Calculation of Infrastructure Networks Project Name Location Project Categ. Owner Design by Date

This document calculates the infrastructure requirements for a project including water and firefighting networks. It estimates the population at 2840 people based on 568 apartments with 5 people per unit. It then calculates the daily water consumption needs and required water tank capacity. It also calculates the firefighting water requirements based on internal and external firefighting flows and tank sizing. Finally, it specifies the minimum residual pressure requirements for the water and firefighting networks.

Uploaded by

Hgagselim Selim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
102 views4 pages

Calculation of Infrastructure Networks Project Name Location Project Categ. Owner Design by Date

This document calculates the infrastructure requirements for a project including water and firefighting networks. It estimates the population at 2840 people based on 568 apartments with 5 people per unit. It then calculates the daily water consumption needs and required water tank capacity. It also calculates the firefighting water requirements based on internal and external firefighting flows and tank sizing. Finally, it specifies the minimum residual pressure requirements for the water and firefighting networks.

Uploaded by

Hgagselim Selim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

CALCULATION OF INFRASTRUCTURE NETWORKS

Project Name
Location
Project categ.
Owner
Design by
Date
1-CALCULATION OF POPULATION
Item Vakue Unit
NO.OF Apartment 568 Apartment
No.of Cpita/Unit 5 Capita
No.of Population 2840 Capita
No.of Employes 85 Employee
2- CALCULATION OF WATER NETWORKS Vakue Unit
No.of Employess'Water Consumption/Captia 320 L/d
No.of Employess'Water Consumption/Employee 50 L/d
Assume working Hours 16 hr
Qdaily 913 m3/d
Qhourly 1370 m3/d
Q/sec 16 L/sec
3- CALCULATION OF FIREFIGHTING NETWORKS Vakue Unit
Q - internal firefighting 750 gpm
Q - External firefighting 500 gpm
Q FF 1250 gpm
Q FF 79 L/sec
ASSUMING WORKING HOUR 1 hr
Q FF 284 m3

4- CALCULATION OF WATER & FIREFIGHTING TANK Vakue Unit


Required Capacity for Water /time 913 m3
time for filling of tank ( from owner 1day) 1 day
Required Capacity for Water /time 913.06 m3
Required for firefighting 284 m3
Capacity of Ground Tank 1197 m3
GROUND TANK Vakue Unit
NO.of Partitions of tank 2.00 Partitions
Length of tank 18.00 m
Width of partition of tank 9.00 m
Water Depth 3.7 m
Free Board 0.5 m
Total Tank Depth 4.2 m
Depth of water Capacity (Upper) 2.8 m
Depth of water Capacity (Lower) 0.9 m
5- CALCULATION OF WATER & FIREFIGHTING TANK Vakue Unit
Required Min.Residual Pressure for any Tie in Point in Water networks 3 bars
Required Min.Residual Pressure for any Tie in Point in Firefighting networks 9 bars
Required Min.Residual Pressure for any Fire Hydrant in Firefighting networks 6.9 bars
Guide

5 - 7
-----
3 -7% Of Population
Guide
280 0320 L/d ( egypt code 2010)
50 L/d (egypt code 2010 )
16-20 hr
For storage tank
For Water Pump
For Water Pump
Guide
NFPA -Section -14
NFPA -Section -14
---
For Firefighting Pump
NFPA-section 14
For Firefighting Tank

Guide

Guide
code 2010
< 50 m
1/2 of length
3 - 5
0.5m - 1m -code 2010
Guide
2.5 -4 (According to building height & plumping Design )
NFPA (According to internal FF friction losses)
NFPA-Section-14