CHILLER SELECTION
User Igor Spirov (Prima Engineering) Date 13.12.2020
Reference: Berovo
SELECTION
Family EasyPack HT65
THAETY 269-296 HT65
Model THAETY 296 HT65 ASP1
Webcode EAS01 (EAS11)
The images are for reference purposes only and may not represent exactly the models or the equipment subject of this document.
The cer ed standard performances and the cer ed so ware tool version can be veri ed in www.eurovent-cer ca on.com
CONSTRUCTION FEATURES
Heat pumps for hot water at high temperature reversible on cooling cycle with evapora on / condensa on and air axial fans.
Units equipped with herme c Scroll compressors and refrigerant R410A.
T - High temperature/e ciency version
ASP1 - Installa on with pump and storage tank. (230 l)
HT65 - Produc on of hot water up to 65°C
POWER SUPPLY: 400V/3PH+N/50HZ
TYPE OF COIL: BRA-COPPER/ALLUMINIUM COIL
CONDENSING CONTROL: FI10-CONDENSING CONTROL
FINISH ELECTRICAL BOX: TQE - RAIN PROT.EL.BOX
PRESSURE VISUALISATION DISPLAY: SPS-HIGH-LOW PRESSURE DISPLAY
º Load-bearing structure and panels in galvanised and RAL 9018 painted sheet metal; galvanised steel sheet metal base
º The structure consists of two sec ons:
• technical compartment that houses the compressors, the electrical panel and the main components of the cooling circuit
• aeraulic circuit dedicated to housing the heat exchanger coils and electric fans
º Herme c, Scroll-type rotary compressors complete with internal circuit breaker protec on and crankcase resistance automa cally ac vated when
the unit stops (as long as the unit is powered)
º Adequately insulated, braze-welded plate water side heat exchange made of stainless steel
º Air side exchanger composed of coil with copper pipes and aluminium ns
º Electric helical fans with external rotor, supplied with internal circuit breaker protec on and complete with protec on mesh
º Propor onal electronic device (FI10) for pressure and con nuous adjustment of the fan rota on speed, down to a minimum outdoor air
temperature of -10°C when opera ng as a chiller, and up to a maximum outdoor air temperature of 40°C when opera ng as a heat pump
º Victaulic-type hydraulic connec ons
º Di eren al pressure switch that protect the unit from any water ow interrup ons
º Cooling circuit made with annealed copper pipes (EN 12735-1-2) equipped with: dryer lter cartridge, load connec ons, high pressure side
manual reset safety pressure switch, LP and HP pressure transducer, safety valve(s), valve upstream of the lter, liquid indicator, intake line
isola on, thermosta c or electronic expansion valve (op onal), cycle inversion and liquid receiver valve, check valves, compressor intake gas
separator and solenoid valve on the liquid line
º Unit with IP24 protec on ra ng
º Control with Adap veFunc on Plus opera on
º The unit is complete with a charge of R410A refrigerant
ELECTRICAL PANEL
º Electrical panel can be accessed by opening the front panel, in compliance with IEC Standards in force, ed with opening and closing via speci c
tool
º Complete with:
• electrical wiring arranged for power supply 400-3ph+N-50Hz
• auxiliary circuit power supply 230V-1ph+N-50Hz derived from main power supply
• main power supply switch with interlocking safety door isolator
• circuit breaker switch protec ng the compressor, pumps and electric fans
• auxiliary circuit protec on fuse
• compressor, pumps and fans power contactor
• remote machine controls: ON/OFF and summer/winter selector
• remote machine controls: compressor opera ng light and general lock light
Family: EasyPack HT65 - Model: THAETY 296 HT65 ASP1 Software Release: 20201204/20201204
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email: rhoss@rhoss.com - web: http://www.rhoss.com
1/6
CHILLER SELECTION
º Programmable microprocessor electronic board handled by the keyboard inserted in the machine
º This electronic board performs the following func ons:
• regula on and management of the set points for unit outlet water temperature; cycle inversion; safety mer delays; circula ng pump;
compressor and system pump hour-run meter; defrost cycles; electronic an freeze protec on with automa c ac va on when the machine is
switched o ; and the func ons which control the opera on of the individual parts making up the machine
• complete protec on of the unit, possible shutdown and display of all the triggered alarms
• compressor protec on phase sequence monitor
• unit protec on against low or high phase power supply voltage (CMT accessory)
• visual indica on of the programmed set points on the display; of the in/out water temperature via the display; of the condensa on and
evapora on pressures, of the alarms via the display; and of chiller/heat-pump opera ng mode via display
• user interface menu
• automa c pump opera ng me balance (DP1-DP2, ASDP1- ASDP2 installa ons)
• automa c ac va on of the pump in standby in the event of an alarm (DP1-DP2, ASDP1-ASDP2 set ups)
• alarm code and descrip on
• alarm history management (menu protected by factory password)
º In par cular, for every alarm, the following are memorised:
• date and me of interven on
• in/out water temperature values as soon as the alarm was triggered
• the evapora on and condensa on pressure values at the me of the alarm
• alarm delay me from the switch-on of the connected device
• compressor status at the me of the alarm
º Advanced func ons:
• Pump Energy-Saving management
• Hi-Pressure Prevent func on with forced cooling capacity par alisa on for a high outdoor temperature (in summer mode)
• set-up for serial connec on (SS, FTT10, KBE, KBM, KUSB accessory)
• possibility to have a digital input for remote management of double set point (DSP)
• possibility of having a discrete input for produc on of domes c hot water by means of the 3-way diverter valve (VDEV). In this case, there is the
possibility of using a temperature probe instead of the discrete input (refer to the speci c sec on for more details)
• possibility to have an analogue input for the shi ing Set-point (CS) via a 4-20mA remote signal
• management of me bands and opera on parameters with the possibility of daily/weekly func oning programs
• check-up and monitoring of scheduled maintenance status
• computer-assisted unit tes ng
• self-diagnosis with con nuous monitoring of the unit func oning status
• MASTER/SLAVE management logic integrated in single systems (SIR - Sequenziatore Integrato Rhoss - Rhoss Integrated Sequencer) - Refer to the
speci c sec on for more details
º Set-point regula on via the Adap veFunc on Plus with two op ons:
• xed set-point (Precision op on)
• set-point sliding (Economy op on)
Family: EasyPack HT65 - Model: THAETY 296 HT65 ASP1 Software Release: 20201204/20201204
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email: rhoss@rhoss.com - web: http://www.rhoss.com
2/6
CHILLER SELECTION
TECHNICAL DATA - THAETY 296 HT65 ASP1
Design parameters
Cooling Hea ng
External air temperature [°C] 35 -18
External air humidity [%] 50 90
User side exchanger inlet uid temperature [°C] 12 41
User side exchanger outlet uid temperature [°C] 7 45
Al tude [m] 986
Ethylen glycole Ethylen glycole
User side exchanger uid
35% 35%
Fouling factor [m²°C/kW] 0.035 0.035
Performances
At design condi ons: Cooling Hea ng
Capacity (gross) [kW] 87.8 52.9
Absorbed power (gross) [kW] 32.1 27.8
EER (gross) 2.74
COP (gross) 1.9
Capacity (UNI EN 14511/2018) [kW] 88.6 52.1
EER (UNI EN 14511/2018) 2.75
COP (UNI EN 14511/2018) 1.87
At Eurovent condi ons:
ESEER (UNI EN 14511/2018) 4.27
EER 100% (UNI EN 14511/2018) 2.98
EER 75% (UNI EN 14511/2018) 3.81
EER 50% (UNI EN 14511/2018) 4.59
EER 25% (UNI EN 14511/2018) 4.51
Func oning limits
User side exchanger
Flow rate [m³/h] 17.3 12.8
Sta c Pressure [kPa] 80 114
Family: EasyPack HT65 - Model: THAETY 296 HT65 ASP1 Software Release: 20201204/20201204
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email: rhoss@rhoss.com - web: http://www.rhoss.com 3/6
CHILLER SELECTION
Sta c Pressure
Fans
Type: Axial
Fan number 3
Consump on for each [kW] 0.69
Air ow rate [m³/h] 29600
Technical features
Refrigerant: (5) R410A
Amount of refrigerant (6) [kg] 41
Global Warming Poten al (GWP) 2088
Equivalent CO 2 [ton] 85.6
Compressors Scroll
Oil charge [kg] 5.3
Number of compressors 2
Number of indipendent circuits 1
Number of compressor steps 2
Noise
Sound Power level (1) [dBA] 83
Sound Pressure level (10m) (2) [dBA] 51
Sound Pressure level (1m) (2) [dBA] 65
(Performance given without pump)
[Hz] [dB]
63 86
125 86
250 85
500 82
1000 78
2000 69
4000 61
8000 56
Family: EasyPack HT65 - Model: THAETY 296 HT65 ASP1 Software Release: 20201204/20201204
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email: rhoss@rhoss.com - web: http://www.rhoss.com 4/6
CHILLER SELECTION
Electrical data
Total electrical power (3) [kW] 33.1 28.8
Pump nominal power [kW] 1.5
Pump absorbed power [kW] 0.99
Electrical power supply [V-ph-Hz] 400-3-N-50
Auxiliary power supply [V-ph-Hz] 230-1+N-50
Nominal current (4) [A] 58.9
Maximum current [A] 73.8
Star ng current [A] 250.2
Star ng current SFS [A] 165.4
Size and weight
Length [mm] 3250
Height [mm] 1700
Depth [mm] 1210
Weight (6) [kg] 1155
Par al loads
Cooling
Outlet uid temperature °C 7
External air temperature °C 35
Load % 100 90 80 70 60 50 40 30 20 10
Capacity (GROSS VALUE) kW 87.8 79 70.2 61.4 52.7 43.9 35.1 26.3 17.6 8.8
EER (GROSS VALUE) 2.74 2.72 2.8 2.92 3.09 3.14 3.05 2.92 2.69 2.17
Flow rate determined at full load condi on
Hea ng
Outlet uid temperature °C 45
External air temperature °C -18
Load % 100 90 80 70 60 50 40 30 20 10
Capacity (GROSS VALUE) kW 52.9 47.6 42.3 37 31.7 26.4 21.2 15.9 10.6 5.3
COP (GROSS VALUE) 1.9 1.86 1.86 1.86 1.85 1.84 1.79 1.72 1.59 1.3
Flow rate determined at full load condi on
SCOP (EN 14825)
Reference condi ons
Reference hea ng season AVERAGE AVERAGE -
Applica on type LOW MEDIUM -
Applica on temperature [°C] 35 55 -
Tdesign [°C] -10 -10 -
Water ow FIXED FIXED -
Outlet water temperature VARIABLE VARIABLE -
Bivalent temperature [°C] -7 -7 -
Pdesign [kW] 76 75 -
Annual Hea ng Demand Qhe [kWh] 44.004 52.102 -
SCOP net 3.60 2.99 -
SCOP 3.57 2.97 -
Seasonal e ciency (Reg.813/2013 UE) [%] 140% 116% -
E ciency class (Reg.811/2013 UE) - - -
The SCOP values could be di erent from what published in the commercial documenta on. This is possibly due to a di erent unit con gura on and/or to di erent
selected parameters
RHOSS reserves the right to make the changes it deems necessary to improve / update the data at any me and without prior no ce.
Family: EasyPack HT65 - Model: THAETY 296 HT65 ASP1 Software Release: 20201204/20201204
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email: rhoss@rhoss.com - web: http://www.rhoss.com 5/6
CHILLER SELECTION
Note
(1) Standard reference UNI EN-ISO 9614
(2) Standard reference UNI EN-ISO 3744
(3) Total absorbed power (compressors, fans if present and pumps if selected)
(4) Referred to nominal condi ons: Ta: 35°C Tw:12/7°C
(5) Regulated transport ADR UN 2857
(6) The value is indica ve and may be subject to change based on the selected accessories