0% found this document useful (0 votes)
64 views8 pages

Technical Data: Technical Data Oi/En Td/C12 Pacis Operator Interface

This document describes the technical requirements and capabilities of the PACiS Operator Interface software package. It outlines that the minimum PC requirements are a Pentium IV 2.4 GHz computer with 1024 MB RAM running Windows 2000 or XP. It also lists the requirements for printers, remote access, smart card readers, SQL server and Crystal Reports. Finally, it provides the maximum authorized numbers of components that can be connected including clients, printers, equipment, switches and data points.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views8 pages

Technical Data: Technical Data Oi/En Td/C12 Pacis Operator Interface

This document describes the technical requirements and capabilities of the PACiS Operator Interface software package. It outlines that the minimum PC requirements are a Pentium IV 2.4 GHz computer with 1024 MB RAM running Windows 2000 or XP. It also lists the requirements for printers, remote access, smart card readers, SQL server and Crystal Reports. Finally, it provides the maximum authorized numbers of components that can be connected including clients, printers, equipment, switches and data points.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Technical Data OI/EN TD/C12

PACiS Operator Interface

TECHNICAL DATA
Technical Data OI/EN TD/C12

PACiS Operator Interface Page 1/6

CONTENT

1. SCOPE OF THE DOCUMENT 3

2. REQUIREMENTS 4
2.1 PC 4
2.2 Printers 4
2.3 Remote Access 4
2.4 Smart Card Reader 4
2.5 Microsoft SQL 2000 Server 4
2.6 Crystal Reports 4

3. CAPABILITIES 5
OI/EN TD/C12 Technical Data

Page 2/6 PACiS Operator Interface

BLANK PAGE
Technical Data OI/EN TD/C12

PACiS Operator Interface Page 3/6

1. SCOPE OF THE DOCUMENT


This document is a chapter of the PACiS Operator Interface (OI) equipment documentation
binder. It describes the Technical Data (OI/EN TD) of this product.
PACiS OI is a software package installed on an industrial or laptop PC to increase
environmental capabilities. Technical characteristics of this PC are described thereafter.
OI/EN TD/C12 Technical Data

Page 4/6 PACiS Operator Interface

2. REQUIREMENTS
The following tables give the minimum hardware requirements to run correctly PACiS OI
application.
2.1 PC

PACiS OI Server & PACiS OI Client


Type of PC Standard desktop with Pentium IV 2.4 GHz minimum
RAM 1024 MB RAM
Hard Disk 40 GB - FT32 format – 7200 rmp
CD-ROM Reader
Operating System Windows 2000 Professional current SP according to the language
Windows XP Pro current SP according to the language
Graphical VGA screen 256 colours minimum, resolution 1024*768
Ethernet Ethernet port (100 Mb)

2.2 Printers
Three types of printers are available:

⇒ The SOE printers (Sequence Of Event)

⇒ The LB printers (Log Book)

⇒ The HC printers (Hard-Copy)


The SOE and LB printers are 132 column printers, the available printer is LEXMARK 2491.
All types of graphic printer are available for Hard-Copy.
PACIS OI doesn't support EPSON printers.
For LEXMARK printers, page code 1004 has to be selected to print marked characters.
2.3 Remote Access
PACIS OI Client can be on all type of remote PC.
2.4 Smart Card Reader
Licence Calyx SSO, from Calyx NetSecure company, with smart card reader (external USB
reader, keyboard with card reader).
2.5 Microsoft SQL 2000 Server
PACiS OI requires Microsoft SQL 2000 Personal Edition Rel 8.00.194 English Version with
Service Pack 1.
2.6 Crystal Reports
Only in case of reports customisation: Crystal Reports v8 or v10.
Otherwise, it is not required to install Crystal Reports on PACiS OI.
Technical Data OI/EN TD/C12

PACiS Operator Interface Page 5/6

3. CAPABILITIES
Component Maximum authorised
OI client 8
OI server 1+ 1 redundant
Printers at OI level 4 (* 2 if redundant)
Station Bus equipment (computers and IEDs) 96
Ethernet MiCOM switches 127
Site 1
Substation 1
Voltage level 4 if ATCC used
Bays 256
Circuit breakers 256
Disconnectors 1024
Transformers 256
Digital Input Points 8192
Output Control Points 2048
Measurements 2048
Tap Position Indication 256
Counters 256
Setpoint (digital or analogue) 512
Animated objects in one OI mimic 128
OI/EN TD/C12 Technical Data

Page 6/6 PACiS Operator Interface

BLANK PAGE