Mechanical Vibration Transformer
Mechanical Vibration Transformer
Article
Analysis of Winding Vibration Characteristics of
Power Transformers Based on the
Finite-Element Method
Xiaomu Duan 1 , Tong Zhao 1, * , Jinxin Liu 2 , Li Zhang 1 and Liang Zou 1
 1   School of Electrical Engineering, Shandong University, Jinan 250061, China;
     201613055@mail.sdu.edu.cn (X.D.); zhleee@sdu.edu.cn (L.Z.); zouliang@sdu.edu.cn (L.Z.)
 2   State Grid, Jining Power Supply Company, Jining 272000, China; ljxwillingheart@gmail.com
 *   Correspondence: zhaotong@sdu.edu.cn; Tel.: +86-531-8169-6129
                                                                                                  
 Received: 25 August 2018; Accepted: 7 September 2018; Published: 11 September 2018               
 Abstract: The winding is the core component of a transformer, and the technology used to diagnose
 its current state directly affects the operation and maintenance of the transformer. The mechanical
 vibration characteristics of a dry-type transformer winding are studied in this paper. A short-circuit
 test was performed on an SCB10-1000/10 dry-type transformer, and the vibration signal at the
 surface was measured. Based on actual experimental conditions, a vibration-simulation model of
 the transformer was established using COMSOL Multiphysics software. A multiphysics coupling
 simulation of the circuit, magnetic field, and solid mechanics of the transformer was performed on
 this model. The simulation results were compared with measured data to verify the validity of the
 simulation model. The simulation model for a transformer operating under normal conditions was
 then used to develop simulation models of transformer-winding looseness, winding deformation,
 and winding-insulation failure, and the winding fault vibration characteristics were analyzed.
 The results provide a basis for detecting and analyzing the mechanical state of transformer windings.
1. Introduction
     The safety and reliability of power transformers, which are the core pieces of equipment in a
power grid, are important for the reliable operation of the entire power grid [1]. Foreign statistics show
that approximately 2% of transformers that run continuously for more than four years will experience
accidents of varying degrees [2]. The high failure rate of transformers has always affected the safe
and stable operation of the power grid [3], and it is not difficult to find that mechanical faults in
transformer are often due to latent issues upon reviewing historical cases of transformer accidents [4].
Transformer faults generally involve the failure of main components and accessories, with the primary
source of these faults being due to windings and core failures. In China, faults have occurred in
18 transformers in and above the 110 kV class [5]. Of these faults, 10 (55.6%) were caused by winding
issues. From 2006 to 2010, the State Grid Corporation of China (SGCC) compiled statistics on the causes
of faults in 46 transformers, of which 26 (56.5%) were caused by winding deformation [6]. In 2013,
there were five accidents in transformers of the 110 kV class and above belonging to the Guangxi
Power Supply Company of the Southern China Power Grid [7]. Of these, four cases (80%) were caused
by winding deformation.
     The study of electromagnetic vibration in transformers began in the 1920s, mainly by large
power-transformer manufacturers and related research institutions. However, that work was limited
by the technology available at that time, when winding fault simulations were not ideal [8]. Fahnoe H.
studied the forced vibration of a transformer’s vibrating iron core under magnetostriction and
resonance at the harmonic frequency [9]. A substantial amount of simulation of the transformer was
carried out. The modal-resonance frequency of the transformer was analyzed such that the transformer
avoided resonance, but the simulation results were not verified via experimentation [10]. Foster S. L.
and others used finite element numerical analysis to calculate the electromagnetic field and structural
force field of large transformers, and obtained the vibration of the transformer core [11]. By combining
electromagnetic-field theory with the theory of structural mechanics, Yang Qingxin and other scholars
in China established a mathematical model of the electromagnetic vibration of the iron core of a
power transformer [12–14]. The model was used to simulate magnetostriction of silicon steel sheets.
On this basis, the distribution of the sound field around the core was analyzed. These researchers
paid considerable attention to the vibration of the iron core, but the vibration of the windings at
various working conditions was less important to them. Liu Dichen and other scholars established an
electromagnetic mechanical sound field finite-element model of a transformer core and its winding [15].
In ANSYS Workbench, a finite-element model of the transformer winding, iron core, and oil tank were
established. Transient electromagnetic-field analysis was used to obtain the alternating electromagnetic
force of the transformer core and winding under the effect of alternating currents. Noise distribution
was analyzed, but little attention was paid to the spectrum analysis of the windings under various
fault conditions. Ji Shengchang and other scholars discussed in detail the relationship between the
vibration of the winding, the iron core, the load current, and the no-load voltage, and proposed a
method for extracting the characteristics of the vibration signal of the transformer based on wavelet
analysis [16,17]. Through simulation and experimentation, Yu Xiaohui and others discussed the
interaction between the tightening force and the natural frequency of the winding and concluded that
the pretension of the windings can change their natural frequency [18]. A comprehensive analysis of
the research conducted by experts around the world reveals that, although many effective diagnostic
methods based on vibration signals have been proposed, there still exist problems, such as incomplete
simulations of the various types of winding faults and poor diagnostic accuracy.
     In recent years, various nondestructive testing methods for transformer-winding deformation
have been developed, such as the frequency-response analysis method for comparing transformer
frequency-response changes, and vibration analysis method for judging winding state based on
the transformer-vibration signal. The principle of frequency-response analysis is to detect the
amplitude-frequency response characteristics of each winding of the transformer, and compare
the detection results horizontally or vertically. According to the difference of amplitude-frequency
response characteristics, winding faults that may occur in the transformer are comprehensively judged.
In recent years, scholars have paid more and more attention to vibration-detection transformer research.
The vibration-analysis method discriminates the winding state of the transformer by detecting the
vibration signal transmitted to the body surface [19,20]. The principle is to reflect the winding states by
detecting a change in the mechanical characteristics of the winding. The frequency-response method
has many factors that affect the test results, such as the position of the signal source, the length of test
leads, the length of the test instrument grounding wire, the position of the transformer tap changer,
and connection mode. Compared with the frequency-response method, the vibration-analysis method
has fewer factors affecting the test results. The noise of the transformer cooling system will pollute the
vibration signal. When collecting the signal, it should be as far away from the fan group as possible,
or you should take noise-reduction measures. The vibration test results of transformer-winding
deformation are affected by the vibration of the core. Power frequency 150 Hz and 250 Hz components
appear in the frequency spectrum of transformer-vibration signals under a three-phase asymmetric
operation. The severe overvoltage generated in the asymmetric phase increases the amplitude of the
resonant frequency of the core, which interferes with the test results of winding. When a short-circuit
fault occurs, the vibration of the iron core is far less than that of winding, and it can be approximated
that the detected vibration contains only vibration signals of the winding. The frequency-response
Energies 2018, 11, 2404                                                                          3 of 19
method is blackout detection, while the vibration-detection method is live detection [21,22]. It can
continuously monitor transformer-winding deformation and reflect the decline trend of transformer
short-circuit resistance after repeated short-circuit shocks, which reduces the difficulty of online
monitoring and fault diagnosis of the power transformer.
      Because the vibration of the transformer is a complicated process, the interaction between the
magnetic field and the load current, as well as between the magnetostriction of the silicon steel sheet
and the structural change in the transformer, produce changes in the vibration signal in both the
time and frequency domains, thus increasing the difficulty in fault monitoring and diagnosis. In this
paper, the SCB10-1000/10 dry-type transformer is studied in detail from the perspective of simulation
modeling, fault simulation, and feature analysis to obtain state diagnostics on transformer winding via
vibration analysis. Based on the mechanical-vibration characteristics of dry-type transformer windings,
a short-circuit experiment was performed on the SCB10-1000/10 transformer, and the vibration signals
at its surface were measured. A vibration-simulation model of the SCB10-1000/10 transformer was
established using COMSOL Multiphysics 5.3, and the coupling calculations were performed with
regard to the circuit, magnetic field, and solid mechanics of the transformer, among other areas of
physics. By comparing the simulated data to the actual data of the transformer, the accuracy of
the model was proven. Using this model, faults like loosening, deformation, and loss of insulation
from the transformer windings were simulated, and the vibration characteristics of the winding
fault were subsequently analyzed. The model utilizes multiphysical field-coupling simulation of the
electromagnetic solid mechanics of dry transformer windings, which can provide a new basis for the
state simulation and fault diagnosis of transformer windings.
2.1. Vibration-Signal Conduction Process and Winding Electrodynamic Analysis of Dry-Type Transformers
      This paper focuses on dry-type transformers. To understand the mechanism behind the
mechanical vibration of transformer windings, a short-circuit experiment of the SCB10-1000/10
dry-type transformer was conducted, and the vibration signal at the surface was measured.
The vibration of power transformers during operation is complicated and influenced by many factors,
but there are two main phenomena: the vibration caused by the electric force on the winding and the
vibration caused by the Lorentz force and the magnetostrictive force on the silicon steel sheet [23].
Figure 1 shows the conduction process of a vibration wave for a dry-type transformer. The vibration
caused by the winding and the iron core is transferred to the surface of the fixed clamp of the
transformer through the rigid component that connects the two. A dry-type transformer consists of
layer-type windings, which cause vibration from the effect of the electrical power. These windings pass
through the rigid connecting component to the fixed-clamp surface. The iron core of a dry-type
transformer is subjected to magnetostrictive force and the action of the Lorentz force, which is
transmitted to the surface of the fixed clamp of the transformer by a support unit, such as the cushion
block or the fastening bolt [24].
      When the load current of the dry-type transformer is loaded, leakage of the magnetic field occurs
in its vicinity, which produces electrical power and causes mechanical vibration of the transformer
winding. This vibration is transferred through the connecting component to the surface of the
transformer clamp. When the transformer is in a steady state, the load current inside the winding can
be found as follows:
                                             it = I cos ωt                                           (1)
    In Equation (1), the current effective value is presented, where ω represents the current
angular frequency.
Energies 2018, 11, 2404                                                                                       4 of 19
 Energies 2018, 11, x FOR PEER REVIEW                                                                           4 of 19
                           Figure1.1.Dry-type
                          Figure      Dry-typetransformer-vibration
                                                transformer-vibrationtransmission
                                                                       transmissionroute.
                                                                                     route.
      The vibration of the transformer body is mainly caused by core vibration, which, in turn, is caused
        The vibration of the transformer body is mainly caused by core vibration, which, in turn, is
by the magnetostriction of the silicon steel sheet and winding vibration resulting from load current.
  caused by the magnetostriction of the silicon steel sheet and winding vibration resulting from load
The vibration of the core is caused by the magnetostriction of the silicon steel sheet in a strong magnetic
  current. The vibration of the core is caused by the magnetostriction of the silicon steel sheet in a strong
field [25]. The amplitude of the vibration is directly proportional to the square of the excitation voltage,
  magnetic field [25]. The amplitude of the vibration is directly proportional to the square of the
and the fundamental frequency is two times greater than the voltage frequency. The vibration of the
  excitation voltage, and the fundamental frequency is two times greater than the voltage frequency.
winding is caused by the electromagnetic force produced by the current in the winding. The amplitude
  The vibration of the winding is caused by the electromagnetic force produced by the current in the
of the vibration is proportional to the square of the winding current, and the basic frequency is two
  winding. The amplitude of the vibration is proportional to the square of the winding current, and the
times greater than the current frequency. In the short-circuit test of the transformer winding, due
  basic frequency is two times greater than the current frequency. In the short-circuit test of the
to low excitation voltage, the vibration of the winding is far greater than the vibration of the core.
  transformer winding, due to low excitation voltage, the vibration of the winding is far greater than
Therefore, the detected vibration signals can be approximated as containing only the vibration signals
  the vibration of the core. Therefore, the detected vibration signals can be approximated as containing
of the winding.
  only the vibration signals of the winding.
      The leakage of the magnetic field around the winding of the transformer is a function that changes
        The leakage of the magnetic field around the winding of the transformer is a function that
with time. When the winding generates a change in position, the distribution of the leakage of the
  changes with time. When the winding generates a change in position, the distribution of the leakage
magnetic field around the winding also changes [26]. To calculate the force on a single conductor,
  of the magnetic field around the winding also changes [26]. To calculate the force on a single
the discrete magnetic field value is fitted to a continuous distribution function. By the Biot–Savart Law,
  conductor, the discrete magnetic field value is fitted to a continuous distribution function. By the
magnetic flux density B at a certain point on the windings can be expressed as follows:
  Biot–Savart Law, magnetic flux density B at a certain point on the windings can be expressed as
  follows:                                 →       u0
                                                          Z
                                                              dl 0 × r0
                                           Bt =        it                                                     (2)
                                                 4πu0 l 0 dlr'2× r 0
                                                Bt =
      At a given point in space, all quantities except
                                                           it
                                                      4π li' are                                             (2)
                                                                   r 2 constant. Thus, in the calculation of the
                                                               t
static electromagnetic
       At a given point field, the magnetic-flux
                         in space,                 leakage
                                   all quantities except     density
                                                         it are      Bt ofThus,
                                                                constant.  the winding   can be simplified
                                                                                in the calculation          to
                                                                                                   of the static
the following:
  electromagnetic field, the magnetic-flux leakage density Bt of the winding can be simplified to the
                                                 →       →
 following:                                      B t = k I cos ωt                                                 (3)
        →                                                   
where k is the proportionality constant between               kI cos ωt
                                                        Bt =magnetic-flux    density and load current.              (3)
             magnetic-field leakage induced by the load current flowing through the transformer
      The axial
  where kBztis
winding   is    , and
                   the radial  electromagnetic
                       proportionality             force
                                            constant     Fx is induced
                                                       between           by the action
                                                                  magnetic-flux        of the
                                                                                  density  andload
                                                                                                loadcurrent. Similarly,
                                                                                                      current.
the magnetic    leakage   field
       The axial magnetic-field  B   , induced   by  radial induction,   can induce  axial  electromagnetic
                                   xt leakage induced by the load current flowing through the transformer     force Fz
through
  winding theisload
                Bzt, current.
                     and radial Theelectromagnetic
                                       axial force and radial
                                                         force force
                                                                Fx is of the conductor
                                                                       induced   by the can   be calculated
                                                                                         action   of the loadfrom  the
                                                                                                               current.
electric-force  equation    as follows:
  Similarly, the magnetic leakage field Bxt, induced by radial induction, can induce axial
  electromagnetic force Fz through the loadFcurrent.   x = it BztThe
                                                                  2πRaxial force and radial force of the conductor
                                                                                                                    (4)
  can be calculated from the electric-force equation  Fz = it Bas
                                                               xt 2πR
                                                                   follows:
                                                     F x = it B zt 2π R
                                                                                                                  (4)
                                                     F z = it B xt 2π R
Energies 2018, 11, 2404                                                                                     5 of 19
   By vector calculation, the axial and radial electric forces are integrated to simplify the electric
power of the winding:                    p
                                     F = Fx2 + Fz2 = it Bt 2πR
                                    = I cos ωt · kI cos ωt · 2πR                                   (5)
                                     = 2πRkI 2 ( 21 + 12 cos 2ωt)
where it is the load current in the winding, ω represents the angular frequency of the power, and R
represents the transformer-winding radius. Equation (5) shows that the magnitude of the electric
force on the transformer winding is proportional to the square of the load current flowing through
the transformer winding, and the fundamental frequency of the vibration signal is twice the power
frequency of the power grid.
                             (a)                                                       (b)
                                               vibration-acceleration sensor;
                     Figure 2. (a) Position of vibration-acceleration sensor; (b)
                                                                              (b) field
                                                                                  field experiment.
                                                                                        experiment.
    When the transformer is short-circuit tested, the secondary low-voltage side is short-circuited,
and a three-phase voltage is applied to the primary high-voltage side such that the load current in the
winding attains its rated value. The vibration signals were measured using a vibration acceleration
sensor (YD70C) (Xieli Science and Technology, Qinhuangdao, China), a charge amplifier (DHF-10),
and a Tek oscilloscope.
Energies 2018, 11, x FOR PEER REVIEW                                                                   6 of 19
                                                     U = a × S1 × S 2                                    (6)
Energies 2018, 11, 2404                                                                                6 of 19
     The sensitivity S1 of the vibration acceleration sensor was 2 pC/ms−2, and the sensitivity S2 of the
charge amplifier was 656 V/pC. The mechanical-vibration-signal diagram in Figure 3 can be obtained
via transformation.
              Table 1. Main technical parameters of the SCB10-1000/10 dry-type transformer.
     Figure 3 shows a set of typical mechanical-vibration signals measured during the experiment.
The ordinate axis in this picture represents vibration acceleration a. The relationship between vibration
acceleration a and output voltage U of the charge amplifier is as follows:
                          (a)                                                  (b)
                                             U = a × S1 × S2                                           (6)
                      Figure 2. (a) Position of vibration-acceleration sensor; (b) field experiment.
                                Figure 3.
                                Figure 3. A set of typical mechanical-vibration
                                                           mechanical-vibration signals.
                                                                                signals.
      The sensitivity S1 of the vibration acceleration sensor was 2 pC/ms −2 , and the sensitivity S of the
3. Multiphysical    Field-Coupling   Model   for Winding   Vibration of Dry-Type    Transformer 2
charge amplifier was 656 V/pC. The mechanical-vibration-signal diagram in Figure 3 can be obtained
      In this paper, COMSOL Multiphysics software was used to simulate the vibration of the SCB10-
via transformation.
1000/10 dry-type transformer winding, and coupling simulation analysis of the magnetic field and
theMultiphysical
3.   solid mechanics   was performed.
                   Field-Coupling    Model for Winding Vibration of Dry-Type Transformer
      In this paper,
3.1. Establishment  andCOMSOL      Multiphysics
                         Mesh Generation          software was used
                                         of a Vibration-Simulation     tofor
                                                                   Model   simulate  the Transformer
                                                                             a Dry-Type   vibration of the
SCB10-1000/10 dry-type transformer winding, and coupling simulation analysis of the magnetic
      The the
field and  structure  of the transformer
               solid mechanics            is complex and includes a variety of components such as the
                                 was performed.
winding, iron core, and cooling device. For the purpose of the simulation, the transformer is
simplified
3.1.         and treated
     Establishment         as Generation
                    and Mesh   an ideal model    in which the internal
                                         of a Vibration-Simulation       cooling
                                                                   Model for      device
                                                                             a Dry-Type    and supporting
                                                                                        Transformer
fastening components are neglected. The finite-element geometric model was set up based on the
      The structure of the transformer is complex and includes a variety of components such as
actual structural parameters of the SCB10-1000/10 dry-type transformer (Xuzhou Debon Electric
the winding, iron core, and cooling device. For the purpose of the simulation, the transformer
Equipment Co., Ltd., Xuzhou, China), and a fixed constraint was applied at both ends of the winding
is simplified and treated as an ideal model in which the internal cooling device and supporting
to simulate clamping. To simulate the electrical insulation of the actual transformer, three-phase high-
fastening components are neglected. The finite-element geometric model was set up based on the
and low-voltage winding turns and layers were used, which allowed the electromagnetic field to be
actual structural parameters of the SCB10-1000/10 dry-type transformer (Xuzhou Debon Electric
solved. The solid mechanics model was set up as a fully coupled solution to understand the
Equipment Co., Ltd., Xuzhou, China), and a fixed constraint was applied at both ends of the winding
connection between the differential equation of motion and the differential equation of the
to simulate clamping. To simulate the electrical insulation of the actual transformer, three-phase high-
electromagnetic field. The simulation model is shown in Figure 4a. To improve efficiency, the
and low-voltage winding turns and layers were used, which allowed the electromagnetic field to be
solved. The solid mechanics model was set up as a fully coupled solution to understand the connection
between the differential equation of motion and the differential equation of the electromagnetic field.
Energies 2018, 11, 2404                                                                                             7 of 19
Energies 2018,
Energies 2018, 11,
               11, xx FOR
                      FOR PEER
                          PEER REVIEW
                               REVIEW                                                                                77 of
                                                                                                                        of 19
                                                                                                                           19
The simulation model is shown in Figure 4a. To improve efficiency, the geometric transformer model
was  simplified
geometric
geometric       by considering
           transformer
           transformer model    it symmetric.
                        model was
                               was    simplifiedFigure
                                     simplified        4b illustrates
                                                 by considering
                                                 by considering          the simplified
                                                                  itit symmetric.
                                                                       symmetric.       geometric
                                                                                   Figure
                                                                                   Figure           modelthe
                                                                                           4b illustrates
                                                                                          4b  illustrates  of
                                                                                                          the
the body. geometric
simplified
simplified geometric model
                      model of
                            of the
                               the body.
                                     body.
                               (a)
                               (a)                                                        (b)
                                                                                          (b)
                  Figure 4.
                  Figure    (a) Integral
                         4. (a) Integral model
                                         model of
                                               of transformer;
                                                  transformer; (b)
                                                               (b) simplified          transformer.
                                                                   simplified model of transformer.
     The geometric
     The  geometricmodel
          geometric   modelof
                      model    ofofthe
                                     thetransformer
                                   the      transformer
                                         transformer     is is
                                                        is     meshed
                                                             meshed
                                                            meshed    byby
                                                                      by    means
                                                                         means
                                                                         means    of aaof
                                                                                  of       a free
                                                                                        free
                                                                                        free       tetrahedron
                                                                                              tetrahedron
                                                                                              tetrahedron         network,
                                                                                                              network,
                                                                                                             network,   and
                                                                                                                       and
and
the  the mesh
the mesh
    mesh  modelmodel
           model  shown
                 shown  shown
                           in      in Figure
                           in Figure
                               Figure    5a   can5a
                                         5a can   becan
                                                  be      be obtained.
                                                     obtained.
                                                     obtained.           Thequality
                                                                  The mesh
                                                                  The  mesh    mesh quality
                                                                              quality    is shown
                                                                                        is  shown is in
                                                                                                      shown
                                                                                                     in       in5b,
                                                                                                         Figure
                                                                                                        Figure   Figure
                                                                                                                5b,      5b,
                                                                                                                    and the
                                                                                                                    and  the
and  the
closer   closer
       the valuethe
                 is  value
                    to 1, the is to
                                higher1,  the
                                           the higher
                                               mesh     the
                                                      quality mesh
                                                                is.  quality
                                                                    The       is.
                                                                        winding    The
                                                                                    and   winding
                                                                                          core        and
                                                                                                structural
closer the value is to 1, the higher the mesh quality is. The winding and core structural parameters of     core structural
                                                                                                             parameters   of
parameters  of the
the SCB10-1000/10
the                 SCB10-1000/10
    SCB10-1000/10 dry-type
                     dry-type transformer  dry-type
                                  transformer are    transformer
                                                   are shown
                                                       shown in      are shown
                                                                 in Tables
                                                                    Tables 22 and  in
                                                                              and 3.3. Tables   2 and   3.
                               (a)
                               (a)                                                        (b)
                                                                                          (b)
         Figure 5.
         Figure
         Figure 5. (a)
                   (a) Mesh-generation results
                   (a) Mesh-generation
                       Mesh-generation results of
                                       results of geometric
                                                  geometric model;
                                                            model; (b)
                                                                   (b) quality
                                                                       quality diagram
                                                                               diagram of
                                                                                       of grid
                                                                                          grid division.
                                                                                               division.
                Table
                Table 2.Main
                Table2.
                      2. Mainparameters
                         Main parametersof
                              parameters ofthe
                                         of theSCB10-1000/10
                                            the               dry-type
                                                SCB10-1000/10 dry-type
                                                SCB10-1000/10          transformer
                                                              dry-type transformer coil
                                                                       transformer coil structure.
                                                                                   coil structure.
                                                                                        structure.
       Coil               Parameter Type         Size Size
                                                      (mm)            Coil            Parameter Type          Size (mm)
         Coil               Parameter    Type        Size          Coil         Parameter    Type     Size (mm)
         Coil               Parameter
                          Internal       Type
                                   diameter         286            Coil         Parameter
                                                                                    Internal Type
                                                                                             diameter Size (mm)
                                                                                                            252
                                                     (mm)
                                                    (mm)
                          External diameter         369                            External diameter             280
  High pressure
                            Internal
                            Internal  diameter
                               Heightdiameter
                                                      286
                                                      286
                                                    405
                                                                              Internal diameter
                                                                 Low pressure Internal  diameter
                                                                                        Height
                                                                                                             252446
                                                                                                             252
                            External
                            External
                            Turn      diameter
                                      diameter
                                 number               369
                                                      369
                                                   1125                       External
                                                                              External  diameter
                                                                                        diameter
                                                                                     Turn number             28045
                                                                                                             280
                                                                   Low
                                                                   Low
    High pressure
    High pressure               Type
                                  Height
                                  Height         Layer405
                                                       type
                                                      405                                Type
                                                                                    Height
                                                                                    Height                   Layer
                                                                                                             446 type
                                                                                                             446
                                                                pressure
                                                                pressure
                              Turn number
                              Turn number           1125
                                                   1125                        Turn number
                                                                              Turn   number                   45
                                                                                                              45
                                  Type
                               Table
                                 Type            Layer type
                                     3. Main parameters
                                                 Layer type                         Type
                                                        of the transformer core structure.
                                                                                   Type                   Layer type
                                                                                                          Layer  type
3.2.
 3.2.Simulation
      SimulationModel
                 Modelofof
                        ofElectromagnetic
                           ElectromagneticField
                                           Field
 3.2. Simulation Model     Electromagnetic Field
      Figure
       Figure 666shows
                   shows   the circuit
                                circuit diagramofofthe  thetransformer.
                                                             transformer. In In  the  diagram,    an AC    voltage  source
       Figure       showsthethe circuitdiagram
                                         diagram of the       transformer.    the  diagram,
                                                                               In the         an AC
                                                                                       diagram,    an voltage  source
                                                                                                       AC voltage      with
                                                                                                                     source
with
  a 50 a
       Hz50  Hz   frequency
            frequency    was   was  applied
                                applied  to theto  the  three-phase
                                                  three-phase          high-voltage
                                                                  high-voltage     side,side,
                                                                                          and and
                                                                                               the  the  low-voltage
                                                                                                    low-voltage   side side
                                                                                                                        was
  with a 50 Hz frequency was applied to the three-phase high-voltage side, and the low-voltage side
was   short-circuited.
  short-circuited.       A   50
                       A 50AHz  Hz  AC
                                 ACAC   voltage
                                      voltage      to
                                                to to the
                                                    thethe rated
                                                         rated    current
                                                                 current   was   applied   to the high-voltage   winding
  was  short-circuited.       50 Hz      voltage            rated  currentwas
                                                                            wasapplied
                                                                                  appliedtotothe
                                                                                               thehigh-voltage
                                                                                                   high-voltage winding
by an    external voltage source. The   Thethree-phase
                                              three-phaseinduction
                                                               inductioncurrent
                                                                           currentof    the low-voltage winding was
  by an external voltage source. The          three-phase      induction   current    of the low-voltage winding was
obtained
  obtainedby byelectromagnetic-coupling
                 electromagnetic-couplingcalculation,
                                                 calculation,as  asshown
                                                                    shownin inFigure
                                                                                Figure7.7.AsAsaaresult,
                                                                                                 result,the
                                                                                                          theamplitude
                                                                                                              amplitudeofof
the three-phase induction current of         the   low-voltage    winding    was   2041   A, and  its effective value was
  the three-phase induction current of the low-voltage winding was 2041 A, and its effective value was
1443.38
 1443.38 A. The simulation results are consistent with the rated current of the transformer,as
          A.   The   simulation   results are  consistent    with   the rated   current   of the transformer,    asshown
                                                                                                                     shown
ininTable
     Table1.1.
                                      power
                                       power
                                      supply
                                       supply high voltage
                                               high voltage           low voltage
                                                                       low voltage
                                                winding
                                        AC
AC
                                                 winding                winding
                                                                         winding
                                                  Resistor 1              Resistor 2
                                                   Resistor 1              Resistor 2
                                  Transformerlow-voltage
                       Figure7.7.Transformer
                      Figure                  low-voltagecoil
                                                          coilthree-phase
                                                               three-phaseinduction
                                                                           inductioncurrent.
                                                                                     current.
                       Figure 7. Transformer low-voltage coil three-phase induction current.
       The current obtained from the circuit module is used as the excitation source of the magnetic-field
      The current obtained from the circuit module is used as the excitation source of the magnetic-
       The
 model, andcurrent obtained
              current densityfrom
                              J wasthe circuitinto
                                    brought    module    is used as thedifferential
                                                    the magnetic-field  excitation source  of as
                                                                                    equation  thefollows:
                                                                                                   magnetic-
field model, and current density J was brought into the magnetic-field differential equation as
 field model, and current density J was brought into the magnetic-field differential equation as
follows:
 follows:                                    µ0−1 µr−1 ∇2 A = J e                                         (7)
                                                            −1 −1 2   e
                                                  μμ0−1μμr −∇
                                                            1 2A = J e
                                                                    = J space and has a value of 4π *10−7 H/m,(7)
                                                     0 r ∇of
       In Equation (7), µ0 represents the permeability           Afree                                            (7)
                                                                                                                  R is
  the relative permeability,  A  is the vector magnetic       potential, and J e is the current density. Additionally,
      In Equation (7), μ0 represents the permeability of free space and has a value of 4π *10 −7H/m, R is −7
       In Equation (7), μ0 represents the permeability of free space and has a value of 4π *10 H/m, R is
  the relative
the   followingpermeability,
                 relationship exists
                                 A is inthe
                                          thevector
                                              electromagnetic-field       model:and Je is the current density.
                                                        magnetic potential,
 the relative permeability, A is the vector magnetic potential, and Je is the current density.
Additionally, the following relationship exists in the electromagnetic-field model:
 Additionally, the following relationshipBexists = µ0 µinr H the=electromagnetic-field
                                                                   ∇×A                     model:                  (8)
                                                B = μ0 μr H = ∇ × A                                              (8)
                                                 B = μ0 μr H = ∇ × A                                              (8)
 where B represents the magnetic-flux density, and H represents the magnetic-field intensity. Figure 8
where B represents the magnetic-flux density, and H represents the magnetic-field intensity. Figure
 where
  shows B   represents
          the H–B curve theofmagnetic-flux
                             the transformer  density,
                                                when and        H represents
                                                          it is in operation. the
                                                                                Themagnetic-field
                                                                                     curve in Figureintensity. Figure
                                                                                                      8 also provides
8 shows the H–B curve of the transformer when it is in operation. The curve in Figure 8 also provides
 8information
    shows the H–B    curve  of the  transformer   when     it is in operation.   The  curve in Figure 8 also
                on the material properties of the dry-type transformer core, which agrees with the actual    provides
information on the material properties of the dry-type transformer core, which agrees with the actual
 information    on the material
  material properties             properties of the dry-type transformer core, which agrees with the actual
                       of the transformer.
material properties of the transformer.
 material   properties  of the transformer.
       The magnetic-flux density distribution around the winding and the core of the dry-type
      The magnetic-flux density distribution around the winding and the core of the dry-type
       The magnetic-flux
  transformer                 density distribution
                during a short-circuit                   around
                                         test was obtained       by the  winding
                                                                     coupling        and the core of themodel.
                                                                               the electromagnetic-field     dry-type
transformer during a short-circuit test was obtained by coupling the electromagnetic-field model.
 transformer during a short-circuit test was obtained by coupling the electromagnetic-field model.
      As seen from Figure 9, the maximum flux-leakage density of the dry-type transformer winding
was 0.08 T, and the maximum flux density of the core was 1.75 T. The results of the simulation are in
line with the output parameters of the SCB10-1000/10 dry-type transformer. The results verify the
Energies 2018, 11, x FOR PEER REVIEW                                                            9 of 19
correctness
Energies        of2404
         2018, 11,  the model, demonstrating that the model can be further used for the simulation   of
                                                                                               9 of 19
various faults in the windings.
       As seen from Figure 9, the maximum flux-leakage density of the dry-type transformer winding
was 0.08 T, and the maximum flux density of the core was 1.75 T. The results of the simulation are in
line with the output parameters of the SCB10-1000/10 dry-type transformer. The results verify the
correctness of the model, demonstrating that the model can be further used for the simulation of
various faults in the windings.
                                                         Figure 8.
                                                         Figure 8. H–B
                                                                   H–B curve.
                                                                       curve.
      As seen from Figure 9, the maximum flux-leakage density of the dry-type transformer winding
was 0.08 T, and the maximum flux density of the core was 1.75 T. The results of the simulation are
in line with the output parameters of the SCB10-1000/10 dry-type transformer. The results verify
                                         Figure 8. H–B curve.
the correctness of the model, demonstrating that the model can be further used for the simulation of
various faults in the windings.
                                         (a)                                                   (b)
       Figure 9. (a) Flux-density distribution of the transformer winding; (b) Flux-density distribution of the
       transformer iron core.
                                                       2
                                            l Mi ddt2z + Ci dz
                                                            dt + k i z                                      (10)
                                            = 21 BI 2 + 12 BI 2 cos 2ωt + Mi g
     To converge to a solution, it is necessary to impose fixed constraints on both ends of the
transformer winding.
     In Equation (10), mass matrix Mi , damping coefficient Ci , and stiffness coefficient ki are all constant,
which makes it a constant coefficient differential equation. The solution of the equation is composed of
the general solution and the special solution. For the homogeneous part,
                                                           d2 z     dz
                                               Mi               + Ci + k i z = 0                            (11)
                                                           dt2      dt
the general solution is as follows:
                                                                     Ct
                                                                   − 2Mi
                                               z0 = Ye                     i    sin(v0 t + θ )              (12)
     In Equation (12), Y and θ are constants whose values are determined by the initial conditions,
and v0 represents the natural frequency of the vibration of the transformer winding, which is expressed
as follows:                                   s
                                                  Ki      C 2
                                       v0 =          −( i )                                         (13)
                                                 Mi      2Mi
      There are two special solutions for Equation (10):
                                                             0.5BI 2 + Mi g
                                               z1 =                         =D                              (14)
                                                                   Ki
                                                   z2 = G cos(2ωt + ψ)                                      (15)
                                            BI 2
                             G=   q
                                                   2
                                                                     ;
      In the equation:             (Ki −4Mi ω 2 ) +4Ci2 ω 2              .
                               tan ψ = − K −2C    iω
                                                     2
                                            i 4Mi ω
    The total displacement of the transformer winding at any time can be expressed as follows in
Equation (16):
                                                            Ct
                                                       − 2Mi
                          z = z0 + z1 + z2 = Ye                i   sin(v0 t + θ ) + D + G cos(2ωt + ψ)      (16)
where t, the total displacement of the winding, and the displacement velocity are zero. Integral
constants Y and θ can then be obtained.
     By quadratic derivation of the total displacement equation of the transformer winding,
the vibration acceleration a of the transformer winding at any time t can be obtained as in Equation (17):
                                                                               Ci t
                                             a = −v02 Ye− 2M sin(v0 t + θ )                                 (17)
                                             −4ω 2 G sin(2ωt + ψ)
     From the solution above, it can be seen that the vibration characteristics of a given transformer’s
windings are mainly related to the elastic coefficient and the winding geometry, that is, when elastic
coefficient K and the geometric structure of the transformer winding are changed, the vibration
acceleration of the transformer-winding surface changes accordingly. Table 4 shows the main material
properties of the winding and the core in the solid mechanics model [29].
Energies 2018, 11, x FOR PEER REVIEW                                                                                        11 of 19
acceleration of the transformer-winding surface changes accordingly. Table 4 shows the main
material properties of the winding and the core in the solid mechanics model [29].
       Energies 2018, 11, 2404                                                                                   11 of 19
                          Table 4. The main material properties of the solid mechanics model.
     The amplitude and axial forces on the transformer winding are obtained through a simulation
of the solidThe  amplitude as
              mechanics,      anddemonstrated
                                   axial forces on the  transformer
                                                    in Figure          winding
                                                                  10. The       are obtained
                                                                           legend   shows thethrough  a simulation
                                                                                                magnitude           of
                                                                                                               of stress, and
       the solid mechanics,   as demonstrated    in  Figure   10. The legend  shows  the magnitude
the red arrows indicate the direction of force. As seen in Figure 10a, the external high-voltage    of stress, and the
       red arrows indicate the direction of force. As seen in Figure 10a, the external high-voltage windings
windings receive outward traction, while the inner low-voltage windings are pushed inward; the
       receive outward traction, while the inner low-voltage windings are pushed inward; the force of the
force of  thewinding
       outer  outer winding       is obviously
                        is obviously               lower
                                      lower than that        than
                                                        of the     that
                                                               inner     of theFigure
                                                                     winding.    inner10b
                                                                                        winding.   Figure
                                                                                          shows that the two10b  shows
                                                                                                               ends of    that
the twotheends   of the winding
           transformer    transformer      winding
                                    are subjected  to are
                                                      inwardsubjected   topressure.
                                                                extrusion   inward Therefore,
                                                                                      extrusionthe
                                                                                                 pressure.    Therefore, the
                                                                                                   above simulation
above results
        simulation    results
               are in line  withare
                                 the in  lineforce
                                      actual  withonthetheactual   force windings.
                                                            transformer   on the transformer windings.
(a)
                                                               (b)
      FigureFigure
             10. (a)10. (a) Radial-stress
                     Radial-stress        distributiondiagram
                                      distribution     diagram of
                                                               of transformer
                                                                   transformerwindings; (b) axial-stress
                                                                                windings;                distribution
                                                                                            (b) axial-stress    distribution
            diagram   of transformer
      diagram of transformer winding. winding.
             To further verify the accuracy of the above model, the vibration signals measured by the
     To  further verify
      transformer          the test
                   short-circuit accuracy   of the above
                                    were compared    with themodel,
                                                             vibrationthe  vibration
                                                                       signals from thesignals   measured
                                                                                         simulation. Figure 11 by the
transformer
      shows short-circuit
              the layout of test   were compared
                              the actual              withmeasurement
                                         vibration-signal   the vibrationpoints
                                                                           signalsandfrom   the simulation. Figure
                                                                                       the simulation-model
11 shows   the layout
      measurement        of the
                      points. Theactual  vibration-signal
                                  locations in the simulationmeasurement      points
                                                              model are consistent     and
                                                                                    with  thethe simulation-model
                                                                                              vibration signal
      measured   in the experiment.
measurement points. The locations in the simulation model are consistent with the vibration signal
measured in the experiment.
     Figure 12 shows the calculated results of vibration at the placement of the acceleration vibration
sensor and the measured results. Because the current passing through the winding in the short-circuit
experiment is rated current, the simulation-calculation conditions are close to the actual measurement
conditions. As shown in Figure 12, the simulation results are in good agreement with the measured
 Energies 2018, 11, x FOR PEER REVIEW                                                                                          12 of 19
 results, which further illustrates the validity of the finite-element model and the correctness of the
 calculation
Energies        results.
         2018, 11, 2404  In addition, the vibration waveform of the test point appears in the shape12of the
                                                                                                     of 19
 top cusp, which may be due to the material characteristics [30].
results, which further illustrates the validity of the finite-element model and the correctness of the
calculation results. In addition, the vibration waveform of the test point appears in the shape of the
top cusp, which may be due to the material characteristics [30].
                                      (a)                                                 (b)
       Figure11.
      Figure   11.(a)
                   (a)Experiment
                       Experiment   locations
                                 locations    of measurement
                                           of measurement     points;
                                                          points;       (b) Simulation
                                                                  (b) Simulation        locations
                                                                                 locations        of measurement
                                                                                           of measurement points.
       points.
     Figure 12 shows the calculated results of vibration at the placement of the acceleration vibration
sensor and the measured results. Because the current passing through the winding in the short-circuit
experiment is rated current, the simulation-calculation conditions are close to the actual measurement
conditions. As shown in Figure 12, the simulation results are in good agreement with the measured
results, which further illustrates
                              (a) the validity of the finite-element (b)model and the correctness of the
calculation results. In addition, the vibration waveform of the test point appears in the shape of the
     Figure 11. (a) Experiment locations of measurement points; (b) Simulation locations of measurement
top cusp, which may be due to the material characteristics [30].
       points.
(a) (b)
(a) (b)
(c) (d)
      Figure 14. Axial diagram of the total displacement of windings under various working conditions.
      (a) Normai working; (b) Insulation Shedding; (c) Winding loosing and (d) Winding deformation.
                                     (c)                                           (d)
that the force of the low-voltage coil was greater than that of the high-voltage coil. This result is due
to the opposing directions of current flow along the windings between the high- and low-voltage
sides of the transformer, as well as the mutual exclusion of the electromagnetic force in the radial
direction of the two windings, which is in accordance with the actual force. This result verifies the
 Energies 2018,
accuracy    of 11,
                the2404
                    model.                                                                         14 of 19
(a) (b)
                          (c)                                                     (d)
     Figure
      Figure15.
             15.Amplitude
                 Amplitudedirection
                            directiondiagram of of
                                       diagram  winding   force
                                                    winding     displacement
                                                             force            under
                                                                   displacement      various
                                                                                  under      conditions.
                                                                                         various         (a)
                                                                                                 conditions.
     Normal  working;
     (a) Normal       (b) Insulation
                 working;            Shedding;
                          (b) Insulation        (c) Winding
                                         Shedding;           loosening
                                                    (c) Winding         andand
                                                                 loosening  (d) (d)
                                                                                Winding   deformation.
                                                                                    Winding  deformation.
      Figure
       Figure 16
               14 shows
                   shows athat
                            time-domain    diagram of the
                               the total displacement       vibration-acceleration
                                                       of the   transformer windingssignal
                                                                                        wasatsmallest
                                                                                              measurement
                                                                                                       under
point
 normal 1 under  normal
          conditions,     working
                       while         conditions,
                              the winding   was as well
                                                 more   as intothe
                                                      prone         cases of insulation
                                                                 displacement           shedding,
                                                                                in the event        winding
                                                                                             of a fault. Total
loosening,
 displacementand was
                  winding  deformation.
                      greatest  in the case of winding deformation. The results validate the cumulative
 characteristics of winding mechanical faults, that is, small mechanical faults increase force on the
 winding, which makes it relatively easy for greater mechanical faults to occur. Therefore, considerable
 attention should be paid to the mechanical state of the winding. If a small mechanical failure occurs,
 it should be dealt with in a timely manner; if it is not, it becomes relatively easy for a serious accident
 to occur.
       Figure 15 shows that the total displacement of the low-voltage winding in the inner part of the
 transformer was greater than the displacement of the lateral high-voltage winding, which indicates
 that the force of the low-voltage coil was greater than that of the high-voltage coil. This result is due to
 the opposing directions of current flow along the windings between the high- and low-voltage sides of
                          (a)                                                   (b)
 the transformer, as well as the mutual exclusion of the electromagnetic force in the radial direction
 of the two windings, which is in accordance with the actual force. This result verifies the accuracy of
 the model.
       Figure 16 shows a time-domain diagram of the vibration-acceleration signal at measurement point
 1 under normal working conditions, as well as in the cases of insulation shedding, winding loosening,
 and winding deformation.
       As seen from Figure 16, the vibration signal at measurement point 1 under normal conditions was
 more stable than the vibration signal at the time of failure, and the average amplitude of the vibration
 signal was approximately 0.06 m/s2 . When insulation shedding occurred, the maximum amplitude of
 the vibration-acceleration signal at measurement point 1 was 0.08 m/s2 . When the winding was loose,
 the maximum amplitude of the vibration acceleration signal at measurement point 1 was 0.28 m/s2 .
 When winding deformation occurred, the maximum amplitude of the vibration-acceleration signal at
 measurement point 1 was 0.25 m/s2 . When a winding fault occurred, the amplitude of the vibration
 signal was nonstationary. Moreover, when the winding was loose, and the winding deformation
 failed, the change was more intense. When the transformer windings failed, vibration signals would
                              (c)                                                           (d)
      Figure 15. Amplitude direction diagram of winding force displacement under various conditions. (a)
      Normal
Energies        working;
         2018, 11, 2404  (b) Insulation Shedding; (c) Winding loosening and (d) Winding deformation.                 15 of 19
           As seen from Figure 16, the vibration signal at measurement point 1 under normal conditions
      was more stable than the vibration signal at the time of failure, and the average amplitude of the
      vibration signal was approximately 0.06 m/s2. When insulation shedding occurred, the maximum
      amplitude of the vibration-acceleration signal at measurement point 1 was 0.08 m/s2. When the
      winding was loose, the maximum amplitude of the vibration acceleration signal at measurement
      point 1 was 0.28 m/s2. When winding deformation occurred, the maximum amplitude of the
                            (c)                                                              (d)
      vibration-acceleration signal at measurement point 1 was 0.25 m/s2. When a winding fault occurred,
      the amplitude
     Figure           of the vibration
              16. Time-domain
                  Time-domain           signal
                                  diagram
                                   diagram     ofwas
                                              of     nonstationary. Moreover,
                                                  vibration-acceleration
                                                  vibration-acceleration   signals
                                                                           signals when
                                                                                     at   the winding was
                                                                                     at measurement
                                                                                         measurement     pointloose,
                                                                                                          point      and
                                                                                                                11 under
                                                                                                                   under
      the winding
     various
     various        deformation
               working
               working            failed,
                          conditions:
                          conditions:   (a)the
                                       (a)     change
                                            normal
                                            normal     was more
                                                     working
                                                     working       intense. When
                                                                conditions;
                                                                conditions;  (b)    the transformer
                                                                              (b) insulation
                                                                                  insulation           windings
                                                                                               shedding;
                                                                                               shedding;    (c)   failed,
                                                                                                            (c) winding
      vibration signals
     loosening;           would
                 (d) winding      obviously change. The amplitude of the vibration signal in the fault was
                                deformation.
      higher than the amplitude of the normal vibration signal, and the fluctuation of the signal was
      intense.
     Figure
     As   seen17from
                  presents
                       Figurea spectrum-analysis
                                16, the vibration signaldiagram     of the vibration
                                                               at measurement            signal
                                                                                     point        at measurement
                                                                                             1 under                  point 1,
                                                                                                        normal conditions
whenmore   Figure  17 presents
        the transformer         a spectrum-analysis
                            wasvibration
                                  working signal
                                               under at  diagram
                                                       normal      of the vibration
                                                                 conditions,     asandsignal
                                                                                    wellthe  at
                                                                                           as formeasurement
                                                                                                   the cases     point 1,
                                                                                                                of insulation
was          stable than the                               the time   of failure,              average    amplitude     of the
      when the transformer was working under normal              conditions,   as well  as for  the  cases of insulation
shedding,    winding    loosening,   and    winding    deformation.
vibration signal was approximately 0.06 m/s . When insulation shedding occurred, the maximum
                                                          2
      shedding, winding loosening, and winding deformation.
amplitude of the vibration-acceleration signal at measurement point 1 was 0.08 m/s2. When the
winding was loose, the maximum amplitude of the vibration acceleration signal at measurement
point 1 was 0.28 m/s2. When winding deformation occurred, the maximum amplitude of the
vibration-acceleration signal at measurement point 1 was 0.25 m/s2. When a winding fault occurred,
the amplitude of the vibration signal was nonstationary. Moreover, when the winding was loose, and
the winding deformation failed, the change was more intense. When the transformer windings failed,
vibration signals would obviously change. The amplitude of the vibration signal in the fault was
higher than the amplitude of the normal vibration signal, and the fluctuation of the signal was
intense.                   (a)                                          (b)
     Figure 17 presents a spectrum-analysis diagram of the vibration signal at measurement point 1,
when the transformer was working under normal conditions, as well as for the cases of insulation
shedding, winding loosening, and winding deformation.
                                    (c)                                                  (d)
           Figure
      Figure  17. 17.Spectrum
                       Spectrum diagram
                                 diagramof of
                                            vibration signalsignal
                                               vibration      at measurement  point 1 under
                                                                    at measurement          different
                                                                                        point  1 underworking
                                                                                                         different
           conditions:  (a) normal condition; (b)  insulation  shedding; (c) winding  loosening;
      working conditions: (a) normal condition; (b) insulation shedding; (c) winding loosening;   (d) winding
           deformation.
      (d) winding deformation.
                              (a)                                                           (b)
Energies 2018, 11, 2404                                                                            16 of 19
      As shown in Figure 17, the maximum frequency attained by the vibration-acceleration signal
at transformer measurement point 1 was 100 Hz under normal operating conditions, at which point
the amplitude was 0.05. Signals with frequencies of 50 Hz, 200 Hz, and 300 Hz can also be seen in
this diagram. When insulation was shed, the amplitudes of the 100 Hz, 200 Hz, and 300 Hz signals
increased. When the windings were loose, the maximum amplitude of the signal in the frequency
domain occurred at 200 Hz, and the amplitude of the signal of 300 Hz increased apparently as well.
When winding deformation occurred, the maximum amplitude of the vibration signal occurred at 300
Hz, and the amplitude of the signal spectrum at 200 Hz was greater than the amplitude at 100 Hz.
These results are consistent with the experimental results of transformer faults in Reference [32],
which verifies the accuracy of the model.
      By studying the vibration characteristics of transformer windings, it is known that the
corresponding mechanical vibration will change when the mechanical state of the windings
changes. In order to make the change more intuitive and distinguish the characteristics of
different mechanical states, based on the analysis of transformer-winding vibration characteristics,
some artificial-intelligence algorithms can be used to identify fault features, such as Improved
Variational Mode Decomposition (IVMD)-Weight Divergence, which is a feature-extraction method
presented for vibration signals of transformer windings. In the process of feature extraction,
the mechanical vibration signals of transformer windings in different states are decomposed into
a series of finite-bandwidth intrinsic-mode functions (IMFs) by means of Improved Variational Mode
Decomposition; K-L divergence (K-L) between the IMF component and the original vibration signal is
calculated, and the weighting coefficients are multiplied. Weight divergence is obtained to represent
the time-frequency domain complexity of mechanical-vibration signals of transformer windings
in different states. It can effectively extract the characteristics of a mechanical-vibration signal of
transformer windings [33].
      Many scholars have studied the vibration state of the transformer. Gu Hongxia of Kunming
University of Technology, through the finite-element analysis of winding-loosening faults, showed that
the natural frequency of the four orders in winding-loosening faults and the natural frequency of the
normal state of the winding transfer to a low frequency [34]. The simulation experiment shows that it
can be used. Natural frequency is used to judge the working condition of power-transformer windings.
However, this paper only focuses on the loosening fault of windings, and other faults such as winding
deformation and insulation shedding are not studied. From the point of view of acoustic measurement,
C. Bartoletti extracts the weighted values and proportions of the middle-, low-, and high-frequency
signals from the noise signals for transformer-fault diagnosis [35]. In this paper, the operation state of
the transformer is diagnosed by the sound signal. But the vibration signal is transmitted through air,
and noise reduction is needed to obtain the available vibration signal. The monitoring effect is not as
accurate as the vibration of the transformer itself. Hyun-Mo Ahn has more analysis on the vibration
and stress of short-circuit faults, but less research on the vibration caused by load changes in normal
operation [36]. Ji Shengchang of Xi’an Jiaotong University has done long-term work on the vibration
characteristics of the transformer. The radial vibration of the transformer winding, axial-vibration
characteristics of the pressure plate, and influencing factors were studied [37]. The vibration law and
propagation characteristics of transformer windings were revealed. There is no theoretical calculation
of the radial vibration of the winding, and no research on the change rule of the vibration characteristics
of the typical winding mechanical-fault state, which makes it difficult to judge the actual fault.
      By setting winding looseness, winding deformation, and insulation shedding, and by means of
simulation and experiment, the frequency-spectrum characteristics of winding-vibration signals under
different conditions were analyzed. From the research, it can be seen that the transformer-vibration
model provides a reliable basis for transformer-winding state simulation and fault diagnosis, and can
be used to easily calculate the distribution of the magnetic field and the winding characteristics of the
transformer. Moreover, this model can be used to analyze vibration control during the design of a
transformer, thereby shortening the design cycle. It also provides a theoretical basis and method of
Energies 2018, 11, 2404                                                                                17 of 19
calculation for further analysis and verification of new methods of reducing electromagnetic noise
in transformers.
5. Conclusions
     In this paper, the mechanical-vibration characteristics of transformer windings were studied
theoretically. Changes in the mechanical state of the windings were reflected in their vibration
signals. A simulation model of vibration was established for an SCB10-1000/10 dry-type transformer
winding using COMSOL software, and a multifield-coupling simulation of the circuit, magnetic
field, and solid mechanics was performed. The following conclusions were obtained through
simulation and experimental analysis. By changing the geometry model and power parameters,
similar conclusions can be obtained for other types of dry-type transformers, which can be extended
to the study of winding-vibration characteristics of various types of dry-type power transformers.
For the oil-immersed transformer, the simulation model was greatly changed, so it was necessary to
add an oil-tank wall to the transformer model, replace the medium with insulation oil, and consider
the vibration-signal propagation process in the insulation oil. At the same time, we also studied
the occurrence and propagation of the winding vibration of oil-immersed transformers. Because the
oil-immersed transformer was closed, the vibration-signal sensor could only be mounted on the wall of
the oil tank. When analyzing the signal received by the vibration-signal sensor, we needed to consider
the properties of the different insulating oil. Therefore, the vibration analysis in this paper was limited
to dry-type transformers.
     (1) A short-circuit experiment was performed on an SCB10-1000/10 transformer, which is a
dry-type transformer. Information on the vibration acceleration at the surface of the transformer
was obtained using a vibration-acceleration sensor (YD70C), a charge amplifier (DHF-10), and a Tek
oscilloscope. Vibration-signal analysis showed that, when the secondary winding of the transformer
was short-circuited, the signal was mainly composed of a 100 Hz component and contained relatively
small components at 50 Hz, 200 Hz, and 300 Hz.
     (2) Based on the vibration data obtained from the transformer short-circuit experiment,
a multiphysical field-coupling vibration-simulation model of the dry-type transformer winding is
established using the parameters of the actual transformer. The vibration-acceleration signal was
obtained from actual measurement points, which was then compared to the corresponding points in
the simulation. The similarity between the two exceeded 80%. Therefore, the model can be used to
investigate the vibration of transformer windings and possesses high value in engineering applications.
     (3) Based on the simulation model, for normal working conditions, fault simulations of the
transformer windings were carried out. Specifically, winding loosening, deformation, and insulation
shedding were simulated, and the vibration characteristics of these winding faults were analyzed.
When insulation was shed, the amplitude in the frequency domain at 100 Hz, 200 Hz, and 300 Hz
increased. When the winding was loose, the maximum amplitude in the frequency domain appeared
at 200 Hz, and the amplitude at 300 Hz was also relatively larger. When winding deformation occurred,
the maximum amplitude of the vibration signal occurred at 300 Hz, and the amplitude at 200 Hz
exceeded the amplitude at 100 Hz. The simulation results are consistent with the experimental results,
which verify the accuracy of the fault model. This method can provide a new basis for simulating and
diagnosing transformer-winding faults.
Author Contributions: X.D. and J.L. designed the multiphysics field-coupling model for transformer-winding
vibration, performed the data analysis, and prepared the manuscript. L.Z. (Li Zhang) and L.Z. (Liang Zou)
assisted the project and managed to obtain the transformer-vibration signal. T.Z. led the project and research.
All authors discussed the results and approved the publication.
Funding: This research was supposed by the Key Research and Development project of Shandong Province
(2018GGX104009).
Conflicts of Interest: The authors declare no conflict of interest.
Energies 2018, 11, 2404                                                                                       18 of 19
References
1.    Zhang, F.; Ji, S.; Shi, Y.; Lu, W.; Li, D.; Chen, L. Research on transformer winding vibration and propagation
      characteristics. Trans. China Electrotech. Soc. 2018, 38, 2790–2798.
2.    Ghoneim, S.S.M.; Taha, I.B.M. A New approach of DGA interpretation technique for transformer fault
      diagnosis. Int. J. Electr. Power Energy Syst. 2016, 81, 265–274. [CrossRef]
3.    Wang, J.; Li, D. Accidents and defects analysis of 110 kV and above voltage transformers. Guangxi Electr.
      Power 2014, 37, 63–64.
4.    Wang, Z. Cause analysis to deteriorate of 220 kV power transformer and its counter measure. Inner Mong.
      Electr. Power 2016, 59, 34–41. [CrossRef]
5.    Wang, M. 220 kV power transformer damage analysis and countermeasures 2005 year 110 (66) kV and above
      transformer accident and defect statistical analysis. Power Equip. 2006, 7, 99–102.
6.    Deng, Y. Typical Examples of Transformer Equipment Failure (2006–2010 Years); China Electric Power Press:
      Beijing, China, 2012; pp. 16–23.
7.    Wang, M. Statistic analysis of transformer0 s faults and defects at voltage 110 kV and above. Distrib. Util.
      2007, 24, 1–5.
8.    Report, A.C. Bibliography on transformer noise. Power Appar. Syst. Part III 1954, 73, 1760–1762. [CrossRef]
9.    Fahnoe, H. A Study of sound levels of transformers. Electr. Eng. 2013, 60, 277–282. [CrossRef]
10.   Masti, R.S.; Desmet, W.; Heylen, W.; Leuven, K. On the Influence of Core Laminations upon Power
      Transformer Noise. In Proceedings of the 2004 International Conference on Noise and Vibration Engineering,
      Heverlee, Belgium, 20–22 September 2004.
11.   Foster, S.L.; Reiplinger, E. Charcteristics and control of transformer sound. IEEE Trans. Power Appar. Syst.
      1981, PAS-100, 1072–1077. [CrossRef]
12.   Xu, L.; Liu, X. Study on the Three dimension attenuated model and the algorithm of environmental noise in
      substations. Proc. CSEE 2012, 32, I0024.
13.   Wu, G.; Cheng, S.G.; Huang, L.; Huang, L.; Gao, F. Prediction on noise of 220 kV outdoor substation to
      environmental infection. Noise Vib. Control 2007, 27, 135–137.
14.   Zhu, L.; Yang, Q.; Yan, R.; Zhan, X. Research on vibration and noise of power transformer cores including
      magnetostriction effects. Trans. China Electrotech. Soc. 2013, 28, 1–6.
15.   Hu, J.; Liu, D.; Liao, Q.; Yan, Y.; Liang, S. Analysis of transformer electromagnetic vibration noise based on
      finite element method. Trans. China Electrotech. Soc. 2016, 31, 81–88.
16.   Ji, S.; Li, Y.; Fu, C. Application of on-load current method in monitoring the condition of transformer’s core
      based on the vibration analysis method. Proc. CSEE 2003, 2, 154–158.
17.   Ji, S.C. Vibration Characteristics of Transformer Winding and Core and Its Application in Fault Monitoring; Xi’an
      Jiaotong University: Xi’an, China, 2003.
18.   Yu, X.; Li, Y.; Jing, Y.; Li, H. Calculation and analysis of natural frequency of winding model of transformer.
      Transformer 2010, 47, 5–8.
19.   Zhang, B.; Xu, J.Y.; Chen, J.B.; Li, H.; Lin, X.; Zang, Z. Diagnosis method of winding deformation based on
      power transformer vibration information. High Volt. Eng. 2015, 41, 2341–2349.
20.   Cheng, J.; Li, Y.; Ji, S.; Hao, H. Application of vibration method on monitoring the winding and core condition
      of transformer. High Volt. Eng. 2005, 31, 43–45.
21.   Malewski, R.; Poulin, B. Impulse testing of power transformers using the transfer function method.
      IEEE Trans. Power Deliv. 1988, 3, 476–489. [CrossRef]
22.   Zhu, Y.; Ji, S.; Zhang, F.; Liu, Y.; Dong, H.; Cui, Z.; Wu, W. Vibration mechanism and influence factors in
      power transformers. J. Xi’an Jiaotong Univ. 2015, 49, 115–125.
23.   Zhang, B. The Study on Multi-Information Diagnosis Method of Power Transformer Winding Mechanical State;
      Shenyang University of Technology: Shenyang, China, 2015.
24.   Xie, P.; Rao, Z.; Zhu, Z. Finite element modeling and analysis on transformer windings. J. Vib. Shock 2006,
      25, 134–137.
25.   Xu, J.; Shao, Y.; Jin, Z.; Rao, Z.; Jiang, Y.; Zhou, K. The detection of transformer windings’ deformation based
      on the method of frequency response analysis. Noise Vib. Control 2009, 29, 26–29.
26.   Wan, D.F. Magnetic Theory and Its Application; Huazhong University of Science and Technology Press: Wuhan,
      China, 1996; pp. 56–62.
Energies 2018, 11, 2404                                                                                         19 of 19
27.   Cheng, J.; Ji, S.; Liu, J.; Li, Y. Analysis of the measuring position for on-line monitoring on vibration signal of
      the winding. High Volt. Eng. 2004, 30, 46–48.
28.   Zhang, L.; Zhang, W.; Liu, J.; Zhao, T.; Zou, L.; Wang, X. A New Prediction Model for Transformer Winding
      Hotspot Temperature Fluctuation Based on Fuzzy Information Granulation and an Optimized Wavelet
      Neural Network. Energies 2017, 10, 1998. [CrossRef]
29.   Nagata, T.; Hirai, K.; Iwasaki, S.; Ebisawa, Y. Estimation on On-load Vibration of Transformer Windings.
      In Proceedings of the 2002 IEEE International Conference on Power Engineering Society Winter, New York,
      NY, USA, 27–31 January 2002; pp. 1378–1382.
30.   Wang, F.; Duan, R.; Geng, C.; Qian, G.; Lu, Y. Research of Vibration Characteristics of Power Transformer
      Winding Based on Magnetic-mechanical Coupling Field Theory. Proc. CSEE 2016, 36, 2555–2562.
31.   Wang, X.; Hao, N.; Zhang, G. Simulation study on detection of transformer winding deformation by
      frequency response considering phase characteristic. Transformer 2018, 55, 25–31.
32.   Wang, H.; Wang, N.; Li, T. Axial Nonlinear Vibration of Large Power Transformer Winding.
      Power Syst. Technol. 2000, 24, 42–45.
33.   Liu, J.; Wang, G.; Zhao, T.; Zhang, L. Fault diagnosis of on-load tap-changer based on variational mode
      decomposition and relevance vector machine. Energies 2017, 10, 946. [CrossRef]
34.   Gu, H. Research on the Relationship between Winding Deformation and Vibration Signal of Power Transformer;
      Kunming University of Technology: Kunming, China, 2017.
35.   Bartoletti, C.; Desiderio, M.; Carlo, D.D.; Fazio, G. Vibro-acoustic techniques to diagnose power transformers.
      IEEE Trans. Power Deliv. 2004, 19, 221–229. [CrossRef]
36.   Ahn, H.M.; Oh, Y.H.; Kim, J.K.; Song, J.S.; Hahn, S.C. Experimental verification and finite element analysis of
      short-circuit electromagnetic force for dry-type transformer. IEEE Trans. Magn. 2012, 48, 819–822. [CrossRef]
37.   Ji, S.; Wang, S.; Li, Q.; Li, Y.; Sun, Q. The application of vibration method in monitoring the condition of
      transformer winding. High Volt. Eng. 2002, 28, 13–15.
                          © 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
                          article distributed under the terms and conditions of the Creative Commons Attribution
                          (CC BY) license (http://creativecommons.org/licenses/by/4.0/).