0% found this document useful (0 votes)
877 views1 page

Daikin Air Cooled Package

This document provides specifications for a line of high static ducted split air conditioning units including: - Nominal cooling capacities range from 80,000 BTU/h to 750,000 BTU/h - Indoor unit dimensions, outdoor unit dimensions, unit weights, pipe sizes, electrical specifications and sound levels are provided for each model - Multiple outdoor units can be used for larger indoor units to achieve higher nominal cooling capacities

Uploaded by

Jeghi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
877 views1 page

Daikin Air Cooled Package

This document provides specifications for a line of high static ducted split air conditioning units including: - Nominal cooling capacities range from 80,000 BTU/h to 750,000 BTU/h - Indoor unit dimensions, outdoor unit dimensions, unit weights, pipe sizes, electrical specifications and sound levels are provided for each model - Multiple outdoor units can be used for larger indoor units to achieve higher nominal cooling capacities

Uploaded by

Jeghi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1



INDOOR UNIT FBHN80HBV1X FBHN100HBV1X FBHN125HBY1C FBHN150HBY1C


MODEL
OUTDOOR UNIT RHN80HMHY1X RVN100HMHY1C RVN125HMHY1C RVN150HMHY1C
Btu/hr 80,000 100,000 125,000 150,000
NOMINAL COOLING CAPACITY
W 23,447 29,308 36,635 43,962
NOMINAL TOTAL INPUT POWER W 7,100 10,000 11,350 14,800
NOMINAL RUNNING CURRENT - 1ø[3ø] A [12.5] [17.1] [19.7] [28.7]
EER Btu/hr / W 11.27 10.00 11.01 10.14
POWER SOURCE V/Ph/Hz 380-415 / 3 /50
REFRIGERANT TYPE/ CONTROL R410A / INDOOR TXV + CAPTUBE
EXTERNAL STATIC PRESSURE (W/O FILTER) Pa (in.wg) 145 / 0.58 175 / 0.7 200 / 0.8 200 / 0.8
AIR FLOW l/s / CFM 1,086 / 2,300 1,416 / 3,000 1,770 / 3,750 2,124 / 4,500
SOUND PRESSURE LEVEL
dBA 52 55 53 56
(MEASURED IN SOUND ROOM)
UNIT DIMENSION - INDOOR UNIT mm 553 x 1402 x 605 776 x 1,540 x 850
HxWxD OUTDOOR UNIT mm 929 x 1235 x 496 1,067 x 880 x 880 1,067 x 980 x 980 1,166 x 980 x 980
INDOOR UNIT 83 84 159
UNIT WEIGHT kg
OUTDOOR UNIT 111 135 157 177
LIQUID mm/in 12.7 / 1/2 12.7 / 1/2 12.7 / 1/2 15.88 / 5/8
COPPER PIPE SIZE
GAS mm/in 22.23 / 7/8 25.4 / 1.0 28.58 / 1-1/8 34.93 / 1-3/8

INDOOR UNIT FBVN200H2BY1C FBVN250H2BY1C FBVN300H2BY1C FBVN300H3BY1C FBVN350H3BY1C


MODEL
OUTDOOR UNIT RVN100HMHY1C X 2 RVN125HMHY1C X 2 RVN150HMHY1C X 2 RVN100HMHY1C X 3 RVN100HMHY1C RVN125HMHY1C X 2
Btu/hr 200,000 250,000 300,000 300,000 350,000
NOMINAL COOLING CAPACITY
W 58,617 73,271 87,925 87,925 102,579
NOMINAL TOTAL INPUT POWER W 19,700 23,880 30,520 29,710 34,550
NOMINAL RUNNING CURRENT- 1ø [3ø] A [35.1] [40.6] [58.7] [52.60] [60.4]
EER Btu/hr / W 10.15 10.47 9.83 10.10 10.13
POWER SOURCE V/Ph/Hz 380-415 / 3 /50
REFRIGERANT TYPE/ CONTROL R410A / INDOOR TXV + CAPTUBE
EXTERNAL STATIC PRESSURE (W/O FILTER) Pa (in.wg) 225 / 0.9 300 / 1.2 300 / 1.2 300 / 1.2 300/ 1.2
AIR FLOW l/s / CFM 2,832 / 6,000 3,540 / 7,500 4,248 / 9,000 4,248 / 9,000 4,956 / 10,500
SOUND PRESSURE LEVEL
dBA 61 63 66 66 66
(MEASURED IN SOUND ROOM)
UNIT DIMENSION - INDOOR UNIT mm 885 x 1,794 x 850 1,231 x 1,766 x 1,069 1,486 x 2,022 x 1,069
HxWxD OUTDOOR UNIT mm (1,067 x 880 x 880) x 2 (1,067 x 980 x 980) x 2 (1,166 x 980 x 980) x 2 (1,067 x 880 x 880) x 3 1,067 x 880 x 880 (1,067 x 980 x 980) x 2
INDOOR UNIT 196 323 337 337 431
UNIT WEIGHT kg
OUTDOOR UNIT 135 x 2 157 x 2 177 x 2 135 x 3 135 157 x 2
LIQUID mm/in 12.7 / 1/2 12.7 / 1/2 15.88 / 5/8 12.7 / 1/2 12.7 / 1/2 12.7 / 1/2
COPPER PIPE SIZE
GAS mm/in 25.4 / 1.0 28.58 / 1-1/8 34.93 / 1-3/8 25.4/ 1.0 25.4 / 1.0 28.58 / 1-1/8

INDOOR UNIT FBVN400H4BY1C FBVN450H3BY1C FBVN500H4BY1C FBVN600H4BY1X FBVN750H5BY1X


MODEL OUTDOOR UNIT RVN100HMHY1C X 4 RVN150HMHY1C X 3 RVN125HMHY1C X 4 RVN150HMHY1C X 4 RVN150HMHY1C X 5
Btu/hr 400,000 450,000 500,000 600,000 750,000
NOMINAL COOLING CAPACITY
W 117,233 131,887 146,542 175,850 219,812
NOMINAL TOTAL INPUT POWER W 39,330 45,930 49,990 61,620 78,640
NOMINAL RUNNING CURRENT- 1ø [3ø] A [70.2] [89.3] [85.6] [118.9] [152.1]
EER Btu/hr / W 10.17 9.80 10.00 9.74 9.54
POWER SOURCE V/Ph/Hz 380-415 / 3 /50
REFRIGERANT TYPE/ CONTROL R410A / INDOOR TXV + CAPTUBE
EXTERNAL STATIC PRESSURE (W/O FILTER) Pa (in.wg) 310 / 1.24 330 / 1.32 390 / 1.56 390 / 1.56 430 / 1.72
AIR FLOW l/s / CFM 5,664 / 12,000 6,372 / 13,500 7,080 / 15,000 8,496 / 18,000 10,620 / 22,500
SOUND PRESSURE LEVEL
dBA 66 68 68 70 71
(MEASURED IN SOUND ROOM)
UNIT DIMENSION - INDOOR UNIT mm 1,486 x 2,174 x 1,336 1,918 x 2,174 x 1,775 2,197 x 2,174 x 1,775
HxWxD OUTDOOR UNIT mm (1,067 x 880 x 880) x 4 (1,166 x 980 x 980) x 3 (1,067 x 980 x 980) x 4 (1,166 x 980 x 980) x 4 (1,166 x 980 x 980) x 5
INDOOR UNIT 488 533 580 899 946
UNIT WEIGHT kg
OUTDOOR UNIT 135 x 4 177 x 3 157 x 4 177 x 4 177 x 5
LIQUID mm/in 12.7 / 1/2 15.88 / 5/8 12.7 / 1/2 15.88 / 5/8 15.88 / 5/8
COPPER PIPE SIZE
GAS mm/in 25.4 / 1.0 34.93 / 1-3/8 28.58 / 1-1/8 34.93 / 1-3/8 34.93 / 1-3/8



 


