
: systuyg pue adeys ‘azts pazynbax uy Atq0exe sy
: PETTURSUT By Tes Jy BAdYM woe sy) 3eyI WITZUOD (T}
quaudtnba 30 uoyzoadsur © z ‘ON
*yaoTs uveTo @ YaTA WeYa sAoUDT
‘ue 31 ‘Buyyoed oy3 x0 Jaxseb dno ayy JO aovzans
BuyTeas ay; uo astxa sa9qqeu uByeI0y AUD zy 994d (Fr)
*2u0 MOU B Y3TH
37 vovtder ‘eouewxoyxed sz] obewep ptnom yoTYR
Buyddyyo 20 Your Bey sous Teas ayy JUBAe yz UT (C)
ToyooTe 20 (NH) VOIeX TAWA ‘TFUIAN YAaTA peqaeM
“UROTD 9JOS YaTA 9ovF OY UvaTS "Aue Zr‘ 9dRz
| [89s yz UO ABTxXO Braz;eU UGFex0y Aue JT X99UD (z)
“TFRE ANOUITA S{UauOdUOD T{e ervdazd 03 vINs BxVH (T)
[was TeoTUVYDIN Fo UOTZ0edsUT T ‘ON
[was TwoTueyoaN Jo BInpsooIg UOTITTVISUT
z
—34—SHEET
_ ‘PewxyzUOD sf uoTaTPUCD TeuIOU ay T8ATT
uoyzvrado 34x 42033 “:uoT]TPUCD TeuroUGe zo abexe9T
Aue ef 233y3 FT yoayo 07 spuey Aq azeys ayy 2avz0u (S
*pearaqzuord ATIOFIIS |q plMoys buyuuns Arq (¥)
seBexeay Ou suy Teas TeoTURYOSW oy; avWG WxTFUCO
03 xoq BuyyINgs B43 03 sanssezd prnbyT apyaoza (C
spabuezae Atxadozd by
PTNbyT vopaetnoryo roy Buydyd ayy aeuy wxysuod (z,
” + Ayaoar709
POTTERSUT SF Teas TeoTUBYSAW BI F¥ya WTZUOD (T
voraezedo 9 ‘ON
*patteasuy Atzedozd aze
xeptoy Buyzds ayy pue Buyxde TFOo 84a avy WxFFUCD (1)
-35—
xeT{aduz pur xaptoy Buyzds *Buyzds Tyoo zo voyIeTTeISUL ¢ ‘ON
+Suyy Suyaey ayy 03 s3o"qQUCD Buy [wes
ayy Tyaun azeYs O49 TVA HUTA ‘buyaezor ayy BPTTS (S
razeys 9u9
qsuyebe Buydumq fq 99vz Twas 84a sBeuep oF Qou
paTTejeuy ATINyoxeo vq prnoys Buys Buyayegor aus (br)
suoTa eT Tea SUT
8U3 799z¥ p29z036T7p aq JOU PTNoYs ‘Buyxoed VuL (C)
SuOTaeTTEIBUT’ BAFRO3TZe PUT
Aewa 303 papuammosat sy TOO] UOFIVITeISUT SUL (Zz)
suopaeT Tea oUy Asve TOF vere vOTIeT
-Teasuy 9A JO eoRFING yz Uo 39zeM vInd ePTAoId (T
. ageys 243 Teno (BuTU aatza ‘a5ed
‘Buyyows “Buy Twas) Buyy Buyaegou zo woTAeTTeISUT ‘ON
a
a
onicinat”SCALE INHIBITOR FOR FRESH WATER GENERATOR
SASABIT
SASABIT is developed as a scale inhibitor of poly carboxylic
acid for the use of fresh water generators.
Mechanism of scale inhibitor is to ‘prevent scale deposits by
dispersing scale formation as well as delaying reaction and
to prevent this scale from adhering to the heat transfer
surfaces, in general this is called "Threshold Effect".
SASABIT increases threshold effect more than usual scale
inhibitor, so as that its performance of preventing scale
formation is much improved.
SASABIT prevents scale formation of calcium carbonate and
magnesium hydroxide which is produced by heating and
enriching sea water by pouring into feed water.
SASABIT ensures stable fresh water production without long~
time cleaning.
Typical Physical Properties
Main components : Poly carboxylic acid aqueous |
macromolecule
Appearance
Red brown liquid
Specific gravity: 1.25 ( at 25°C )
70 cps { at 25°C )
2.1 ( 1% solution )
Viscosity
PH
Dosage
Dosage is based on the standard of 10 cc per produced
water 1 ton in case of submerged tube type distilling plant
whose brine densities lower than 1.5 .
SASABIT is fed continuously to the evaporator inlet line by
means of electromagnetic pump or vacuum injection system.
Please refer to the attached "SASABIT injection manual" for
detailed injection method.Nvave _ vavsO 2 Nave vaso
LevZ-SLb(90)XV43IAL pSSt-12(90) TAL BBlE-EzS XT vElz-ELy (90) TaL
~—QUTOD URLN39 J1NN3S VUNHVSYS “QIT"09 SNINSINISNA VUNHYSYS
wee BREE ep engin Le Rith UXA NCH LOL HRM LS “
: “esate YY SG ‘
uvamonasiovavo — MQLAQIGE “AVE EBOISzaEENY (4751073 AKG
TONS 07 SAE GA GUE SY “LUM OBB %'ION C'B +1
eee cee ce cena UY GAMES 4 UU 1 ENG SUMOACALMUT CLS “%
OS sy oy SE OF sz’ oz si Gt Hien SIY _ (agind/99)@/0118/99pR0'O “WRC RM *t
001 06 OB OL 09 OS OF Oe OZ % ION EB EY ECA. EEA
ce yas pue ydes6 ay} 0} Gulpiooce sayoujs yo Jaquinu ayy XIy
| oF ‘dn yt ANS PUB JBJEM YSaly YIM YEW 3 GZ
0} dn jy pue UR} O} LIGYSVS 40 @ SZO'2 snod
S40°% = €80'0X SZ
“9.SZ S| ue) yeoIWaYo
Jo Ayoedeo uaYyM UOINIOS %']OA E'g BYEW 0} : BIdWEXd
UB} J2OIWAYO 0} UOI|N|OS ayy
Try aa} pue yde6 0} Guipioo0e Ajisuap uoNNjOs Bly asoOYD Z
oor “a0N1S/99 pBO'O SI dwnd jo Ajoedeg 4
poyjaw uoysalul dwnd ajaubewos9a/y
SFY EID! HR UOL | BHR HY CALA, TIIMOOUd UILVM 40 NOL 1 Hdd O38 SI LIVSYS 40 990)
Hees YENCAAA QOHLIIN NOLLOIPNI TWOHNSHD LIGVSYS
os
09
on
(unmexons)
Be-oie
sayous jo JequNN
\—| og
-37-
23Precautions on handling
Stock should not be, exposed to thé direct rays of sun and kept
in the place where the temperature is under 50 °c.
Do not worry if SASABIT spills on the skin, please wash in
water.
If SASABIT comes into the eyes, Please rinse out and see a
doctor.
When SASABIT spills on the floor or the equipment, wash.or
wipe up by cloths.
Packaging
20 kg polyethylene tank
60 kg polyethylene tank
220 kg iron drum inside polyethylene coating or
polyethylene tankWONG 401271 SS FRESH WATER GENERATOR
SECTIONAL ARRANGEMENT
TO WATER EJECTOR
+ =
Feeb WAIgR bRE—HEATER)
‘CONDENSER’
JACKET COOLING /
‘WATER OUTLET.
JACKET COOLING.
‘WATER INLET
Part WATERIAL
no. | NAME OF PART Focanarion Barba, COmnC
1 | Tor cover STEEL _|$5400 PORE EPO
2_ | EvaPORATOR SwELL | STEEL | S8400] NEOPRENE
3] verector FREESE | ra
a 4 | CONDENSER SHELL |STAINLESS STEEL BUS30-
S| COND, TUBE SHEET | NAVAL BRASS
@ | COoUNG TUBE _[ALUWINUW BRASS|
~ 7_|COND, WATER CHAMBER] CAST IRON URE EPOXY|
@_|_AEATER SHELL STEEL
[3 | HEATING TUBE [ALUMINUM BRass| +s
10_| HEATER TUBE SHEET | NAVAL BRASS
11 | BOFTOm COVER STEEL [58400 | NEOPRENE
12 | _ BAFFLE PLATE STEEL [38400
13 FORROSION PLATE/BAR| ZINC OR IRON [20/Fe L
MESH SEPARATOR _| STAINLESS STEEL SUS304 ieee
le SASAKURA ENGINEERING CO.,LTD. el
—39-Ria
C2
2
110) (520)(305) (301
158)
PHENO 10078 BRON FRESH WATER GENERATOR
: [DISTILLATE PUMP]
124 |
IMPELLER WASHER
[STAINLESS STEEL BUS3O:
158
COUPLING SET SCREW
Cr=Mo STEEL_BOMA3:
301
COUPLING
cASTIRON _|FC200
(03) (001
raat WATERAL Jovan] PART] WATERTAL Journ]
No. | NAME OF PART NOMINATION Byveoy-TITY} NG. eacuae NOMINATION _Bymsou-TITY|
Dor) CASS CASTIRON [F200] 1_|[ 305] CUPREREETROT[-eowceo Steet |55400|3 SET]
003] _MPELLER | PHOS. BRONZE | PEC2| 1 [404] PUMPFRAE | _CASTIRON [FC200| 1
20-1 CASING RING eronze | acs | 1
20-4 CASING RING BRONZE Bc3 | 1 |[520] MECHANICAL SEAL | EAS60-25(SP)| -_ [1 SET
Ti] sharT____[Stanuess sree fusca) 1
TOS] wPELLER KEY [STAINLESS STEEL Puseaod 1
10] RING museer | ne | 1
120 | _wPELLER nT [STAINLESS STEEL BuSSod 1
1
1
1
SASAKURA ENGINEERING CO.,LTD.
—4D-337 8% ware | .wa78x | Konus waa] weeveor | set 2 3 m Es >
aatino | aarm fastino | sai
omgvau
aunssaug| ustan 3univuaawai|aunivusanal walva
aunssaua “a1Ni| “ssaug auras | astovavo | UaivM uaive ¥3S Ons 1003, ON 11009" 43x3vr|
Ausariza | woidara| waivm | wanovA saway
awag "1810 waive) “osss | “Sans FFSRRIETES! waswaonos warvan | tans fawiuprval:
‘ON TH "ON GaN w BdAL
GuvAd INS
SAVN JIMS,
i3aHs vivo
HOLVUSN3O WSLVM HS3HS VENNVSVS
41
26SASAKURA ENGINEERING CO.,LTD.
6-45 Takeshima 4-Chome, Nishiyodogawa-ku,
OSAKA JAPAN
MAKER’ S
CERTIFICATE
No, C-95027 Date. February 23rd 1995
Sasakura Engineering Co., Ltd. Onoda Works.
Ohama Onoda City Yamaguchi Pref. Japan
Customer : Daewoo Shipbuilding & Heavy Machinery Ltd.
Intended : Ship No. 1094
Job No. : 014-7455
This is to certify that the SASAKURA FRESH WATER GENERATOR
(MODEL :KE25)
have been inspected, tested in accordance with specification and the
maker's standard.
INSPECTION & TEST RESULTS
1st Hydrostatic test
Evaporator shell.
Cover of Condenser...
2nd Hydrostatic test
Condenser Shell .. soorereseee 1.5)
Heat Exchanger She] 1...
Final inspection
Dimension and Appearance inspection —
Air Leak test after assembly... 0.6
Conditions of Fittings & Accessories———
Conditions of Spares & Tools.
Z-
c Qo. [Fact
Manager of Inspection & Testing Section. Inspéctor of SASAKURA ENG.CO..LTD-
Pa—
TEST RECORD OF puscror pump
FoR: DAEWOO S.1094
SASAKURA ENGINEERING lospacted by
co., LTD.
nw
te | [O0HC-B.M 15 kW |Freaveney | 60) Ha
Sevoets | G0 Th 440 V c.
[Total heod | m A TALYO
esis 3500 rom 3460 roa" | GT109a
es ( Taran ad 7 aa a
: ‘eon eight ttciner
+l tne pa bate | Secon rod al cone
SL meando | gy [eT ato ly | n w [x
T_T O01 8.0 1 ee 6.731 0
z To] 4A 67.0 bed 5.48 * 180 11:02/49.5)
ae Se aaa
toe x : ates : 1471619 |
=] P1194 T8480 [35.07 30 8 28°5 4.291604
o i |
[ey T
o i
tame Tom [veneer
1. Consimous runing test wos corred out Sire [ Gad 15 | Seif goviy
10. [eeceama aa Worst PPD
2 pny mea expe sie BVA)
90°Triangular Weir Tank
2
RPM
Capacity (mr) Q
D} tewoww wachwert wows, ur